Delta COA02
Delta COA02 – CANopen Slave Communication Module
The Delta COA02 connects a serial device to a CANopen network as a slave node. On the serial side, the selected profile determines how it communicates with a Delta DVP PLC, an AC motor drive, a DTA/DTB temperature controller, an ASDA-A servo drive or a DOP-A operator panel. A custom equipment profile can connect suitable Modbus RTU devices.
CANopen connection and power supply
The module supports CANopen DS301 v4.02. PDOs exchange process data, while SDOs provide access to object dictionary parameters. Eight CANopen bit rates are available from 10 kbit/s to 1 Mbit/s. The five-pin removable connector is wired as 1 V−, 2 CAN_L, 3 SHIELD, 4 CAN_H, 5 V+. Delta specifies a supply range of 11–25 V DC across V+ and V−. When using a nominal 24 V DC power supply, keep its output within that range. Use a suitable CANopen cable for CAN_H and CAN_L and connect the shield according to the panel’s grounding arrangement.
PORT1 and PORT2 pin assignments
PORT1 is an RJ-12 RS-485 port using pin 2 GND, pin 3 DATA− and pin 4 DATA+. The male DB9 PORT2 supports RS-232 or RS-485, depending on the selected mode. For RS-232, use pin 2 RXD, pin 3 TXD and pin 5 GND. For RS-485, use pin 3 DATA− and pin 8 DATA+.
Delta specifies DVPACAB215 and DVPACAB230 as RS-232 cable options for a compatible DVP PLC. This connection runs from the COA02 DB9 port to the PLC’s eight-pin mini-DIN serial port. When selecting a Delta PLC cable, check the COA02-to-PLC serial connection and the PC-to-PLC programming connection separately.
Node ID, DIP switches and software
The ID_H and ID_L rotary switches set a hexadecimal CANopen node ID from 01 to 7F. For example, set ID_H to 1 and ID_L to A for node 26. On SW3, switches 1–3 select the equipment profile, 4–5 select the serial interface and 6–8 set the CANopen bit rate. Cycle power after changing these settings.
For the DVP PLC profile, Delta’s default example uses serial station 1, 115,200 bit/s and 7E1 ASCII. The custom equipment profile defaults to 19,200 bit/s, 8N2 RTU. The CANopen node ID and serial station number are separate settings. Match the bit rate, parity, stop bits and protocol at both ends of the serial link.
Configure the network through the CANopen master. For example, with a DVPCOPM-SL master, use CANopen Builder to configure the network and PDO mapping. Download the DVP PLC program directly to its CPU using a compatible version of WPLSoft or ISPSoft. Use COMMGR for the ISPSoft connection where applicable.
Editor’s Note
When buying a used unit, check that the five-pin CANopen plug is present. Inspect the DB9 pins and the node ID rotary switches.
Before removing the old module, photograph the ID_H, ID_L and SW3 positions. Record the serial device’s station address and communication format as well.
RUN and ERROR show CANopen status. SCAN shows the serial device connection. If RUN is solid green while SCAN is red, check the serial cable, equipment profile and device port settings.
A flashing green RUN LED can indicate that the node is pre-operational. Check the NMT state and node configuration at the master.
On the bench, start by reading a status value from the serial device. Confirm that the master sees the same value before testing write commands under controlled conditions.
Related communication products
The DNA02 is a DeviceNet slave gateway. The DVPCOPM-SL can serve as a CANopen master. The DVPCP02-H2 is a CANopen card for the DVP-EH2 series. The DVP-ES2 CANopen range includes CPU models with CANopen connectivity.
Manual and wiring diagram
Chapter 13 of the DVP-PLC Application Manual for Special Modules covers COA02 wiring, DIP switch settings and the object dictionary. For series documentation, see Delta DVP PLC files.
Delta COA02 · Specialty communication modules · DVP expansion modules · Used Delta PLC models · Delta Automation