Delta UC-CMC050-01A is a 5-metre preassembled CANopen communication cable with RJ45 connectors at both ends. It completes the network connection between a compatible controller and drive. Check the cable code, the function of both device ports and the actual cable route together.

Applications in the manufacturer's guide

Delta's cable guide lists UC-CMC050-01A for the Delta DVP10MC11T in the Delta DVP-MC family using CANopen. The same guide also shows this cable with Delta AH20MC-5A using DMCNET. Verify the exact drive model and its network option against the drive documentation.

The cable carries signals; the connected device ports determine the network protocol. Listing the same cable for CANopen and DMCNET does not make it a converter between those networks. An RJ45 connector alone does not establish Ethernet or EtherCAT compatibility. Compare the separate cable group under Delta EtherCAT cables.

CANopen pin functions

The manufacturer's Figure 1 identifies pin 1: CAN+, pin 2: CAN−, pins 3 and 7: CAN_GND and pin 6: CAN_SHLD. Pins 4, 5 and 8 are marked “—” in its CANopen table. Read pin numbers together with the connector viewing direction; do not use unassigned contacts as supply connections.

The DMCNET section of the same drawing assigns 1/2: D1+/D1−, 3/6: D2+/D2− and 7/8: DMCNET_GND. Do not transfer CANopen signal names directly to a DMCNET port. Review connectors and distribution components separately under Delta network connectors.

Selecting length within the UC-CMC family

Shorter options are listed as UC-CMC003-01A at 0.3 m, UC-CMC005-01A at 0.5 m, UC-CMC010-01A at 1 m, UC-CMC015-01A at 1.5 m, UC-CMC020-01A at 2 m and UC-CMC030-01A at 3 m.

Beyond the 5 m UC-CMC050-01A, longer options are UC-CMC100-01A at 10 m and UC-CMC200-01A at 20 m. These values describe individual cable lengths. Assess the permitted length of the complete CANopen network separately against its bit rate, trunk and branch arrangement.

Cable routing and network settings

Include duct turns and service access when planning the 5-metre route. Keep pulling forces off RJ45 latches and avoid crushing the cable beneath covers or against duct edges. Do not bundle it tightly with motor and drive power wiring.

Check the physical ends of the CANopen bus and active termination against the device drawings. For distribution components such as Delta TAP-CN03, use the component's own port and termination documentation. Verify addresses, bit rate and device configuration independently of the cable.

Use the Delta CANopen Builder page in the context of supported controller and network-module configuration. UC-CMC050-01A does not require a separate cable driver; project and network settings are handled through the tools for the connected hardware.

PDF and connection documentation

Start document selection at Delta PLC accessories files. In the PLC/HMI Cable Selection Guide, printed page 3-7 / PDF page 148 provides the application table, and Figure 1, printed page 3-9 / PDF page 150 shows connectors and pin functions. Printed page 49 / PDF page 50 of the 2023 DVP/TP catalogue provides UC-CMC cable lengths.

Editor's Note

Record which ports the cable actually connects. Photograph both device models, port labels and the cable marking. Adjacent RJ45 sockets should not be assumed to perform the same function.

Inspect latches and connector exits on a used cable. Look for broken latches, crushed insulation and replacement plugs. Disconnect using the connector housing rather than pulling on the cable, and check that each plug seats fully.

Test continuity with both ends disconnected from equipment. Follow pin numbers and viewing direction in the manufacturer's drawing. A continuity beep alone does not establish reliable communication under operating conditions.

If the fault began after a bit-rate change or an added station, inspect that change first. Check addresses, speed settings, physical bus ends and termination together. Use a systematic diagnosis before replacing parts.

Complete the final test under the machine's operating conditions. Observe that all nodes remain online and communication error counters do not increase. Record the tested route and cable code in the maintenance log.

Related topics

Browse parent groups under Delta CANopen cables and Delta PLC accessories, and device documentation under Delta PLC and HMI manuals.

External references: Delta PLC/HMI Cable Selection Guide — 2019, English · Delta DVP/TP manufacturer catalogue — 2023, English.