Delta AS08AN01T-A

Delta AS08AN01T-A 8-channel NPN digital output module

The Delta AS08AN01T-A is a PLC expansion module with 8 NPN transistor outputs in the Delta AS digital module range. It switches suitable DC loads such as panel indicators, interposing relay coils and solenoid valves. The 0–7 markings identify the physical outputs.

Load supply, current limits and C0

The output circuit uses a 5–30 V DC load supply. Delta specifies 0.5 A per channel and 4 A total for the C0 group. An active NPN sinking output provides a return path to 0 V. Delta’s diagram connects both C0 terminals to the same 0 V common. Connect the load between the positive DC supply and the selected output.

The spring-clamp terminal block is removable. Internal power consumption is 0.72 W. Include the module’s internal consumption when sizing the AS power supply, and account for coil and indicator currents when sizing the field supply. Check the rated capacity of an AS-PS02 or AS-PS02A when planning the panel.

PLC connection and Y addresses

The module installs on the AS expansion bus to the right of a compatible CPU such as an AS200 or AS300. Connect the computer to the CPU with a Mini USB data cable or over Ethernet. After setting up COMMGR, check the model and module order in HWCONFIG in ISPSoft.

HWCONFIG assigns a 16-bit Y address block to each 08AN module. Use the project’s starting Y address when testing physical outputs. If the module order changes, check the PLC program and HMI output mapping.

Model selection

The AS08AN01P-A provides eight PNP outputs, the AS08AN01R-A provides eight relay outputs, and the AS16AN01T-A provides 16 NPN outputs. For eight digital inputs, see the AS08AM10N-A. For input channels and NPN outputs in one module, see the AS16AP11T-A.

Editor’s Note

On a used unit, check the full AS08AN01T-A nameplate code alongside the 08AN front marking.

With power off, inspect the terminal block and C0 connections for loose or discoloured terminals.

On the bench, test one output first with a current-limited DC supply and a suitable load.

If the OUT LED is on and the load stays off, measure the load supply and the C0 return.

Before replacement, record the module position and starting Y address in HWCONFIG.