Delta AS32AM10N-A
Delta AS32AM10N-A 32-Point Digital Input Module
The Delta AS32AM10N-A is an AS expansion module with 32 digital inputs rated at 24 V DC for compatible AS200 and AS300 PLCs. Field signals connect through a 40-pin MIL connector.
PNP and NPN input wiring
Delta’s model wiring diagram specifies 24 V DC, 4.2 mA per input. The inputs accept 24 V DC contact signals and PNP or NPN inductive sensors when the S/S common is wired accordingly. Check the manual diagram for the sensor type and field supply used in the panel.
MIL cable, terminal and addressing
Use a UB-10-ID32A terminal with a UC-ET010-24B (1 m), UC-ET020-24B (2 m) or UC-ET030-24B (3 m) cable. The terminal has DVP markings. Use Delta’s AS terminal mapping when wiring it to this module. See the Delta PLC accessory PDF archive for external terminal and cable selection.
The module has two 16-input groups labelled X0 and X1. The LED selector chooses which group appears on the front panel. Confirm the project’s actual input addresses in ISPSoft HWCONFIG. Connect the PC through COMMGR using Ethernet or the programming cable supported by the CPU.
Related models
The AS08AM10N-A, AS16AM10N-A and AS64AM10N-A have 8, 16 and 64 digital inputs respectively. The AS32AM10N-B is the 32-input version with spring-clamp terminals. The AS32AN02T-A provides 32 NPN transistor outputs.
Editor’s Note
On a used module, check the -A suffix and look for bent MIL pins.
Check the part numbers on the cable and field terminal as well.
If some inputs appear missing, check the X0/X1 LED selector first.
If an entire group fails to respond, check its S/S common and cable continuity.
Isolate power before removal. Start testing in a safe state with one sensor and one input.
Related topics · Analog vs. digital inputs · What is a DIN rail?
More Delta pages · AS expansion modules · Delta AS PLC series
External references · AS module manual, §2.4.12 (EN) · AS hardware and operation manual (EN)