Delta AS08AN01R-A 8-channel relay output module

The Delta AS08AN01R-A is a PLC expansion module with 8 relay outputs in the Delta AS digital module range. The contacts switch suitable panel indicators, interposing relay coils and other control loads. The 0–7 markings identify the physical outputs.

Contact ratings and C0 wiring

The Delta AS hardware manual specifies a load voltage of 10–240 V AC or 5–24 V DC. For resistive loads, the limits are 2 A per output and 8 A total for C0. Add the currents of loads that operate at the same time. For inductive loads such as coils, use the contact life curve. The manual lists maximum switching rates of 1 Hz for resistive loads and 0.5 Hz for inductive loads.

The two C0 terminals on the removable spring-clamp block share the same common. Each relay contact connects its output to that common. Use separate output groups for separate AC and DC load circuits. Include the module’s 1.7 W internal consumption when sizing the AS power supply. When selecting an AS-PS02 or AS-PS02A, size the module bus and field load supplies separately.

PLC connection and Y addresses

The module installs on the AS expansion bus to the right of a compatible CPU such as an AS200 or AS300. Connect the computer to the CPU with a Mini USB data cable or over Ethernet. After setting up COMMGR, check the module order and starting Y address in HWCONFIG in ISPSoft.

HWCONFIG allocates a 16-bit Y address block to each 08AN module. Use the project’s starting address to check the mapping for terminals 0–7. If the module order changes, review the PLC and HMI output mappings.

Model selection

The AS08AN01T-A provides eight NPN transistor outputs and the AS08AN01P-A provides eight PNP transistor outputs. See the difference between NPN and PNP when choosing an output circuit. For 16 relay outputs, see the AS16AN01R-A. For digital inputs and relay outputs in one module, see the AS16AP11R-A. For eight digital inputs, see the AS08AM10N-A.

Editor’s Note

On a used unit, verify the full AS08AN01R-A nameplate code alongside the 08AN front marking.

With power off, inspect the C0 terminals and removable block for looseness, discoloration or damage.

On the bench, test one output first with a current-limited 24 V DC supply and a suitable load.

If the relay clicks and the load stays off, check contact closure and load voltage separately.

Before replacement, record the module position, starting Y address and loads connected to the C0 group.

Related topics

Delta AS PLC series · Delta PLC models · Delta PLC and HMI manuals

External references

AS08AN01R-A instruction sheet (TR/EN PDF) · AS series hardware and operation manual (EN PDF)

The instruction sheet states 250 V AC / 30 V DC. The load voltage ranges on this page follow the model table in the 2024 hardware manual.