Delta AH32AN02T-5A
Delta AH32AN02T-5A 32-Point NPN Transistor Output Module
Delta AH32AN02T-5A is a digital output module with 32 NPN sinking outputs for Delta AH500 rack-based PLC systems. Field wiring connects to a removable front terminal block. The module switches compatible control inputs and low-current DC loads under PLC control.
Wiring diagram and manual
AH32AN02T-5A wiring diagram (PDF, English) · Printed page 4-45 of the AH500 Hardware & Operation Manual. See page 2-31 for electrical limits and page 5-13 for ISPSoft addressing.
Output current and terminal layout
The model-specific wiring diagram shows 12–24 V DC. For resistive loads, the limits are 100 mA per output and 1 A per common. Account for both limits when adding up the current of outputs that can be on at the same time.
The terminal block labels the two output groups 0.0–0.15 and 1.0–1.15. Check the model wiring diagram for the 24 V DC auxiliary supply connections at UP/ZP. An NPN output sinks load current toward 0 V when it switches on. For coil loads, use a suitable interposing relay or driver interface and select suppression to suit the load circuit.
5A, 5B and 5C versions
The AH32AN02T-5A has a removable terminal block. The AH32AN02T-5B uses DB37 and the AH32AN02T-5C uses a latch connector. The 32-point PNP sourcing version with a terminal block is the AH32AN02P-5A.
ISPSoft and Y addresses
Check the module slot and start address in HWCONFIG in ISPSoft. The module occupies 32 Y bits. With a start address of Y0.0, the groups are Y0.0–Y0.15 and Y1.0–Y1.15. Check the port supported by the CPU and the COMMGR profile for the PC connection. See the Delta PLC software section for setup information.
Editor’s note
When buying a used module, check the full AH32AN02T-5A code on the label and make sure the front terminal block is included.
Inspect the terminal latch, screw threads and rear rack connector. A discoloured UP or ZP terminal is a reason to check what loads the group previously switched.
On the bench, use a suitable low-current test load and check all 32 outputs one at a time. Watch the LED and the load response together.
If several outputs in one group fail to respond, start with that group’s UP/ZP supply and terminal contact.
If the LED turns on and the load stays off, check the load current, common terminal and Y address before replacing the module.
Related topics
16-point options include the AH16AN01T-5A NPN output, AH16AN01P-5A PNP output and AH16AN01R-5A relay output. For more NPN outputs, see the AH64AN02T-5C. For 32 digital inputs, see the AH32AM10N-5A.
For rack planning, see AH expansion modules, Delta PLC accessories and AH power supplies.
Browse · Delta Automation · Delta PLC · Delta AH PLC series