Delta AH32AN02P-5C

Delta AH32AN02P-5C 32-channel PNP digital output module

The Delta AH32AN02P-5C is a 32-channel PNP sourcing transistor output module for the Delta AH500 system. Its catalog rating is 12–24 V DC and 0.1 A per channel for resistive loads. Field wiring uses a 40-pin MIL connector. It belongs to the AH digital module family.

Output type and current limits

When a PNP output turns on, it supplies positive voltage to the load. The load returns to 0 V. Delta specifies 0.1 A per output and 1 A per common group for resistive loads. Add up the currents of the outputs that will be on at the same time in each group. The manual specifies a 24 V DC auxiliary supply at UP/ZP.

MIL cable and external terminal selection

To bring the transistor outputs to a terminal block, use a 40-to-40-pin UC-ET010-24A cable with the UB-10-OT32A.

For relay contacts, use a UC-ET010-24C or UC-ET010-24D cable that splits one 40-pin connector into two 20-pin connectors, with UB-10-OR16B blocks. Two 16-channel relay blocks cover all 32 outputs. Compare part numbers on the AH I/O cables and AH external terminals pages.

Output addressing in ISPSoft

HWCONFIG in ISPSoft assigns the module a 32-bit Y output range. For a start address of Y0.0, that range is Y0.0–Y0.15 and Y1.0–Y1.15. Check the actual start address in the existing project. For PC communications, see COMMGR and Delta PLC software.

Manual and wiring diagram

AH32AN02P-5C wiring diagram (PDF, English) · Section 4.7.19 of the AH500 Hardware and Operation Manual covers the module and its external terminals.

All Delta AH PLC PDF files

Editor’s Note

When buying a used unit, ask for a photo of the complete nameplate. The P-5C suffix identifies both the output type and the connector.

Inspect the 40-pin socket for bent pins, a broken latch or signs of overheating.

If the cable and terminal block are included, check both labels. The UB-10-OT32A and UB-10-OR16B serve different wiring arrangements.

If a channel LED turns on but there is no output voltage, first check the UP/ZP auxiliary supply and the load’s 0 V return.

On the bench, use a known resistive load to test outputs from both 16-channel groups and record the results.

Related models and topics

AH32AN02P-5A PNP with removable terminals · AH32AN02P-5B PNP with DB37 · AH32AN02T-5C NPN with MIL · AH64AN02P-5C 64-channel PNP.

For Derell DLC systems, see the Derell EXLC-1410-R-A digital I/O module.

Delta AH PLC series · AH expansion modules · AH power supplies · Delta PLC

External reference · Delta PLC/HMI Cable Selection Guide · Section 2.2.7.