Delta AH08DA-5B

Delta AH08DA-5B 8-channel analog voltage output module

The Delta AH08DA-5B is an 8-channel, 16-bit analog voltage output module for the Delta AH500 PLC. Each channel can be set to 0–5 V, 1–5 V, ±5 V, 0–10 V or ±10 V. Conversion takes 150 µs per channel, and field wiring uses a removable JIS terminal block. It belongs to the Delta AH analog module family.

The module converts a digital PLC command into a drive speed reference, a proportional valve command or a voltage signal for a recorder. For example, when using a 0–10 V frequency reference with a Delta VFD-EL, check both the PLC output range and the drive’s analog input setting.

Power supply and field wiring

VO0–VO7 are the voltage outputs, AG is the analog common and SG is the shield connection. The external supply at UP/ZP is rated at 24 V DC, with an allowable range of 20.4–28.8 V DC. Check the receiving device’s input impedance against the selected range. The manual specifies 1 kΩ–2 MΩ for the 0–10 V and ±10 V ranges.

The analog circuitry is isolated from the digital circuitry. The analog channels share a reference. Delta’s wiring diagram shows shielded signal cable routed separately from power cables. For panel components, see AH power supplies and Delta PLC accessories.

ISPSoft configuration and output addressing

Use HWCONFIG in ISPSoft to check the module slot and channel ranges. Each channel occupies two registers, so the eight channels use 16 output registers. Read the assigned start address from the project. For PC connections, see COMMGR, Delta PLC software and programming cables.

Manual and wiring diagram

AH08DA-5B wiring diagram (PDF, English) · Section 4.9.5 of the AH500 Hardware and Operation Manual shows the VO, AG, SG and UP/ZP connections.

All Delta AH PLC PDF files

Editor’s Note

When buying a used unit, ask for a photo of the full nameplate. The DA-5B provides voltage outputs, while the DA-5C provides current outputs.

Check that the removable terminal block is included and that its latch is intact.

If there is no output, check the UP/ZP supply, the AG reference and the ISPSoft channel setting before diagnosing a failed channel.

On the bench, test a channel set to 0–10 V with 0, 5 and 10 V commands. Measure between the corresponding VO terminal and AG.

Before replacing the module, back up the channel ranges, scaling settings and start register with the PLC project.

Related models and topics

AH08DA-5A eight voltage or current outputs · AH08DA-5C eight current outputs · AH04DA-5A four analog outputs · AH06XA-5A four analog inputs and two analog outputs.

For reading voltage signals into the PLC, see the AH08AD-5B analog input module. For a standalone panel-mounted 0–10 V reference, see the Derell DTPV-37 electronic potentiometer.

Delta AH PLC series · AH expansion modules · Delta PLC · Delta Automation

External reference · Delta AH500 Module Manual · Chapter 3 covers analog output settings.