Delta AH08AD-5B

Delta AH08AD-5B 8-Channel Analog Voltage Input Module

The Delta AH08AD-5B is an eight-channel analog voltage input module for the Delta AH500 PLC. It converts signals from position sensors, voltage-output pressure transmitters and drive feedback into values the PLC can read. See the Delta AH analog modules.

Model selection. The AH08AD-5B accepts voltage inputs. The AH08AD-5A supports voltage and current inputs, while the AH08AD-5C handles current signals such as 4–20 mA. See the AH04AD-5A for four inputs or the AH06XA-5A for four inputs and two outputs.

Wiring diagram and user manual

AH08AD-5B wiring diagram (PDF) · English. PDF page 239, printed page 4-69. Shows the first and last voltage input channels and the shield connection.

AH08AD-5B ISPSoft channel modes (PDF) · English. PDF page 54, printed page 2-28. The input mode table is on this page and the scaling settings follow on the next page. All Delta AH PLC PDF files.

Specifications and terminal wiring

Voltage ranges. Set each channel individually to −10 to +10 V, 0 to 10 V, −5 to +5 V, 0 to 5 V or 1 to 5 V. Hardware resolution is 16 bits, conversion time is 150 µs per channel and voltage input impedance is above 1 MΩ. The nominal supply is 24 V DC, with a specified supply range of 20.4 to 28.8 V DC. See AH expansion modules and AH power supplies for rack and supply selection.

Removable terminal block. For CH0, connect the signal to V0+ and its return to V0−. For CH7, the corresponding terminals are V7+ and V7−. SLD is the shield connection. Follow the grounding arrangement in the manual and route analog signal cables separately from motor and power cables. The analog circuit is isolated from the digital circuit. The analog channels share a non-isolated circuit, so check the signal references when using separate field supplies.

ISPSoft, channel modes and scaling

In ISPSoft, open the channel under HWCONFIG → Parameter Setting. Mode 0 disables the channel. Mode 1 selects ±10 V, 2 selects 0–10 V, 3 selects ±5 V, 4 selects 0–5 V and 5 selects 1–5 V. For example, for a 0–10 bar transmitter with a 0–10 V output, select mode 2 and set the channel scale to 0–10 bar. On a linear transmitter, 5 V represents approximately 5 bar.

PLC addressing. Each measured value uses two consecutive 16-bit D registers in REAL format. The eight channels occupy 16 D registers. If the HWCONFIG start address is D200, CH0 uses D200–D201, CH1 uses D202–D203 and CH7 uses D214–D215. For the PC-to-CPU connection, see COMMGR and Delta PLC software.

Editor’s Note

When buying a used module, check the full AH08AD-5B nameplate and ask whether the removable terminal block is included.

On the bench, use an adjustable voltage source to test the low, middle and high points of the selected range. Compare the voltage measured at the terminals with the value in ISPSoft.

If a channel always reads zero, check for a signal across V+ and V−. Then check whether the channel is still set to mode 0.

If readings fluctuate, check the cable shield and signal return. When the fluctuation starts as a drive runs, check the analog cable route through the cabinet.

If the PLC reading differs from the field measurement, check the HWCONFIG input range, scaling endpoints and REAL address used in the program.

Related topics

AH08DA-5A voltage and current outputs · AH08DA-5B voltage output · AH08DA-5C current output · AH04PT-5A RTD input.

Delta AH PLC series · Delta PLC accessories · Delta PLC models · Second-hand Delta.

External references

Delta AH500 Hardware and Operation Manual, section 4.9.2 · Delta AH500 Module Manual, section 2.4.6.