Delta ADP485-01
Delta ADP485-01
Delta ADP485-01 is a communication adapter offering four connection formats for linking Delta equipment to an RS-485 network. It supports connection arrangements involving suitable RS-485 ports on DVP PLC, DOP HMI, VFD and ASD families. It is not an I/O expansion module; select it against the complete device model and port diagram.
Connections and pin assignments
Connections comprise COM1: DB9 female, COM2: DB9 male, RJ12 and an RS-485 terminal connection, with 35 mm DIN-rail mounting. COM1 and COM2 have different pin assignments. Consult the application drawing before selecting a straight-through DB9 cable or a simple gender adapter.
Four connection formats should not be treated as four independent communication channels. Do not select ADP485-01 as an RS-232-to-RS-485 converter or a gateway between different protocols. Identify the equipment under Delta DVP PLC series and Delta HMI files; use the relevant device document under Delta manuals for drive ports.
120 Ω termination and line checks
The adapter includes surge absorption, current limiting protection and a selectable 120 Ω termination resistor. The termination switch defaults to OFF. Terminate the network at its two physical ends, rather than enabling termination at every intermediate adapter.
First draw the actual start and end of the line. Adding another device can move a former endpoint into the middle of the network. Account for termination already built into other equipment. Review cable selection alongside Delta DVP communication cables.
Relationship with ADPCAB03A and ADPCAB03B
Delta ADPCAB03A is the 30 cm cable specified for ASD-A / ASDA-A, while Delta ADPCAB03B is specified for ASD-B / ASDA-B. Match the servo side through Delta ASDA-A and Delta ASDA-B. Similar family names do not establish compatibility with A2, B2 or other generations.
Delta DVPACAB403 and Delta DVPACAB4A07 are PLC extension cables and serve a different purpose from the RS-485 connections on ADP485-01. Delta TAP-CN01 belongs to the DeviceNet/CANopen connection group. Their presence in the same accessory section does not establish interchangeability.
Software, backups and documents
Before replacing the adapter, save the PLC project and communication parameters of the connected devices. Select Delta WPLSoft or Delta ISPSoft according to CPU support. Review PC communication tools under Delta COMMGR and Delta PLC software. Software settings cannot correct an incorrectly wired cable.
Start document selection at Delta PLC accessories files. The first PDF page of the 2013-12-15 ADP485-01 Instruction Sheet, 5011679501-DP01, contains port drawings, termination information and cable connections. Check DB9 and RJ12 ends against these drawings.
Product lifecycle: the 2023 PLC and Accessories notice issued by Delta Electronics (Americas) lists ADP485-01 among discontinued products and gives None in the suggested replacement field. This regional notice does not establish another RS-485 adapter as a direct replacement.
Editor's Note
Photograph COM1, COM2 and the switch position before removal. An installation that has operated for years provides a useful starting record. Still check the original connection against the drawing when fitting the replacement.
Do not blame the adapter first when communication stops. Compare station addresses, speed and data format, and check for duplicate addresses. Preserve the working parameters before changing the connection.
Do not enable termination by habit. Identify both line ends and the resistors inside connected devices. An OFF setting on the original adapter can be correct when the line is terminated elsewhere.
Inspect connectors and terminals with power disconnected. Look for bent DB9 contacts, loose screws, cracked RJ12 sockets and crushed cable. A connector that fits does not establish correct internal wiring.
Back up the working arrangement before comparison tests. Starting with one device and the correct cable, then adding connections in order, can help locate a faulty branch. Test cable continuity with both ends disconnected.
Related topics
Review supporting products under Delta DVP other accessories and Delta PLC accessories, and device documentation under Delta PLC and HMI manuals.
External references: ADP485-01 manufacturer instruction sheet — English/Chinese · Delta DVP/TP manufacturer catalogue — 2023 · Delta Electronics (Americas) discontinuation notice — 2023.