Delta COMMGR

Delta COMMGR: communication manager, versions and connections

Delta COMMGR (Communication Manager) is Windows software that manages connections between Delta engineering applications and supported automation devices. While ISPSoft edits PLC logic, COMMGR establishes a serial, USB, Ethernet or supported gateway channel. The PLC editor, Windows USB device driver and network configuration tool have separate roles.

Current installation and update route: obtain the installer from the official Delta DIAInstaller V2 page, then select COMMGR using a DIAStudio account. Delta Turkey’s official support also directs current COMMGR installation through DIAInstaller and account registration. Software downloads remain on Delta’s official service.

V1/V2 and build numbers · Connection options · Connection errors · PDF references

COMMGR V1, V2 and complete build numbers

COMMGR V1 is the 1.x generation found on existing machines and older ISPSoft installations. Manufacturer documents and official support mention V1.00, V1.06.05, V1.09, V1.14 and V1.15. COMMGR V2 is the 2.x generation distributed with DIAStudio. Do not assume identical menus or status behavior across generations; check the engineering application, Windows environment and device together.

Checked on 14 November 2026: the official download-centre title reads COMMGR V2.11, dated 10 November 2025, with a 455 MB multilingual package. The same version is listed under DIAStudio, PLC and AC drives; these three category records do not establish separate editions.

A V2.11 title does not establish that the installed build is V2.11.1. Delta’s advisory dated 6 March 2026 requests V2.11.1 or later for V2.11.0 and earlier. A distributor also lists a package named 2.13.0.9; that filename alone does not establish Delta’s latest official release. Check the complete installed version/build in DIAInstaller and COMMGR version information.

The 2025 manufacturer advisory covers every COMMGR V1 version and V2.9.0/earlier, recommending V2.10.0 or later. The subsequent 2026 correction requirement also applies. An old V1.15 support download entry therefore does not make V1.15 the current general installation recommendation. Plan changes to existing machines alongside the engineering software and project backups.

Which applications and devices use it?

With ISPSoft: its manual documents COMMGR in the communication architecture from ISPSoft V2.00 onward. For supported DVP, AS and AH devices, create the correct COMMGR channel and select it in ISPSoft. This does not mean every old CPU supports every newer interface or protocol.

DIADesigner and other Delta tools: COMMGR supplies the communication layer. The manufacturer’s C2000 Plus EtherNet/IP example uses DIADesigner V1.2.3, COMMGR V2.2.1 and a CMC-EIP02 card. COMMGR V2.2.1 is the version of a historical application example, not a current installation baseline. Preparing a CANopen network in CANopen Builder is a separate task.

WPLSoft distinction: WPLSoft includes its own communication settings, so a separate COMMGR installation is not compulsory for every WPLSoft connection. The CP2000/CFP2000 application describes WPLSoft and ISPSoft+COMMGR separately. Do not infer a COMMGR requirement for PMSoft, TPEditor or another editor from similar product names.

Serial, USB, Ethernet and DirectLink

Serial: match the COM port, bit rate, data bits, parity, stop bits, ASCII/RTU mode and device station address. A visible COM port does not prove that the cable has the correct PLC pinout or electrical interface. Select the Delta programming cable for the exact CPU port.

USB: a COMMGR driver is a communication-channel definition; it does not replace the Windows USB device driver. Check the model-specific USB driver and connection type for AS200, AS300 and applicable AH CPUs. The DVP-SX2 example uses internal USB-to-serial conversion and a serial connection type. A USB socket does not imply one universal COMMGR setting.

Ethernet: select the correct network adapter and target IP for hardware such as DVP-SE, DVPEN01-SL or AH10EN-5A. Check network addressing, duplicate IPs and the actual connection route. Appearing in Search results or responding to ping does not establish every condition required for access to the PLC program.

DirectLink: the PC reaches a PLC through a supported HMI. The HMI’s USB/Ethernet connection, downstream PLC port and bypass capability must all match. Direct USB access to a PLC is different from DirectLink. DIACom or eComm remote access also requires the appropriate software, device and connection; it is not automatically available on every PLC.

Simulators: supported DVP, AH and AS simulators can use virtual COMMGR connections. Match the simulator to the project CPU and start it when required. A running simulation alone cannot validate physical I/O, high-speed counters, analogue measurement, field networks or motion axes.

Establishing an ISPSoft connection

1. Identify the full CPU code and physical port. Confirm the required USB/converter device driver in Windows Device Manager. Preserve the current COMMGR channel settings and project files before changing them.

2. Use Add / New Driver, depending on the version, to create a clearly named channel. Select the actual serial/USB/Ethernet/DirectLink connection and save it. Start/Stop buttons from older screenshots are not mandatory for every connection type; hardware driver status may be detected automatically.

3. In ISPSoft, select that channel under Tools → Communication Settings. Verify the device station address and target IP where applicable. Use a read operation such as PLC → System Information to confirm access to the intended PLC. A COMMGR OK indicator alone is insufficient.

4. Program transfer and online monitoring are separate operations after establishing communication. Upload reads from the PLC to the PC; Download writes from the PC to the PLC. A communication test does not require changing the running program. Make a backup before writing a program or updating firmware.

Common connection errors

“Invalid driver or COMMGR not start up”: confirm that COMMGR is running, the channel is saved and ISPSoft selects the correct channel. Delta EMEA’s note describes recreating drivers, choosing Save All Data and reopening ISPSoft communication settings. Record existing channel settings before deleting configurations used by other machines.

Missing or busy COM port: compare its number in Device Manager. Another terminal, PLC editor or communication manager may hold the same serial port. Moving a USB connection to another socket can change its COM number. In older versions, closing the COMMGR window with X may leave the process running in the background.

Ethernet device not found: verify the selected adapter, PLC IP and cable connection. A VPN or virtual adapter can direct scanning to the wrong interface. Check the relevant application/local-network firewall rule when necessary; permanently disabling all protection is not an installation step.

DIAInstaller “Server connection failed”: check the installer’s own version. The manufacturer transition notice states that DIAInstaller V1 server connections stopped on 1 July 2024. This V1 refers to a different application from COMMGR V1. Use the official V2 installer route and distinguish account/sign-in problems from PLC cabling faults.

Windows and version compatibility

The central COMMGR V2.11 record lists Windows 10 / Windows 11, 64-bit. XP/Windows 7 or 32-bit information from old manuals does not establish support in a current 2.x package. An x86 distributor filename also does not independently establish current 32-bit Windows support. Check the complete package, build, Windows version and engineering editor together.

COMMGR V1, COMMGR V2, DIAInstaller V2, USB device drivers and simulator packages are distinct components. Keep their version numbers separate. Do not assume that multiple generations can be installed together or that every old editor behaves identically without checking the supported combination.

PDF manuals and application documents

The following eight original manufacturer PDFs cover connections, applications and version corrections. A preview of the COMMGR V2.3.0 / DIAS-Manual-0006-EN interface manual dated 2023-11-27 was found, but its original PDF could not be downloaded independently during this research. No prepared local link is provided for that manual. Check the current general software manual through DIAInstaller / Software Manual. EN means English; EN-ZH denotes English and Chinese text.

ISPSoft manual: COMMGR connections and simulator sections — Sections 1.2 and 2.4: installation, driver creation, USB/serial/Ethernet/DirectLink, simulators and ISPSoft connection selection. See PDF 91–110. Historical 2021 interface; not the current COMMGR V2 manual. Language: EN; 2021-03-29; 1160 pages; 32.19 MB.

AS hardware and operation: COMMGR and USB driver — Chapter 3 and appendices: COMMGR with AS hardware, connections and USB drivers. PDF 486 includes an older EtherNet/IP example using COMMGR V1.06.05. Preserves the previous filename and bytes. Language: EN; 2021-02-25; 654 pages; 30.13 MB.

CP2000/CFP2000 application: WPLSoft versus ISPSoft+COMMGR — Section 4.1.1 and PDF 15: built-in drive PLC tools, WPLSoft integrated communication setup and the ISPSoft+COMMGR workflow. Not a general parameter-setting guide for every drive. Language: EN; 2023-09-20; 66 pages; 1.59 MB.

C2000 Plus: DIADesigner and COMMGR EtherNet/IP application — Manufacturer example with C2000+, CMC-EIP02, DIADesigner V1.2.3 and COMMGR V2.2.1. Example versions are historical, not current installation recommendations. Language: EN; 2023-10-25 (source filename; cover: October 2023); 11 pages; 0.92 MB.

DIAInstaller V1 maintenance termination and V2 migration notice — Termination of DIAInstaller V1 server connectivity on 1 July 2024 and transition to V2. This is not a COMMGR V1 end-of-maintenance notice; the two products’ version numbers must remain distinct. Language: EN; 2024-06-06 (source filename); 5 pages; 0.17 MB.

COMMGR V1/V2: 2025 authentication version advisory — Last update inside the PDF: 2025-08-18. Covers all COMMGR V1 versions and V2.9.0/earlier; recommends V2.10.0 or later. Its generic footer number differs from the URL document code. Language: EN-ZH; 2025-08-18 (last update inside PDF); 2 pages; 0.53 MB.

COMMGR V2.9.0 and earlier: separate 2025 correction advisory — Separate advisory dated 2025-08-26, recommending V2.10.0 or later. Read the subsequent 2026 advisory as well. Contains English and Chinese text. Language: EN-ZH; 2025-08-26; 2 pages; 0.50 MB.

COMMGR 2: 2026 advisory requiring V2.11.1 or later — Published/last updated inside PDF: 2026-03-06. Recommends V2.11.1 or later for V2.11.0 and earlier. A V2.11 download title does not establish the complete installed build. Language: EN-ZH; 2026-03-06 (date inside PDF); 2 pages; 0.54 MB.

Editor’s note

A COMMGR OK indicator is not proof of PLC access. It may show that the PC interface is available. Read model or system information from the intended PLC before proceeding; an incorrect IP can lead to a different machine.

Check the cable, Device Manager, COMMGR channel and ISPSoft channel selection before reinstalling everything. Choosing an HMI DirectLink route for a direct AS200 USB connection can make working hardware appear faulty.

A correct COM number is only one condition. Match bit rate, parity, ASCII/RTU mode and station address as well. USB-to-RS232 and USB-to-RS485 converters are different devices; a connector adapter does not change their electrical interface.

For intermittent communication, inspect plugs, USB sockets and converter power. Consider other editors accessing the same port. Record channel settings before deleting a driver so that returning to another machine does not require reconstructing its configuration.

When updating, inspect the complete build and manufacturer correction notice, not only a short 2.11 title. An obsolete installer’s server error is separate from a PLC fault. Verify communication with a small read test after installation, then return to the project.

Preserve the working project and connection details first. Do not press Download while intending to make a backup and write an empty or unrelated project to the PLC. Diagnosing a connection and modifying the running program are separate tasks. Confirm communication before making an intentional write.

Related topics

Delta PLC software · Delta ISPSoft · Delta WPLSoft · Delta PMSoft

Delta CANopen Builder · Delta DCISoft · Delta DeviceNet Builder · Delta TPEditor

Delta device description files · Delta EDS device description files · Delta DVP PLC series · Delta AS PLC series

Delta AH PLC series · Delta DVP-ES3 · Delta DVP-SX2 · Delta DVP-SE

Delta DVP12SE11R · Delta DVP12SE11T · Delta AS200 · Delta AS300

Delta AH500 · Delta DVPEN01-SL · Delta AH10EN-5A · Delta Plc Cables

External references

Official DIAInstaller page · DIAStudio · Official COMMGR download records · Delta Turkey COMMGR support entry

ISPSoft–COMMGR connection example · Invalid driver troubleshooting · AS200 USB versus DirectLink

Current COMMGR installation through DIAInstaller