Danfoss VLT 6000 Fault codes 3

List of Warnings and Alarms

The table below lists the different warnings and alarms for the VLT frequency converter and indicates whether the fault locks the converter. After a Trip lock, the mains supply must be cut off, and the fault must be corrected. Reconnect the mains supply and reset the VLT frequency converter before resuming operation. A Trip can be reset manually in three ways:

+ Via the control key [RESET]
+ Via a digital input
+ Via serial communication

Additionally, an automatic reset may be selected in parameter 400 (Reset function).

A cross placed under both Warning and Alarm indicates that a warning may precede the alarm. It can also mean that it is possible to program whether a given fault results in a warning or an alarm, such as in parameter 117 (Motor thermal protection). After a trip, the motor will coast, and both the alarm and warning will flash on the VLT frequency converter. If the fault is removed, only the alarm will flash. After a reset, the VLT frequency converter will be ready to start operation again.

ALARM 22: Auto-optimisation Not OK (AMA FAULT)

    A fault has been found during automatic motor adaptation (AMA). The display will show a fault message.
    Notes: AMA can only be carried out if there are no alarms during tuning. If parameter 103 or 105 has a wrong setting, correct the setting and start AMA all over. If the motor is too small for AMA to be carried out (parameter 105 must be higher than 35% of the rated output current of the VLT frequency converter), then AMA cannot be enabled.

SYMMETRICAL IMPEDANCE [2]

    AMA has detected an asymmetrical impedance in the motor connected to the system, indicating that the motor could be defective.

MOTOR TOO BIG [3]

    The motor connected to the system is too big for AMA to be carried out. The setting in parameter 102 does not match the motor used.

MOTOR TOO SMALL [4]

    The motor connected to the system is too small for AMA to be carried out. The setting in parameter 102 does not match the motor used.

TIME OUT [5]

    AMA fails because of noisy measuring signals. Try to start AMA multiple times until it is successfully carried out. Note that repeated AMA runs may heat the motor to a level where the stator resistance (R S) is increased, but this is usually not critical.

INTERRUPTED BY USER [6]

    AMA has been interrupted by the user.

INTERNAL FAULT [7]

    An internal fault has occurred in the VLT frequency converter. Contact your Danfoss supplier for assistance.

LIMIT VALUE FAULT [8]

    The parameter values found for the motor are outside the acceptable range within which the VLT frequency converter can operate.

MOTOR ROTATES [9]

    The motor shaft rotates during the AMA process. Ensure that the load is not causing the motor shaft to rotate, then start AMA again.


ALARM 29: Heat Sink Temperature Too High (HEAT SINK OVER TEMP.)
    If the enclosure is IP 00, IP 20, or NEMA 1, the cut-out temperature of the heat sink is 90°C. If IP 54 is used, the cut-out temperature is 80°C. The tolerance is ± 5°C. The temperature fault cannot be reset until the temperature of the heat sink is below 60°C.
    Possible causes include ambient temperature being too high, too long motor cable, or too high switching frequency.

ALARM 30: Motor Phase U Missing (MISSING MOT.PHASE U)
    Motor phase U between the VLT frequency converter and motor is missing.
    Action: Turn off the VLT frequency converter and check motor phase U.

ALARM 31: Motor Phase V Missing (MISSING MOT.PHASE V)

    Motor phase V between the VLT frequency converter and motor is missing.
    Action: Turn off the VLT frequency converter and check motor phase V.

ALARM 32: Motor Phase W Missing (MISSING MOT.PHASE W)

    Motor phase W between the VLT frequency converter and motor is missing.
    Action: Turn off the VLT frequency converter and check motor phase W.

WARNING/ALARM 34: HPFB Communication Fault (HPFB COMM. FAULT)

    The serial communication on the communication option card is not working.

ALARM 37: Inverter Fault (GATE DRIVE FAULT)

    IGBT or the power card is defective.
    Action: Contact your Danfoss supplier.

Auto-optimisation Warnings 39-42

    Automatic motor adaptation has stopped because some parameters have probably been set wrongly, or the motor used is too big/small for AMA to be carried out. A choice must be made by pressing [CHANGE DATA] and choosing 'Continue' + [OK] or 'Stop' + [OK]. If parameters need to be changed, select 'Stop'; start up AMA all over.

WARNING 39: Check Parameters 104, 106 (CHECK PAR. 104, 106)
    Parameters 104 (Motor frequency f M,N) or 106 (Rated motor speed n M,N) have probably not been set correctly. Check the setting and select 'Continue' or [STOP].

WARNING 40: Check Parameters 103, 105 (CHECK PAR. 103, 105)
    Parameter 103 (Motor voltage, UM,N) or 105 (Motor current, I M,N) has not been set correctly. Correct the setting and restart AMA.

WARNING 41: Motor Too Big (MOTOR TOO BIG)
    The motor used is probably too big for AMA to be carried out. The setting in parameter 102 (Motor power, P M,N) may not match the motor. Check the motor and choose 'Continue' or [STOP].

WARNING 42: Motor Too Small (MOTOR TOO SMALL)
    The motor used is probably too small for AMA to be carried out. The setting in parameter 102 (Motor power, P M,N) may not match the motor. Check the motor and select 'Continue' or [STOP].

ALARM 60: Safety Stop (EXTERNAL FAULT)
    Terminal 27 (parameter 304 Digital inputs) has been programmed for a Safety interlock [3] and is a logic '0'.

WARNING 61: Output Frequency Low (FOUT < FLOW)
    The output frequency is lower than parameter 223 (Warning: Low frequency, f LOW).

WARNING 62: Output Frequency High (FOUT > FHIGH)
    The output frequency is higher than parameter 224 (Warning: High frequency, f HIGH).

WARNING/ALARM 63: Output Current Low (I MOTOR < I LOW)
    The output current is lower than parameter 221 (Warning: Low current, I LOW). Select the required function in parameter 409 (Function in case of no load).

WARNING 64: Output Current High (I MOTOR > I HIGH)
    The output current is higher than parameter 222 (Warning: High current, I HIGH).

WARNING 65: Feedback Low (FEEDBACK < FDB LOW)
    The resulting feedback value is lower than parameter 227 (Warning: Low feedback, FB LOW).

WARNING 66: Feedback High (FEEDBACK > FDB HIGH)
    The resulting feedback value is higher than parameter 228 (Warning: High feedback, FB HIGH).

WARNING 67: Remote Reference Low (REF. < REF LOW)
    The remote reference is lower than parameter 225 (Warning: Low reference, REF LOW).

WARNING 68: Remote Reference High (REF. > REF HIGH)
    The remote reference is higher than parameter 226 (Warning: High reference, REF HIGH).

WARNING 69: Temperature Auto Derate (TEMP.AUTO DERATE)
    The heat sink temperature has exceeded the maximum value, and the auto derating function (parameter 411) is active.

WARNING 99: Unknown Fault (UNKNOWN ALARM)
    An unknown fault has occurred which the software is not able to handle. Contact your Danfoss supplier for assistance.

------+

+ Danfoss VLT6000 User Manuals >>

+ Danfoss VLT6000 Fault Codes >>

+ Danfoss VLT6000 Fault Codes 2 >>

+ Danfoss VLT6000 Fault Codes 3 >>

+ Danfoss Main Page (2) >>

+ VFD Home page >>  


-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  18.01.2013     

Your shopping cart is empty!