Danfoss VLT 2800 fault code

   Understanding Danfoss VFD Error codes;

   A warning or an alarm will appear in the display as a numerical code Err. xx. A warning will be shown on the display until the fault has been corrected, while an alarm will continue to flash until
the [STOP/RESET] key is activated.The table shows the various warnings and alarms, and whether the fault locks the frequency converter. After a Trip locked the mains supply is cut off and the fault is corrected.

   The mains supply is reconnected and the frequency converter is reset. The frequency converter is now ready. A Trip can be reset manually in three ways:

1. Via the operating key [STOP/RESET].
2. Via a digital input.
3. Via serial communication.

    It is also possible to choose an automatic reset in parameter 405 Reset function. When a cross appears in both warning and alarm, this can mean that a warning comes before an alarm. It can also mean that it is possible for the user to programme whether a warning or an alarm will appear for a given fault.

   For example, this is possible in parameter 128 Motor thermal protection. After a trip the motor will coast, and alarm and warning will blink on the frequency converter, but if the fault disappears only the alarm will blink. After a reset the frequency converter will be ready to start operation again.
W: Warning, A: Alarm, T: Trip locked

Err 2 Live zero error (LIVE ZERO ERROR)
X X X Voltage or current signal on terminals 53 or 60 is below 50% of preset value.
--------------
Err 4 Mains phase loss (MAINS PHASE LOSS)
X X X No phase on mains supply side.
--------------
Err 5 Voltage warning high (DC LINK VOLTAGE HIGH)
X The intermediate circuit voltage exceeds the limit set.
--------------
Err 6 Voltage warning low (DC LINK VOLTAGE LOW)
X The intermediate circuit voltage is lower the limit set.
--------------
Err 7 Overvoltage (DC LINK OVERVOLT)
X X X The intermediate voltage exceeds the limit set.
--------------
Err 8 Undervoltage (DC LINK UNDERVOLT)
X X X The intermediate voltage is lower than the limit set.
--------------
Err 9 Inverter overload (INVERTER TIME)
X X The frequency converter is close to tripping due to overload.
--------------
Err 10 Motor overloaded ( MOTOR,TIME)
X X The motor is too hot due to overload.
--------------
Err 11 Motor thermistor (MOTOR THERMISTOR)
X X Either the motor is too hot or the thermistor has been disconnected.
--------------
Err 12 Current limit (CURRENT LIMIT)
X X Output current is higher than set in par. 221.
--------------
Err 13 Overcurrent (OVERCURRENT)
X X X The peak current limit has been exceeded.
--------------
Err 14 Earth fault (EARTH FAULT) X X Discharge from output phases to earth.
--------------
Err 15 Switch mode fault (SWITCH MODE FAULT)
X X Fault in switch mode power supply.
--------------
Err 16 Short-circuit (CURR. SHORT CIRCUIT)
X X Short-circuit on the motor terminals or in the motor.
--------------
Err 17 Serial communication timeout (STD BUS TIMEOUT)
X X No serial communication to the frequency converter.
--------------
Err 18 HPFB bus timeout (HPFB TIMEOUT)
X X No serial communication to the communication option card.
--------------
Err 33 Out of frequency range (OUT FREQ RNG/ROT LIM)
X Output frequency has reached the limit set in either par. 201 or par. 202.
--------------
Err 34 HPFB communication fault (PROFIBUS OPT. FAULT)
X X Fault only occurs in fieldbus versions. Please see par. 953 in fieldbus literature.
--------------
Err 35 Inrush fault (INRUSH FAULT)
X X Connected to mains too many times within 1 minute.
--------------
Err 36 Overtemperature (OVERTEMPERATURE)
X X The upper temperature limit has been exceeded.
--------------
Err 37-45 Internal fault (INTERNAL FAULT)
X X Please contact our Danfoss personal.
--------------
Err 50 Auto-tunning not possible X Either RS (stator resistance) value is outside permitted limits, or motor current is too low on at least one phase, or the motor is too small for Auto-tunning.
--------------
Err 51 Auto-tunning fault re. nameplate data (AMT TYPE.DATA FAULT)
X Inconsistency between registered motor data.
--------------
Err 54 Auto-tunning wrong motor (AMT WRONG MOTOR)
X AMA has detected a missing motor phase.
--------------
Err 55 Auto-tunning timeout (AMT TIMEOUT)
X Calculations are taking too long, probably caused by noise on motor cables.
--------------
Err 56 Auto-tunning warning during AMT (AMT WARN. DURING AMT)
X Warning is given while AMA is performed.
--------------
Err 99 Locked (LOCKED) X See par. 018.

- Danfoss Vfd VLT2800 User manual

- Danfoss VFD Contact v

- Danfoss Vfd VLT2800 Fault codes

- Danfoss VFD Contact     

+ Danfoss VLT 2800 user manual 


+ Danfoss Main Page (2) >>

+ VFD Home page >>  


-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  12.01.2013