Teco S310 Vfds
TECO S310 VFD – Basic Setup, Wiring and Parameters

The TECO S310 is a compact variable frequency drive (VFD) used for basic AC motor speed control. Below are a few practical settings for running the drive from an external switch and controlling the speed with an external potentiometer.
Running the S310 from an external switch
On the control terminal strip you will find the COM and S1 terminals. Connect COM to one side of the external 0–1 selector switch or push button, then connect the other side of the switch to S1.
Set parameter 00-03 to 0001. The drive will then take its RUN command from the external terminal instead of the keypad.
Connecting an external potentiometer
For external speed control, use the COM, AIN and 10 V terminals. Connect the potentiometer wiper (centre terminal) to AIN, and connect the two outer terminals to COM and 10 V.
Set parameter 00-05 to 0002 to use the external potentiometer as the frequency reference.
Basic S310 Parameters
00-03 – Run command source
0000 – RUN command from the keypad
0001 – RUN command from the external terminals
0002 – RUN command via RS485 communication
00-05 – Frequency reference source
0000 – Frequency set from the keypad
0001 – Frequency set with the potentiometer on the keypad
0002 – Frequency set with an external potentiometer
00-07 – Maximum frequency
00-08 – Minimum frequency
00-09 – Acceleration time
00-10 – Deceleration time
Once the power and motor wiring have been checked, set the run command source, frequency reference, acceleration/deceleration times and frequency limits to suit the application. The drive can then be started from the selected control source.
TECO S310 Functional Features
Control method: V/f control
Frequency range: 0.01–400.0 Hz
Starting torque: 150% at 1 Hz
Speed control range: 100:1
Speed accuracy: ±0.5%
Digital frequency resolution: 0.01 Hz
Analog resolution: 0.06 Hz / 60 Hz, 10 bit
Keypad adjustment: ▲ / ▼ keys
Display: 5-digit LED display
External reference: 0–10 V / 4–20 mA
Carrier frequency: 1–12 kHz
Acceleration / deceleration time: 0.1–3600 seconds
The S310 also provides upper and lower frequency limits and several preset V/f patterns, including a user-programmable V/f curve.
Other useful functions
Available functions include automatic restart after a short power interruption, speed search, overload detection, up to eight preset speeds, torque boost, slip compensation, upper and lower frequency limits and automatic energy-saving control.
The drive also supports Modbus Slave communication over RS485. Baud rate, stop bit and parity can be configured, and RS485 can be used for either a single drive or a multi-drive network.
Related TECO Pages
Refine Search
Teco S310 0-4Kw
Teco Economy input: 220v Ac output: 0.4 kw Ac motor drive S310 vfd Control M..
79.00USD Ex Tax: 79.00USD
Teco S310 0.75kw
Teco VFD Economy input: 220v Ac output: 0.75 kw Ac motor drive S310 vfd ..
77.00USD Ex Tax: 77.00USD
Teco S310 1.5kw
Teco Economy input: 220v Ac output: 1.5 kw Ac motor drive S310 vfd Control M..
80.00USD Ex Tax: 80.00USD