Invt VFD Modbus adress
Hello there,
Below listed modbus addresses for invt ac driver models.
Dear member, since you prefer the modbus (RS485 modbus) window covering, the first thing you do for each parameter.
These codes are compatible with every invt driver (we tried).
Essentially if you need the essentials for the essentials to file the pilots of the invt speed controller according to the model designation.
-------------------------
HEX= HEX code, DEC= Decimal code
- (HEX) 2000H > (DEC) 408193 (READ/WRITE)
1- Run forward
2- Run reverse
3- jog (forward)
4- jog (reverse)
5- STOP
7- Fault reset
------------------
- (HEX) 20001H > (DEC) 408194 (READ/WRITE)
Speed reference (most used)
-------------------
- (HEX) 2100H >> (DEC) 408449 (Read only)
(status bit)
1- Run forward status
2- Run reverse status
3- Stop
4-VFD Fault
-------------------
(HEX) 3001H > (DEC) 412289 (Read only)
This address is the same as the driver display. It doesn't matter if it's a start or a stop. It is used to read the set (analog or digital or PID) value.
____________
____________
Below we have given the initial addresses of the corresponding HEX and Decimal values for the parameter list. If you have any of the following addresses to use, you can follow them sequentially.
----------------
P00.00= Hex;0 >> Dec; 400001
-----------------
P01.00= Hex;100 >> Dec; 400257
-----------------
P02.00= Hex;200 >> Dec; 400513-----------------
P03.00= Hex;300 >> Dec; 400769-----------------
P04.00= Hex;400 >> Dec; 401025-----------------
P05.00= Hex;500 >> Dec; 401281-----------------
P06.00= Hex; 600 >> Dec; 401537-----------------
P07.00= Hex; 700 >> Dec; 401793-----------------
P08.00= Hex; 800 >> Dec; 402049-----------------
P09.00= Hex; 900 >> Dec; 402305-----------------
P10.00= Hex; A00 >> Dec; 402561-----------------
P11.00= Hex; B00 >> Dec; 402817-----------------
P12.00= Hex; C00 >> Dec; 403073-----------------
P13.00= Hex; D00 >> Dec; 403329-----------------
P14.00= Hex; E00 >> Dec; 403585-----------------
P15.00= Hex; F00 >> Dec; 403841-----------------
P16.00= Hex; 1000 >> Dec; 404097-----------------
P17.00= Hex; 1100 >> Dec; 404353 Setting frequency (Current set freq.)P17.01= Hex; 1101 >> Dec; 404354 . Output frequency
P17.02= Hex; 1102 >> Dec; 404355 . Ramp refence freq. (for acc/dec)
P17.03= Hex; 1103 >> Dec; 404356 . Output voltage
P17.04= Hex; 1104 >> Dec; 404357 . Output current
P17.05= Hex; 1105 >> Dec; 404358 . Motor speed
P17.06= Hex; 1106 >> Dec; 404359 . Torque current
P17.07= Hex; 1107 >> Dec; 404360 . Magnetized current (pm motor)
P17.08= Hex; 1108 >> Dec; 404361 . Motor power (kw)
P17.09= Hex; 1109 >> Dec; 404362 . Output Torque (% )
P17.10= Hex; 110A >> Dec; 404363 . Evaluate the motor rotor frequency
P17.11= Hex; 110B >> Dec; 404364 . Display current DC bus voltage
P17.12= Hex; 110C >> Dec; 404365 . Display current Switch input terminals state of the VFD
P17.13= Hex; 110D >> Dec; 404366 . Display current Switch output terminals state of the VFD
P17.14= Hex; 110E >> Dec; 404367 . Display the adjustment through the keypad of the VFD.
P17.15= Hex; 110F >> Dec; 404368 . Display the torque reference
P17.16= Hex; 1110 >> Dec; 404369 . Display the current linear speed of the VFD
P17.17= Hex; 1111 >> Dec; 404370 . (reserved)
P17.18= Hex; 1112 >> Dec; 404371 . Display current counting number of the VFD
P17.19= Hex; 1113 >> Dec; 404372 . Display analog AI1 input signal
P17.20= Hex; 1114 >> Dec; 404373 . Display analog AI2 input signal
P17.21= Hex; 1115 >> Dec; 404374 . Display analog AI3 input signal
P17.22= Hex; 1116 >> Dec; 404375 . Display HDI input frequency (tacometer)
P17.23= Hex; 1117 >> Dec; 404376 . Display PID reference value
P17.24= Hex; 1118 >> Dec; 404377 . Display PID feedback value
P17.25= Hex; 1119 >> Dec; 404378 . Power factor of the motor
P17.26= Hex; 111A >> Dec; 404379 . Display the current running time of the VFD.
P17.27= Hex; 111B >> Dec; 404380 . Simple PLC and present stage of multi-step speed
P17.28= Hex; 111C >> Dec; 404381 . ASR controller output (%)
P17.29= Hex; 111D >> Dec; 404382 . (reserved)
P17.30= Hex; 111E >> Dec; 404383 . (reserved)
P17.31= Hex; 111F >> Dec; 404384 . (reserved)
P17.32= Hex; 1120 >> Dec; 404385 . Magnetic flux linkage
P17.33= Hex; 1121 >> Dec; 404386 . Exciting current reference
P17.34= Hex; 1122 >> Dec; 404387 . Torque current reference
P17.35= Hex; 1123 >> Dec; 404388 . AC input current
P17.36= Hex; 1124 >> Dec; 404389 . Display the output torque. (nM)
P17.37= Hex; 1125 >> Dec; 404390 . Motor overload counting
P17.38= Hex; 1126 >> Dec; 404391 . Display PID output (%)
P17.39= Hex; 1127 >> Dec; 404392 . (reserved)
P17.40= Hex; 1128 >> Dec; 404393 . Process PID proportional gain
P17.41= Hex; 1129 >> Dec; 404394 . Process PID integral time
P17.42= Hex; 112A >> Dec; 404395 . Process PID differential time
Please note; P17.xx All parameter Read only.
-----------------
P18.00= Hex; 1200 >> Dec; 404609-----------------
P19.00= Hex; 1300 >> Dec; 404865-----------------
P20.00= Hex; 1400 >> Dec; 405121-----------------
P21.00= Hex; 1500 >> Dec; 405377-----------------
P22.00= Hex; 1600 >> Dec; 405633_______________________