Invt VFD Modbus adress

 Hello there,

Below listed modbus addresses for invt ac driver models.

Dear member, since you prefer the modbus (RS485 modbus) window covering, the first thing you do for each parameter.

These codes are compatible with every invt driver (we tried).

Essentially if you need the essentials for the essentials to file the pilots of the invt speed controller according to the model designation.

-------------------------

HEX= HEX code, DEC= Decimal code

(HEX) 2000H > (DEC) 408193 (READ/WRITE)

1- Run forward

2- Run reverse

3- jog (forward)

4- jog (reverse)

5- STOP

7- Fault reset

------------------

- (HEX) 20001H > (DEC) 408194 (READ/WRITE)

Speed reference (most used)

-------------------

- (HEX) 2100H >>  (DEC) 408449 (Read only)

(status bit)

1- Run forward status

2- Run reverse status

3- Stop 

4-VFD Fault

-------------------

(HEX) 3001H > (DEC) 412289 (Read only)

This address is the same as the driver display. It doesn't matter if it's a start or a stop. It is used to read the set (analog or digital or PID) value.

____________

____________

Below we have given the initial addresses of the corresponding HEX and Decimal values for the parameter list. If you have any of the following addresses to use, you can follow them sequentially.

----------------

P00.00= Hex;0 >> Dec; 400001

-----------------

P01.00= Hex;100  >> Dec; 400257

-----------------

P02.00= Hex;200  >> Dec; 400513

-----------------

P03.00= Hex;300  >> Dec; 400769

-----------------

P04.00= Hex;400  >> Dec; 401025

-----------------

P05.00= Hex;500  >> Dec; 401281

-----------------

P06.00= Hex; 600 >> Dec; 401537

-----------------

P07.00= Hex; 700 >> Dec; 401793

-----------------

P08.00= Hex; 800 >> Dec; 402049

-----------------

P09.00= Hex; 900 >> Dec; 402305

-----------------

P10.00= Hex; A00 >> Dec; 402561

-----------------

P11.00= Hex; B00 >> Dec; 402817

-----------------

P12.00= Hex; C00 >> Dec; 403073

-----------------

P13.00= Hex; D00 >> Dec; 403329

-----------------

P14.00= Hex; E00 >> Dec; 403585

-----------------

P15.00= Hex; F00 >> Dec; 403841

-----------------

P16.00= Hex; 1000 >> Dec; 404097

-----------------

P17.00= Hex; 1100 >> Dec; 404353  Setting frequency (Current set freq.)

P17.01= Hex; 1101  >> Dec; 404354 . Output frequency

P17.02= Hex; 1102  >> Dec; 404355 . Ramp refence freq. (for acc/dec)

P17.03= Hex; 1103  >> Dec; 404356 . Output voltage

P17.04= Hex; 1104  >> Dec; 404357 . Output current

P17.05= Hex; 1105  >> Dec; 404358 . Motor speed

P17.06= Hex; 1106  >> Dec; 404359 . Torque current

P17.07= Hex; 1107  >> Dec; 404360 . Magnetized current (pm motor)

P17.08= Hex; 1108  >> Dec; 404361 . Motor power (kw)

P17.09= Hex; 1109  >> Dec; 404362 . Output Torque (% )

P17.10= Hex; 110A  >> Dec; 404363 . Evaluate the motor rotor frequency

P17.11= Hex; 110B  >> Dec; 404364 . Display current DC bus voltage

P17.12= Hex; 110C  >> Dec; 404365 . Display current Switch input terminals state of the VFD

P17.13= Hex; 110D  >> Dec; 404366 . Display current Switch output terminals state of the VFD

P17.14= Hex; 110E  >> Dec; 404367 . Display the adjustment through the keypad of the VFD.

P17.15= Hex; 110F  >> Dec; 404368 . Display the torque reference

P17.16= Hex; 1110  >> Dec; 404369 . Display the current linear speed of the VFD

P17.17= Hex; 1111  >> Dec; 404370 . (reserved)

P17.18= Hex; 1112  >> Dec; 404371 . Display current counting number of the VFD

P17.19= Hex; 1113  >> Dec; 404372 . Display analog AI1 input signal

P17.20= Hex; 1114  >> Dec; 404373 . Display analog AI2 input signal

P17.21= Hex; 1115  >> Dec; 404374 . Display analog AI3 input signal

P17.22= Hex; 1116  >> Dec; 404375 . Display HDI input frequency (tacometer)

P17.23= Hex; 1117  >> Dec; 404376 . Display PID reference value

P17.24= Hex; 1118  >> Dec; 404377 . Display PID feedback value

P17.25= Hex; 1119  >> Dec; 404378 . Power factor of the motor

P17.26= Hex; 111A  >> Dec; 404379 . Display the current running time of the VFD.

P17.27= Hex; 111B  >> Dec; 404380 . Simple PLC and present stage of multi-step speed

P17.28= Hex; 111C  >> Dec; 404381 . ASR controller output (%)

P17.29= Hex; 111D  >> Dec; 404382 . (reserved)

P17.30= Hex; 111E  >> Dec; 404383 . (reserved)

P17.31= Hex; 111F  >> Dec; 404384 . (reserved)

P17.32= Hex; 1120  >> Dec; 404385 . Magnetic flux linkage

P17.33= Hex; 1121  >> Dec; 404386 . Exciting current reference

P17.34= Hex; 1122  >> Dec; 404387 . Torque current reference

P17.35= Hex; 1123  >> Dec; 404388 . AC input current

P17.36= Hex; 1124  >> Dec; 404389 . Display the output torque. (nM)

P17.37= Hex; 1125  >> Dec; 404390 . Motor overload counting

P17.38= Hex; 1126  >> Dec; 404391 . Display PID output (%)

P17.39= Hex; 1127  >> Dec; 404392 . (reserved)

P17.40= Hex; 1128  >> Dec; 404393 . Process PID proportional gain

P17.41= Hex; 1129  >> Dec; 404394 . Process PID integral time

P17.42= Hex; 112A  >> Dec; 404395 . Process PID differential time

Please note; P17.xx All parameter Read only. 

-----------------

P18.00= Hex; 1200 >> Dec; 404609

-----------------

P19.00= Hex; 1300 >> Dec; 404865

-----------------

P20.00= Hex; 1400 >> Dec; 405121

-----------------

P21.00= Hex; 1500 >> Dec; 405377

-----------------

P22.00= Hex; 1600 >> Dec; 405633