what is HART Communicator?

HART 4-20 mA industrial communication protocol

HART — Highway Addressable Remote Transducer is a bidirectional industrial communication protocol used primarily with intelligent process instruments. It allows a field transmitter and a host system to exchange digital configuration, process, diagnostic and maintenance information while preserving the familiar 4–20 mA analog current loop.

In simple terms: a pressure transmitter can continue sending its primary measurement as a normal 4–20 mA signal, while HART carries additional digital information over the same pair of wires. This means the control system can receive the process value and also access device identification, range settings, status, diagnostics and other variables without replacing the existing analog wiring.

HART is especially common with pressure transmitters, temperature transmitters, flowmeters, level instruments, analytical instruments, valve positioners and other intelligent process sensors.

How does HART communication work?

Traditional wired HART superimposes a low-level digital signal on the 4–20 mA current loop using FSK — Frequency Shift Keying.

The conventional HART FSK physical layer is based on Bell 202 signalling and uses two frequencies:

1200 Hz: logical 1 / Mark.
2200 Hz: logical 0 / Space.
Communication rate: 1200 bit/s.

Traditional HART communication is half-duplex: the host and field device take turns transmitting rather than transmitting simultaneously.

Because the FSK waveform has an average value of approximately zero, the digital communication does not change the DC value representing the normal 4–20 mA process signal.

What is the relationship between HART and 4–20 mA?

In the most common point-to-point HART arrangement, the 4–20 mA current represents the Primary Variable — PV, while HART digital communication makes additional device information available on the same loop.

For example, a pressure transmitter may use 4–20 mA for process pressure while HART provides access to:

Primary Variable — PV
additional device variables,
device tag and identification,
engineering units,
Lower and Upper Range Values,
damping settings,
device status,
diagnostic information,
configuration data,
calibration information.

HART therefore extends the traditional analog loop rather than requiring the entire instrumentation system to be replaced by a completely different field network.

Does HART make a sensor more accurate?

Not automatically. HART itself does not improve the physical accuracy of the sensing element. Measurement accuracy still depends on the sensor, transmitter electronics, calibration, installation and process conditions.

However, the digital HART value can provide direct access to the transmitter's internally calculated measurement and avoids an additional analog interpretation step in some systems.

It is therefore more accurate to say that HART provides additional digital process, configuration and diagnostic data, rather than claiming that every HART measurement is inherently more accurate than every analog measurement.

What is a HART Communicator?

A HART Communicator is a HART host used to configure, commission and diagnose HART-enabled field instruments. It may be a dedicated handheld instrument or a software application connected through a HART modem.

A communicator does not simply “convert the analog signal to digital.” Instead, it communicates with the field instrument using the HART command structure carried by the digital FSK signal.

Typical communicator functions include:

reading device identification,
changing the device tag,
changing measurement range,
adjusting damping,
reading diagnostic information,
checking device status,
viewing secondary variables,
performing supported zero or calibration functions.

What is a HART modem?

A HART modem provides the physical communication interface between a PC or digital host and the HART current loop.

USB-to-HART and RS-232-to-HART modems are widely used for commissioning, configuration and maintenance.

The modem modulates and demodulates the HART FSK signal. The configuration software running on the PC performs the actual device-management functions.

Why is a 250 Ω resistor commonly used with HART?

The HART FSK signal requires sufficient loop impedance to create a measurable AC communication voltage.

For this reason, a 250 Ω load resistor is extremely common in HART test and control loops. HART host and modem test systems frequently use this value.

However, blindly adding another 250 Ω resistor is not always correct. Some PLC and DCS analog-input modules already provide suitable HART impedance internally.

The complete loop must also satisfy the field transmitter's minimum operating voltage. The voltage drop across the load resistor, cable, intrinsic-safety barrier and isolator must be considered together with the 24 VDC power supply.

How does HART work with a two-wire transmitter?

Many industrial transmitters are two-wire loop-powered devices. The same two conductors can provide operating power to the transmitter, carry the 4–20 mA measurement current and carry the superimposed HART digital signal.

This arrangement is extremely common in process plants because only one instrument pair needs to run from the control cabinet to a remote pressure, temperature, flow or level transmitter.

How does a PLC communicate with a HART device?

A PLC can access HART information in several ways.

HART-enabled analog input: the PLC module reads the conventional 4–20 mA process signal while also communicating digitally with the transmitter.

Remote HART I/O: distributed I/O can collect analog and HART information near the process and transfer it to the PLC over another network.

HART multiplexer: digital HART information from many existing loops can be collected for an asset-management, DCS or monitoring system without replacing the analog control loops.

A standard analog input capable of reading only 4–20 mA is not automatically HART-capable. The hardware must support the HART physical and protocol layers if digital HART data is required.

How is HART information used on an HMI?

Once the PLC, DCS or HART gateway has collected the information, selected values can be displayed on an HMI panel.

The operator may see not only process pressure or temperature but also transmitter status, a diagnostic alarm or an out-of-range condition.

How is HART used with SCADA and asset-management systems?

At plant level, HART device information can be transferred into a SCADA, DCS or plant asset-management system.

Maintenance personnel can then access device status, identification, process variables and diagnostic information without visiting every transmitter individually.

This is one of HART's major advantages: an existing 4–20 mA control loop can carry useful digital maintenance information that would otherwise remain hidden inside the field instrument.

Which sensors and instruments use HART?

HART is especially common in process instrumentation rather than simple discrete proximity sensing. Typical examples include:

Pressure transmitters
differential-pressure transmitters,
flowmeters and flow transmitters,
radar and hydrostatic level transmitters,
temperature transmitters,
analytical instruments,
valve positioners,
multivariable transmitters.

This should be distinguished from a simple PNP/NPN industrial sensor, which may provide only a switching output and contain no HART interface at all.

How is HART used for temperature measurement?

A bare Pt100 RTD sensor is not itself a HART transmitter. It produces a resistance that changes with temperature.

A temperature transmitter can measure that Pt100 resistance, linearize it and transmit the temperature as 4–20 mA with HART digital communication.

Simpler systems can use Pt100 4–20 mA signal converters, while a HART-enabled transmitter adds digital configuration and diagnostic capability on top of the analog output.

How is HART used for pressure measurement?

Pressure and differential-pressure transmitters are among the most familiar HART devices.

The analog current provides the main pressure measurement to the control system while HART can provide transmitter configuration, range information, device diagnostics and additional calculated variables.

This is particularly useful in pump systems, compressors, filters, steam systems, hydraulic equipment and other applications where pressure measurement is essential.

How is HART used for level measurement?

Radar, guided-wave radar, hydrostatic and some ultrasonic level transmitters can support HART.

The control system can receive the main tank level over 4–20 mA while HART provides additional information such as device status, echo quality, calibration settings or secondary variables where supported.

This is quite different from a simple level switch or relay, which normally provides only an ON/OFF indication rather than a continuous measurement and intelligent device interface.

How is HART used in pump and VFD applications?

HART is normally found on the process-measurement side rather than being the primary motor-drive network.

For example, a HART pressure transmitter can measure discharge pressure and send its normal 4–20 mA feedback to the PLC. The PLC then uses PID control to calculate a new speed command for an AC drive / VFD.

The same basic 4–20 mA signal is also commonly used as a VFD frequency reference, although that does not mean every VFD analog input supports HART digital communication.

What types of HART commands are there?

The HART command model allows multi-vendor devices to provide common functions while still supporting manufacturer-specific features.

Universal Commands: basic commands that conforming HART devices must support, such as device identification and fundamental process information.

Common Practice Commands: standardized commands used by many instruments for configuration and common maintenance tasks.

Device-Specific Commands: additional functions defined for a particular device family or manufacturer.

This layered approach allows a generic host to communicate with many HART instruments while a device-specific configuration package exposes additional manufacturer features.

What are DD, EDD and FDI?

A HART host may use a Device Description — DD/EDD to understand the parameters, menus and functions provided by a particular field device.

This makes it possible for one communicator or asset-management system to provide a device-specific interface for transmitters from many different manufacturers.

Modern systems can also use FDI — Field Device Integration, which packages the information required to integrate intelligent process devices into compatible host systems.

What is HART point-to-point mode?

Point-to-point is the traditional and most common wired HART architecture.

One field instrument is connected to one normal 4–20 mA input loop. The analog current represents the primary process value and the HART digital channel carries the additional device information.

This configuration maintains full compatibility with conventional analog control systems while allowing intelligent maintenance tools to use HART.

What is HART multidrop?

HART can also operate in multidrop mode, where several digitally addressed field devices share one communication pair.

Modern HART addressing allows polling addresses in the 0–63 range, and registered HART 7 products can support up to 63 transmitters in appropriate multidrop implementations.

In a multidrop design, process values are primarily exchanged digitally rather than assigning one independent 4–20 mA analog measurement to each device.

Multidrop is useful where many relatively slow process devices need to share wiring, but it is not the normal architecture for fast independent analog control loops.

What is HART Burst Mode?

Normal HART communication is command/response: the host sends a command and the field device returns a response.

Burst Mode allows a configured field device to repeatedly publish selected HART response information without waiting for the host to request the same value every time.

This can improve the digital update rate for selected data in applications that support Burst Mode.

What is the difference between HART and Modbus?

HART was designed primarily for intelligent process instrumentation and, in its traditional form, combines digital communication with an existing 4–20 mA current loop.

Modbus is a more general industrial application protocol based largely on coils and registers and is commonly used over serial RS-485 or Ethernet/TCP networks.

One plant can therefore use HART for pressure and flow transmitters, Modbus RTU for an energy meter and Modbus TCP or another network for a drive or controller.

What is the difference between ordinary 4–20 mA and 4–20 mA HART?

A conventional 4–20 mA connection usually provides one analog process value.

A HART-enabled 4–20 mA loop can additionally provide:

device identification,
additional process variables,
diagnostics,
measurement-range settings,
calibration information,
maintenance status,
configuration parameters.

The major advantage is therefore not simply “digital instead of analog.” HART allows the familiar analog measurement and intelligent digital device management to coexist.

What is WirelessHART?

WirelessHART extends HART technology into a wireless process-automation network.

WirelessHART uses a self-organizing mesh architecture. Field devices can route messages for neighboring devices, creating alternative communication paths back to the network gateway.

WirelessHART devices can be manufactured with wireless capability built in, or in some cases an adapter can connect an existing wired HART instrument to the wireless network.

A WirelessHART gateway connects the field mesh to higher-level plant control, monitoring and asset-management systems.

What is HART-IP?

HART-IP extends the familiar HART application model to Internet Protocol networks.

FieldComm Group introduced HART-IP into the HART specification in 2012. HART information collected by multiplexers, WirelessHART gateways, I/O and other infrastructure can be transported rapidly over IP networks to plant systems.

HART-IP can operate over standard Ethernet infrastructure. With Ethernet-APL, HART-IP can also extend IP-based process communication closer to the field-instrument level.

Ethernet-APL provides a 10 Mbit/s, two-wire powered Ethernet physical layer designed for process automation, including long cable lengths and hazardous-area applications.

What is SafeHART?

SafeHART extends HART technologies into functional-safety applications. FieldComm Group defines SafeHART for HART 4–20 mA, WirelessHART and HART-IP safety-related communication.

SafeHART is intended to support Safety Instrumented Systems and can be applied in SIL 2 and SIL 3 architectures when the complete safety function is designed appropriately.

A normal HART transmitter does not automatically make a process loop safety-rated. The sensor, logic solver, communication path, final element and complete safety lifecycle must satisfy the relevant functional-safety requirements.

Is HART still a current technology?

Yes. HART is not merely a legacy maintenance protocol for old analog transmitters. FieldComm Group continues to maintain and develop wired HART, WirelessHART, HART-IP and SafeHART.

The current FieldComm Group HART specification page lists HART Communication Protocol Revision 7.10.

The continued development of Ethernet-APL, HART-IP and SafeHART demonstrates how the HART device model is being extended from conventional analog instrumentation into modern digital process architectures.

Why does HART communication fail?

First verify that the field instrument actually supports HART. Not every 4–20 mA transmitter is a HART device.

Check the loop current and transmitter supply voltage. A field device must still receive enough terminal voltage after accounting for cable resistance, barriers, isolators and the HART load resistor.

Verify that the loop provides sufficient HART impedance. A loop with very low impedance may carry the analog current correctly while providing too little HART communication voltage for the modem or host.

If an intrinsic-safety barrier, galvanic isolator or signal conditioner is installed, verify that it is HART transparent. Some devices pass the DC 4–20 mA signal but attenuate or block the HART FSK communication.

Confirm that the HART communicator or modem is connected across an appropriate point of the loop or current-sense resistor.

In panels containing large VFDs, servo amplifiers or heavy switchgear, also inspect instrumentation cable routing, shielding and grounding.

Practical HART troubleshooting checklist

1. Does the transmitter actually support HART?

2. Is the normal 4–20 mA loop current correct?

3. Is there sufficient loop impedance for HART communication?

4. Does the field transmitter have sufficient operating voltage?

5. Are barriers, isolators and signal conditioners HART-compatible?

6. Is the HART modem or communicator connected at the correct point?

7. In multidrop mode, are polling addresses unique?