ATV 78 fault codes 2

    Brake Chopper Supervision:
        Cause: No brake resistor installed, brake resistor is broken, or brake chopper failure.
        Remedial Procedure: Check the brake resistor. If the resistor is okay, the chopper is faulty. Contact the distributor near you.

    Variable Speed Drive Under-temperature:
        Cause: Heatsink temperature is under -10°C.
        Remedial Procedure: Ensure proper operating conditions.

    Variable Speed Drive Over-temperature:
        Cause: Heatsink temperature is over 90°C. Overtemperature warning is issued when the heatsink temperature exceeds 85°C.
        Remedial Procedure: Check the correct amount and flow of cooling air. Check the heatsink for dust. Check the ambient temperature. Make sure that the switching frequency is not too high in relation to ambient temperature and motor load.

    Motor Stalled:
        Cause: Motor stall protection has tripped.
        Remedial Procedure: Check the motor.

    Motor Overtemperature:
        Cause: Motor overheating has been detected by Variable Speed Drive motor temperature model. Motor is overloaded.
        Remedial Procedure: Decrease the motor load. If no motor overload exists, check the temperature model parameters.

    Motor Underload:
        Cause: Motor underload protection has tripped.
        Remedial Procedure: Check the motor load and adjust as necessary.

    EEPROM Checksum Fault:
        Cause: Parameter save fault due to faulty operation or component failure.
        Remedial Procedure: Address the component failure or operational issue.

    Counter Fault:
        Cause: Values displayed on counters are incorrect.
        Remedial Procedure: Check and correct the counter values.

    Microprocessor Watchdog Fault:
        Cause: Faulty operation or component failure.
        Remedial Procedure: Reset the fault with the reset button and restart. Should the fault re-occur, contact the distributor near you.

    Start-up Prevented:
        Cause: Start-up of the drive has been prevented.
        Remedial Procedure: Cancel the prevention of start-up.

    Thermistor Fault:
        Cause: The thermistor input of the option board has detected an increase in motor temperature.
        Remedial Procedure: Check motor cooling and loading. Check the thermistor connection. If the thermistor input of the option board is not in use, it has to be short-circuited.

    IGBT Temperature (Hardware):
        Cause: IGBT Inverter Bridge overtemperature protection has detected too high a short-term overload current.
        Remedial Procedure: Check loading. Check motor size.

    Fan Cooling:
        Cause: Cooling fan of the Variable Speed Drive does not start when the ON command is given.
        Remedial Procedure: Contact your local Schneider Electric sales office.

    CAN Bus Communication:
        Cause: Sent message not acknowledged.
        Remedial Procedure: Ensure that there is another device on the bus with the same configuration.

    Control Unit:
        Cause: ATV78 Control Unit cannot control.
        Remedial Procedure: Change the control unit.

    Device Option Board or Control Unit Changed:
        Cause: Same type of board or same power rating of drive has been changed.
        Remedial Procedure: Reset.

    Device Added (Same Type):
        Cause: Option board or drive added. Drive of same power rating or same type of board added.
        Remedial Procedure: Reset.
        Note: No fault time data record!

    Device Removed:
        Cause: Option board or drive removed.
        Remedial Procedure: Reset.
        Note: No fault time data record!

    Device Unknown:
        Cause: Unknown option board or drive.
        Remedial Procedure: Contact your local Schneider Electric sales office.

    IGBT Temperature:
        Cause: IGBT Inverter Bridge overtemperature protection has detected too high a short-term overload current.
        Remedial Procedure: Check loading. Check motor size.

    Encoder Fault:
        Cause: Issues with encoder channels.
        Remedial Procedure: Check encoder channel connections. Check the encoder board.
        Note the exceptional Fault data record. See 7.3.4.3. Additional codes: 1 = Encoder 1 channel A is missing, 2 = Encoder 1 channel B is missing, 3 = Both encoder 1 channels are missing, 4 = Encoder reversed.

    Device Changed (Different Type):
        Cause: Option board or control unit changed to a different type or different power rating of drive.
        Remedial Procedure: Reset.
        Note: No fault time data record! Application parameter values restored to default.

    Device Added (Different Type):
        Cause: Option board or drive of a different type or different power rating added.
        Remedial Procedure: Reset.
        Note: No fault time data record! Application parameter values restored to default.

    Analogue Input I in < 4mA (Selected Signal Range 4 to 20 mA):
        Cause: Current at the analogue input is < 4mA, indicating a broken or loose control cable or a failed signal source.
        Remedial Procedure: Check the current loop circuitry.

    External Fault:
        Cause: Digital input fault.
        Remedial Procedure: Check the digital input.

    Keypad Communication Fault:
        Cause: The connection between the control keypad and the Variable Speed Drive is broken.
        Remedial Procedure: Check keypad connection and possible keypad cable.

    Fieldbus Fault:
        Cause: The data connection between the fieldbus Master and the fieldbus board is broken.
        Remedial Procedure: Check installation. If installation is correct, contact your local Schneider Electric sales office.

    Slot Fault:
        Cause: Defective option board or slot.
        Remedial Procedure: Check board and slot. Contact your local Schneider Electric sales office.

    PT100 Board Temp. Fault:
        Cause: Temperature limit values set for the PT100 board parameters have been exceeded.
        Remedial Procedure: Find the cause of the temperature rise.