ATV 71 Fault codes 4
- OSF (Mains overvoltage)
Description: Line voltage too high or disturbed mains supply.
Cause: The line voltage may be too high or the mains supply may be disturbed.
+ Solution: Check the line voltage.
- OtF1 (PTC1 overheat)
Description: Overheating of the PTC1 probes detected.
Cause: Could be due to an overload or incorrect sizing of the motor.
+ Solution: Check the motor load and motor size. Check the motor ventilation. Wait for the motor to cool before restarting. Check the type and state of the PTC probes.
- OtF2 (PTC2 overheat)
Description: Overheating of the PTC2 probes detected.
Cause: Similar to OtF1, could be due to an overload or incorrect sizing of the motor.
+ Solution: Follow the same steps as for OtF1.
- OtFL (LI6=PTC overheat)
Description: Overheating of PTC probes detected on input LI6.
Cause: Could be due to an issue with the PTC probes connected to input LI6.
+ Solution: Check the PTC probes connected to input LI6 and their wiring.
- PtF1 (PTC1 probe)
Description: PTC1 probes open or short-circuited.
Cause: There may be a fault in the PTC1 probes or their wiring.
+ Solution: Check the PTC1 probes and the wiring between them and the motor/drive.
- PtF2 (PTC2 probe)
Description: PTC2 probes open or short-circuited.
Cause: Similar to PtF1, there may be a fault in the PTC2 probes or their wiring.
+ Solution: Follow the same steps as for PtF1.
- PtFL (LI6=PTC probe)
Description: PTC probes on input LI6 open or short-circuited.
Cause: There may be a fault in the PTC probes connected to input LI6 or their wiring.
+ Solution: Check the PTC probes connected to input LI6 and their wiring.
- SCF4 (IGBT short circuit)
Description: Power component fault.
Cause: There may be a short circuit in the IGBT or other power components.
+ Solution: Perform a test via the [1.10 DIAGNOSTICS] menu. Inspect and repair the drive.
- SCF5 (Motor short circuit)
Description: Short-circuit at drive output.
Cause: Could be due to a fault in the cables connecting the drive to the motor or the motor's insulation.
+ Solution: Check the cables connecting the drive to the motor and the motor's insulation. Perform tests via the [1.10 DIAGNOSTICS] menu. Inspect and repair the drive.
- SLF1 (Modbus com.)
Description: Interruption in communication on the Modbus bus.
Cause: There may be an issue with the Modbus communication bus or a timeout.
+ Solution: Check the communication bus and the timeout. Refer to the Modbus User's Manual.
- SLF2 (PC com.)
Description: Fault communicating with PC-Software.
Cause: There may be an issue with the PC-Software connecting cable or a timeout.
+ Solution: Check the PC-Software connecting cable and the timeout.
- SLF3 (HMI com.)
Description: Fault communicating with the graphic display terminal.
Cause: There may be an issue with the terminal connection or a timeout.
+ Solution: Check the terminal connection and the timeout.
- SrF (TORQUE TIME OUT FLT)
Description: The time-out of the torque control function is attained.
Cause: The torque control function may have reached its time-out limit.
+ Solution: Check the function's settings and the state of the mechanism.
- SSF (Torque/current lim)
Description: Switch to torque limitation.
Cause: The drive may have switched to torque limitation mode due to mechanical problems.
+ Solution: Check if there are any mechanical problems. Check the parameters of [TORQUE LIMITATION] (tLA-) on page 189 and the parameters of the [TORQUE OR I LIM. DETECT.] (tId-) fault on page 236.
- tJF (IGBT overheat)
Description: Drive overheated.
Cause: The drive may have overheated due to a high load/motor/drive size or high switching frequency.
+ Solution: Check the size of the load/motor/drive. Reduce the switching frequency. Wait for the motor to cool before restarting.
- CFF (Incorrect config.)
Description: Incorrect configuration due to option card change/removal or control card replacement.
Cause: Option card may have been changed or removed, or a control card configured for a different drive rating may have been installed.
+ Solution: Check for any card errors. If the option or control card was deliberately changed or removed, see the relevant remarks. Return to factory settings or retrieve a valid backup configuration (see page 253).
- CFI (Invalid config.)
Description: Invalid configuration loaded in the drive via the bus or communication network.
Cause: The configuration may be inconsistent, or the [Max frequency] (tFr) may have been set at a value higher than 599Hz.
+ Solution: Check the previously loaded configuration. Load a compatible configuration. Set [Max frequency] (tFr) at a value lower or equal to 599 Hz.
- dLF (Dynamic load fault)
Description: Abnormal load variation.
Cause: The load may be blocked by an obstacle.
+ Solution: Check that the load is not blocked by an obstacle. Removal of a run command causes a reset.
- HCF (Cards pairing)
Description: The [CARDS PAIRING] (PPI-) function has been configured, and a drive card has been changed.
Cause: A drive card may have been changed after the [CARDS PAIRING] (PPI-) function was configured.
+ Solution: In the event of a card error, reinsert the original card. Confirm the configuration by entering the [Pairing password] (PPI) if the card was changed deliberately.
- PHF (Input phase loss)
Description: Drive incorrectly supplied or a fuse blown. Failure of one phase. 3-phase ATV71 used on a single-phase line supply. Unbalanced load.
Cause: The drive may be incorrectly supplied, or there may be a failure of one phase.
+ Solution: Check the power connection and the fuses. Use a 3-phase line supply. Disable the fault by setting [Input phase loss] (IPL) = [No] (nO) on page 228.
- USF (Undervoltage)
Description: Line supply too low or transient voltage dip.
Cause: The line supply voltage may be too low, or there may be a transient voltage dip.
+ Solution: Check the voltage and the parameters of [UNDERVOLTAGE MGT] (USb-) on page 231. This protection only operates with the drive running in motor mode.