ATV 38 fault codes 2
PHF Main Line Phase Loss
- The drive is incorrectly supplied or fuses are blown
- Temporary fault on a single phase
- The drive is supplied by the DC bus
+ Check the power connection and fuses
+ Reset
+ Configure "InPhaseLoss" fault (code IPL) as "No" in the FAULT menu
USF Undervoltage
- Line supply too low
- Transient voltage drop
- Damaged load resistor
+ Check the line voltage
+ Replace the load resistor
OSF Overvoltage
- Line supply too high
+ Check the line voltage
OHF Drive Overheat
- Heat sink temperature too high (tttHHHddd > %118)
+ Monitor the motor load, drive ventilation, and wait for the drive to cool before resetting
OLF Motor Overload
- Thermal trip due to prolonged overload (tttHHHrrr > %118)
+ Check the thermal protection setting, monitor the motor load
+ Reset will be possible after approximately 7 minutes
ObF Overbraking
- Braking is too sudden or there is a high load during operation
- Overvoltage in the line supply during operation
+ Increase the deceleration time, add a braking resistor if necessary
+ Check for any overvoltage in the line
OPF Motor Phase Loss
- An open phase at the drive output
+ Check the motor connections and ensure the auxiliary contactor is closed if present
+ If used in a motor starter macro configuration, check that R2 relay is configured as the auxiliary contactor
LFF Loss of Follower
- Loss of 4-20 mA signal at AI2 input
+ Check the reference circuit connections
OCF Overcurrent
- Ramp too short
- Inertia or load too high
- Mechanical blockage
+ Check the settings
+ Check the size of the motor/drive/load
+ Check the condition of the mechanism
SCF Short Circuit
- Short circuit or grounding at the drive output
+ Check the drive connection cables while disconnected and check the motor insulation. Inspect the drive transistor bridge
CrF Precharge Fault
- Load relay control fault
- Damaged load resistor
+ Check the connectors and load resistor on the drive
SLF RS485 Fault
- Incorrect connection at the drive connector port
+ Check the connection at the drive connector port
OtF Motor Overheated
- Motor temperature too high (PTC probes)
+ Check the motor ventilation and ambient temperature, monitor the motor load
+ Check the type of probes used
tSF PTC Probe Fault
- Fault in probe connection to the drive
+ Check the probe connection to the drive
+ Inspect the probes
EEF EEPROM Fault
- Error saving to EEPROM
+ Cut the drive power and reset
InF Internal Fault
- Internal error
- Connection fault
+ Check the connectors on the drive
EPF External Fault
- Fault triggered by an external device
+ Check and reset the device that caused the fault
SPF Speed Feedback Loss
- No speed feedback
+ Check the speed sensor connection and mechanical linkage
AnF Load Deviation Fault
- Ramp not followed
- Speed opposite to reference
+ Check speed feedback settings and wiring
+ Ensure settings are appropriate for the load
+ Verify the motor-drive sizing and need for a braking resistor
SOF Overspeed
- Instability
- Driving load too high
+ Check settings and parameters
+ Add a braking resistor
+ Verify the motor/drive/load sizing
CnF Network Fault
- Communication fault on the field network
+ Check the network connection to the drive
+ Check the timeout
ILF Internal Communication Fault
- Communication error between option card and control card
+ Check the connection of the option card to the control card
CFFF Rating Fault-ENT
Option Fault-ENT
Option Missing-ENT
CKS Fault - ENT
Likely to occur when changing the card:
- Rating change of the power card
- Change in option card type or installing an option card if previously not present and macro-configuration is CUS
- Removal of the option card
- Inconsistent saved configuration
- Message appears when pressing the ENT key:
- Fab.Set? ENT/ESC
- Check the drive hardware configuration (power card, etc.)
- Cut the drive power and reset
- Save the configuration to a file on the terminal
- Press ENT to return to factory settings
CFI Configuration Fault
- Inconsistent configuration sent to the drive via serial link
+ Check the previously sent configuration
+ Send a consistent configuration