ATV 32 fault codes 2

    FbES [FB Stop Fault]:
- Cause: Function blocks have been stopped while the motor was running.
- Remedy: Check [FB Stop mode] (FbSM) configuration.

    FCF2 [Output Contactor Open]:
- Cause: The output contactor remains open although the closing conditions have been met.
- Remedy: Check the contactor and its wiring.
- Remedy: Check the feedback circuit.

    LCF [Input Contactor]:
- Cause: The drive is not turned on even though [Mains V. time out] (LCt) has elapsed.
- Remedy: Check the contactor and its wiring.
- Remedy: Check the time-out.
- Remedy: Check the line/contactor/drive connection.

    LFF3 [AI3 4-20mA Loss]:
- Cause: Loss of the 4-20 mA reference on analog input AI3.
- Remedy: Check the connection on the analog inputs.

    ObF [Overbraking]:
- Cause: Braking too sudden or driving load. Line voltage too high.
- Remedy: Increase the deceleration time.
- Remedy: Install a braking resistor if necessary.
- Remedy: Activate the [Dec ramp adapt.] (brA) function if it is compatible with the application.
- Remedy: Check the line voltage.

    OHF [Drive Overheat]:
- Cause: Drive temperature too high.
- Remedy: Check the motor load, the drive ventilation, and the ambient temperature. Wait for the drive to cool down before restarting.

    OLC [Process Overload Fault]:
- Cause: Process overload.
- Remedy: Check and remove the cause of the overload.
- Remedy: Check the parameters of the [PROCESS OVERLOAD] (OLd-) function.

    OLF [Motor Overload]:
- Cause: Triggered by excessive motor current.
- Remedy: Check the setting of the motor thermal protection, check the motor load. Wait for the motor to cool down before restarting.

    OPF1 [1 Output Phase Loss]:
- Cause: Loss of one phase at drive output.
- Remedy: Check the connections from the drive to the motor.

    OPF2 [3 Motor Phase Loss]:
- Cause: Motor not connected or motor power too low. Output contactor open. Instantaneous instability in the motor current.
- Remedy: Check the connections from the drive to the motor.
- Remedy: If an output contactor is being used, set [Output Phase Loss] (OPL) to [Output cut] (OAC).
- Remedy: Test on a low power motor or without a motor: In factory settings mode, motor phase loss detection is active. To check the drive in a test or maintenance environment without having to use a motor with the same rating as the drive, deactivate motor phase loss detection.
- Remedy: Check and optimize the following parameters: [IR compensation] (UFr), [Rated motor volt.] (UnS), [Rated mot. current] (nCr), and perform [Auto tuning] (tUn).

    OSF [Mains Overvoltage]:
- Cause: Line voltage too high. Disturbed mains supply.
- Remedy: Check the line voltage.

    OtFL [LI6=PTC Overheat]:
- Cause: Overheating of PTC probes detected on input LI6.
- Remedy: Check the motor load and motor size.
- Remedy: Check the motor ventilation.
- Remedy: Wait for the motor to cool before restarting.
- Remedy: Check the type and state of the PTC probes.

    PtFL [LI6=PTC Probe]:
- Cause: PTC probe on input LI6 open or short-circuited.
- Remedy: Check the PTC probe and the wiring between it and the motor/drive.

    SCF4 [IGBT Short Circuit]:
- Cause: Power component detected fault.
- Remedy: Contact Schneider Electric Product Support.

    SCF5 [Motor Short Circuit]:
- Cause: Short-circuit at drive output.
- Remedy: Check the cables connecting the drive to the motor and the motor's insulation.
- Remedy: Contact Schneider Electric Product Support.

    SLF1 [Modbus Communication]:
- Cause: Communication interruption on the Modbus bus.
- Remedy: Check the communication bus.
- Remedy: Check the time-out.
- Remedy: Refer to the Modbus User's manual.

    SLF2 [PC Communication]:
- Cause: Communication interruption with PC Software.
- Remedy: Check the PC Software connecting cable.
- Remedy: Check the time-out.

    SLF3 [HMI Communication]:
- Cause: Communication interruption with the graphic display terminal or remote display terminal.
- Remedy: Check the terminal connection.
- Remedy: Check the time-out.

    SSF [Torque/Current Limitation]:
- Cause: Switch to torque or current limitation.
- Remedy: Check if there are any mechanical problems.
- Remedy: Check the parameters of [TORQUE LIMITATION] (tOL-) and [TORQUE OR I LIM. DETECT.] (tId-).

    tJF [IGBT Overheat]:
- Cause: Drive overheated.
- Remedy: Check the size of the load/motor/drive.
- Remedy: Reduce the switching frequency.
- Remedy: Wait for the motor to cool before restarting.

    ULF [Process Underload Fault]:
- Cause: Process underload.
- Remedy: Check and remove the cause of the underload.
- Remedy: Check the parameters of the [PROCESS UNDERLOAD] (Uld-) function.

    CFF [Incorrect Configuration]:
- Cause: Option card changed or removed. Control block replaced by a control block configured on a drive with a different rating. The current configuration is inconsistent.
- Remedy: Check that there are no card errors.
- Remedy: In the event of the option card being changed/removed deliberately, refer to the relevant remarks in the manual.
- Remedy: In the event of the control block being changed deliberately, refer to the relevant remarks in the manual.
- Remedy: Return to factory settings or retrieve the backup configuration, if it is valid.

    CFI [Invalid Configuration]:
- Cause: Invalid configuration. The configuration loaded in the drive via the bus or communication network is inconsistent.
- Remedy: Check the configuration loaded previously.
- Remedy: Load a compatible configuration.

    CSF [Channel Switch Fault]:
- Cause: Switch to not valid channels.
- Remedy: Check the function parameters.

    dLF [Dynamic Load Fault]:
- Cause: Abnormal load variation.
- Remedy: Check that the load is not blocked by an obstacle.
- Remedy: Removal of a run command causes a reset.

    FbE [Function Block Error]:
- Cause: Function blocks error.
- Remedy: See [FB Fault] (FbFt) for more details.

    HCF [Cards Pairing]:
- Cause: The [CARDS PAIRING] (PPI-) function has been configured and a drive card has been changed.
- Remedy: In the event of a card error, reinsert the original card.
- Remedy: Confirm the configuration by entering the [Pairing password] (PPI) if the card was changed deliberately.

    PHF [Input Phase Loss]:
- Cause: Drive incorrectly supplied or a fuse blown. One phase missing. 3-phase ATV32 used on a single-phase line supply. Unbalanced load. This protection only operates with the drive on load.
- Remedy: Check the power connection and the fuses.
- Remedy: Use a 3-phase line supply.
- Remedy: Disable the detected fault by [Input phase loss] (IPL) = [No] (nO).

    USF [Undervoltage]:
- Cause: Line supply too low. Transient voltage dip.
- Remedy: Check the voltage and the parameters of [UNDERVOLTAGE MGT] (USb-).

    InIt [Initialization in Progress]:
- Description: The microcontroller is initializing. Search underway for communication configuration.

    COM.E [Communication Error]:
- Description: Time-out detected fault (50 ms). This message is displayed after 20 attempts at communication.

    A-17 [Alarm Button]:
- Description: A key has been held down for more than 10 seconds. The keypad is disconnected. The keypad wakes up when a key is pressed.

    CLr [Confirmation of Detected Fault Reset]:
- Description: This is displayed when the STOP key is pressed once if the active command channel is the remote display terminal.

    dEU.E [Drive Disparity]:
- Description: The drive brand does not match that of the remote display terminal.

    rOM.E [ROM Anomaly]:
- Description: The remote display terminal detects a ROM anomaly on the basis of checksum calculation.

    rAM.E [RAM Anomaly]:
- Description: The remote display terminal detects a RAM anomaly.

    CPU.E [Other Detected Faults]:
- Description: Other detected faults.

For the detailed explanation of the CFF [Incorrect Configuration] fault, it is important to note that when an option card is changed or removed, or when a control block is replaced with one configured for a drive with a different rating, the drive will lock in CFF fault mode on power-up. To clear this fault, if the change was deliberate, you can press the ENT key twice, which will restore the factory settings for the affected parameter groups. If an option card of the same type is replaced, only the parameters specific to communication cards will be affected. If the control block is changed, all factory settings will be restored.