ATV 212 fault codes 2
OCA [SC inverter at start]: Ground fault. Check the motor and motor cables for ground faults using a 1000 V megger.
OCL [SC mot. cable at start]: Phase to phase output short circuit or the motor impedance is too low. Check the motor and motor cables for ground faults using a 1000 V megger.
OH [Drive overtemperature]: Cooling fan not working, high ambient temperature, blocked air vent, heat source too close, or malfunctioning heatsink temperature sensor. Restart the drive after cool-off, decrease ambient temperature, check fan operation.
OH2 [PTC overheating]: External PTC indicates motor overtemperature. Correct motor overload condition and check PTC operation.
OL1 [Drive overload]: Short acceleration time, high DC injection current, incorrect [Mot cont. mode sel.] setting, starting into a rotating load, or too large load. Adjust acceleration time, DC injection current level, select correct mode, enable catch on the fly, or use a higher power drive.
OL2 [Motor overload]: Incorrect [Mot cont. mode sel.] setting, motor jammed, continuous low-speed operation, or excessive load. Select correct mode, check load, and adjust overload level for low-speed operation.
OP1 [Overvoltage acceleration]: Abnormal input voltage fluctuation, large power network, power factor capacitor switching, SCR switching, starting into rotating load, or intermittent output phase fault. Install line reactor, enable catch on the fly, and rectify missing output phase.
OP2 [Overvolt. deceleration]: Short deceleration time, overhauling load, abnormal input voltage fluctuation, large power network, power factor capacitor switching, SCR switching, starting into rotating load, or intermittent output phase fault. Increase deceleration time, enable parameter, install line reactor, check circuits for phase loss, and enable catch on the fly.
OP3 [Overvoltage cont. speed]: Abnormal input voltage fluctuation, large power network, power factor capacitor switching, SCR switching, drive regenerating due to load causing motor to run at higher frequency, or intermittent output phase fault. Install line reactor and check circuits for phase loss.
Ot [Overtorque]: Calculated motor torque reached level set by parameter F616. Adjust settings of parameters F615 and F616 and verify machine operation.
pSrF [Prst Spd Error]: Prestart speed not reached due to high load. Reduce the load.
SOUt [PM motor step-out]: Motor jammed, output phase loss, or impact load. Check load, correct jammed condition, and check motor and load wiring.
UC [Underload]: Measured motor current dropped below level set by parameter F611. Check parameters F610–612 for correct settings.
UPI [Undervoltage]: Input voltage too low. Check input voltage, select correct setting for parameter F627, enable catch on the fly, and set parameter F302 to 2.
Atn1 [Auto tune]: Auto-tuning in process. Normal if the message disappears after a few seconds.
CLr [Reset active]: Displayed after STOP key is pressed while a detected fault is displayed. Press the STOP key again to clear the detected fault.
db [DC braking]: DC braking is in process. The alarm code goes off in several seconds if no trouble occurs.
dbOn [dbOn]: DC braking is in process when Crankcase heating (F355) is activated. This is normal behavior if Crankcase heating (F355) is activated and the motor is stopped.
E-17 [HMI error]: A graphic display option key has been held down for more than 20 seconds. Release the graphic display option key. If this does not clear the error, replace the drive.
EI [Excess value]: The number of digits entered for values such as frequencies is more than 4 (the upper digits have priority). Lower the frequency free-unit magnification [Customized freq val] (F702).
EOFF [Loc. Stop en.]: The operation panel is used to stop the operation in automatic control or remote control mode. Press the STOP key for an emergency stop. To cancel the emergency stop, press any other key.
Err1 [Speed ref alarm]: The frequency setting signals at points 1 and 2 are set too close to each other. Set the frequency setting signals at points 1 and 2 apart from each other.
h999 [Pin&1MWh] Integral input power: Integral input power is more than 999.99 kWh. Press and hold down the ENT key for 3 seconds or more when power is off or when the input terminal function CKWH is turned on or displayed.
H999 [Pout&1MWh] Integral output power: Integral output power is more than 999.99 kWh. Press and hold down the ENT key for 3 seconds or more when power is off or when the input terminal function CKWH is turned on or displayed.
HEAd/End [Head]/[End]: Display of first/last data items. Press the MODE key to exit the data group.
H1/LO [High]/[Low]: Parameter adjustment error. During programming, a value was entered that exceeds the maximum or minimum value of the parameter. Enter a value within the bounds of the parameter.
InIt [Initialization]: Parameters are being initialized to default values. Normal if the message disappears after several seconds.
LStp [Low speed stop]: Auto-stop because of continuous operation at the lower-limit frequency. The automatic stop function selected with F256 was activated. To deactivate the automatic stop function, increase the frequency command above the lower-limit frequency LL+F391 or turn off the operation command.
NOFF [Line undervolt flt]: The phase-to-phase input voltage is too low. Measure the main circuit supply voltage. If the voltage is at a normal level, the drive requires repair.
OFF [Drive stop]: The ST-CC (run permissive) circuit is open. Close the ST-CC circuit.
nSt [Lock State]: The Li is already active when the function is validated. The Li is already active when a configuration transfer is done with the function is validated. Deactivate the active Li configured.
rtrY [Auto reset]: The drive is in the process of restart. A momentary stop occurred. The drive is operating normally if it restarts after several seconds.
StOp [Stop supply]: Momentary power loss slowdown stop prohibition function activated. The slowdown stop prohibition function set with F302 (momentary power loss ride-through operation) is activated. To restart operation, reset the drive or input an operation signal again.
Pre-alarm Conditions:
C [Current alarm]: The drive is at current limit. Refer to parameter F601 and F185 for more information.
P [DC bus alarm]: The drive is approaching an overvoltage detected fault due to a high supply line, regenerative motor braking, or a combination of these. Refer to parameters F305 and F626 for more information.
L [Motor overload al]: The motor overload timer has reached or exceeded 50% of its detected fault level.
H [Drv overheat alrm]: The drive is approaching an overheating fault detection.