ATV 212 fault codes

    CApF [Cavitation Error]
- Cause: Loss of speed due to overload or too much torque.
- Solution: Reduce the load on the motor to prevent cavitation.

    CFI2 [Download Transfer Fault]
- Cause: Invalid configuration or unsuccessful transfer due to rating differences.
- Solution: Check and load a compatible configuration. If using PC soft for download, uncheck "Display communication error" in the environment options.

    E-18 [VIA Signal Fault]
- Cause: The VIA analog signal is below the level set by parameter F633.
- Solution: Check the VIA signal and rectify the cause of the signal loss. Ensure parameter F633 is set correctly.

    E-19 [CPU Communications Error]
- Cause: Communication error between control CPUs.
- Solution: Check the electromagnetic compatibility of the environment, restart the product, and contact Schneider Electric support if necessary.

    E-20 [Excess Torque Boost Fault]
- Cause: Auto Torque Boost parameter set too high or motor impedance too low.
- Solution: Repeat auto-tuning and reduce the Auto Torque Boost parameter. Adjust deceleration settings if necessary.

    E-21 [CPU Error 2 Fault]
- Cause: The control board CPU is inoperable.
- Solution: Contact Schneider Electric for repair.

    E-38 [EEprom Power Incompatibility]
- Cause: Incompatible Eeprom power or hardware fault detected.
- Solution: Contact Schneider Electric for repair.

    E-39 [InitPos Det]
- Cause: Error in initial position detection due to incorrect current or phase loss.
- Solution: Check motor phases, maximum current, and motor inductance.

    EEP1 [EEPROM Error 1 Fault]
- Cause: Data writing error.
- Solution: Cycle power to clear the fault.

    EEP2 [EEPROM Error 2 Fault]
- Cause: Power loss during parameter reset operation.
- Solution: Cycle power, retry the parameter reset, and contact Schneider Electric if the fault persists.

    EEP3 [EEPROM Error 3 Fault]
- Cause: Data reading error.
- Solution: Cycle power to clear the fault.

    EF2 [Ground Fault]
- Cause: Ground fault in motor or motor cables.
- Solution: Check for ground faults in the motor and cables.

    EPHO [Output Phase Loss Fault]
- Cause: Loss of one or more output phases.
- Solution: Determine and clear the cause of the missing output phase. Check parameter F605.

    EPHI [Input Phase Loss Fault]
- Cause: Loss of one input phase.
- Solution: Determine and clear the cause of the missing input phase. Check parameter F608.

    EPtF [Threshold Error]
- Cause: Overheating condition reached, exceeding threshold F353.
- Solution: Check the system for overheating issues.

    Err1 [Speed Reference Error Fault]
- Cause: Incorrect settings of parameters F202, F203, F210, or F212.
- Solution: Set these parameters to the correct settings.

    Err2 [RAM Fault]
- Cause: The control board RAM is inoperable.
- Solution: Contact Schneider Electric for repair.

    Err3 [ROM Fault]
- Cause: The control board ROM is inoperable.
- Solution: Contact Schneider Electric for repair.

    Err4 [CPU Fault 1]
- Cause: The control board CPU is inoperable.
- Solution: Contact Schneider Electric for repair.

    Err5 [Com RJ45 Fault]
- Cause: Serial communication error.
- Solution: Check network devices, cables, and communication settings.

    Err7 [Current Sensor Fault]
- Cause: A motor current sensor is inoperable.
- Solution: Replace the drive.

    Err8 [Network Error Fault]
- Cause: Network communication error.
- Solution: Check network control devices and cables.

    Err9 [Remote Keypad Fault]
- Cause: Graphic display option cable disconnected.
- Solution: Check the RJ45 cable.

    Etn1 [Auto-tuning Fault]
- Cause: Incorrect parameter settings or issues with motor size, cable gauge, or rotation.
- Solution: Set parameters correctly, use a larger drive or cable, ensure the motor is stopped before auto-tuning, and use the drive only for a 3-phase induction motor.

    EtYP [Drive Fault]
- Cause: The main control board is inoperable.
- Solution: Set parameter [Parameter reset] (tYP) to 6. If the error persists, replace the drive.

    Fd1 (Closed damper 1 fault): Damper is locked in closed position. Remedy: Set [Damper flt behavior] (F583) to 0, check the FL relay connection (FLA/FLB), and check the relay configuration (F130/F132).
    Fd2 (Closed damper 2 fault): Damper blocked open or soldered. Remedy: Set [Damper fdb type] (F580) to 0 or 1, check the FL relay connection (FLA/FLB), and check the relay configuration (F130/F132).
    M020 (Total input power): The accumulated input power value is more than 999.999 kWh. Remedy: Clear the accumulated input power value using logic input function 51, or parameter F748.
    OC1 (Overcurrent acceleration): The acceleration time is too short, incorrect setting of parameter [Mot cont. mode sel.] (Pt), starting into a rotating load, powering a low impedance motor, or ground fault. Remedy: Increase acceleration time, select correct setting for parameter Pt, enable catch on the fly (F301), adjust switching frequency (F300), and set parameter F316 to 1 or 3.
    OC1P (SC or ground fault acc.): Short circuit or ground fault during acceleration. Remedy: Check the motor and motor cables for ground faults using a 1000 V testing tool megger.
    OC2 (Overcurrent deceleration): The deceleration time is too short or ground fault. Remedy: Increase the deceleration time parameters (dEC or F501) and set parameter F316 to 1 or 3.
    OC2P (SC or ground fault dec.): Short circuit or ground fault during deceleration. Remedy: Check the motor and motor cables for ground faults using a 1000 V megger.
    OC3 (Overcurrent cont. speed): Abrupt fluctuations in load or abnormal load condition. Remedy: Reduce the load fluctuations, check the load, and set parameter F316 to 1 or 3.
    OC3P (SC/ground flt cont. spd): Short circuit or ground fault during constant speed operation or drive cooling fan not working. Remedy: Check the motor and motor cables for ground faults using a 1000 V megger and check the fan operation.