ATV 12 fault codes 1

Altivar 12 (ATV 12) Diagnostics and Troubleshooting:

The Drive Does Not Start and No Fault Code Is Displayed

If the display does not light up, check the drive’s power supply, paying particular attention to the ground connection and input phase connections.

The assignment of the “Fast Stop” (FSt) or “Freewheel Stop” (nSt) functions can prevent the drive from starting until the corresponding logic inputs (LI) are energized. On the ATV12, “nSt” is displayed during a freewheel stop, “FSt” during a fast stop, and “rdY” in the freewheel stop mode. These functions are designed to be active at logic level 0, which means that the drive will stop in the event of a broken control wire. Therefore, check the LI assignments in the COnF / FULL / FUn- / Stt- menu.

Make sure that the run command input(s) are enabled according to the selected control mode. In particular, check the tCC (Control Type) and tCt (2-wire Control Type) parameters in the COnF / FULL / I_O menu.

If the reference channel or command channel is assigned to Modbus, the drive may display “nSt” (Freewheel Stop) when power is applied and remain in the stopped state until it receives a run command via the communication bus.

The RUN button is disabled by default in the factory settings. To control the drive locally, set Fr1 (Reference Channel 1) and Cd1 (Command Channel 1) appropriately in the COnF / FULL / CtL menu. Refer to the relevant instructions for the local control procedure.

Fault Detection Codes That Cannot Be Automatically Cleared

The cause of the detected fault must be corrected before the fault can be cleared. Resetting the drive without eliminating the underlying problem may cause the fault to reappear.

The SOF and tnF faults can also be reset remotely through a logic input (LI). To enable this function, assign the appropriate logic input to the rSF (Detected Fault Reset Assignment) parameter in the COnF / FULL / FLt menu.



Fault Codes and Remedies:

    CrF1 Precharge:
- Possible Causes: Charging relay control fault or charging resistor damaged.
+ Remedies: Turn the drive off and then back on again, check the connections, check the stability of the main supply, contact your local Schneider Electric representative.

    InFI Unknown Drive Rating:
- Possible Causes: The power card is different from the card stored.
+ Remedy: Contact your local Schneider Electric representative.

    InF2 Unknown or Incompatible Power Board:
- Possible Causes: The power card is incompatible with the control card.
+ Remedy: Contact your local Schneider Electric representative.

    InF3 Internal Serial Link:
- Possible Causes: Communication interruption between the internal cards.
+ Remedy: Contact your local Schneider Electric representative.

    InF4 Invalid Industrialization Zone:
- Possible Causes: Inconsistent internal data.
+ Remedy: Contact your local Schneider Electric representative.

    InF9 Current Measurement Circuit:
- Possible Causes: Current measurement is not correct due to hardware circuit.
+ Remedy: Contact your local Schneider Electric representative.

    InFb Internal Thermal Sensor Detected Fault:
- Possible Causes: The drive temperature sensor is not operating correctly, the drive is in short circuit or open.
+ Remedy: Contact your local Schneider Electric representative.

    InFE Internal CPU:
- Possible Causes: Internal microprocessor error.
+ Remedy: Turn the drive off and then back on again, contact your local Schneider Electric representative.

    OCF Overcurrent:
- Possible Causes: Parameters in the Motor control menu drC- are not correct, inertia or load too high, mechanical locking.
+ Remedies: Check the parameters, check the size of the motor/drive/load, check the state of the mechanism, connect line chokes, reduce the Switching frequency SFr, check the ground connection of the drive, motor cable, and motor insulation.

    SCF1 Motor Short Circuit:
- Possible Causes: Short-circuit or grounding at the drive output, ground fault during running status, commutation of motors during running status, significant current leakage to ground if several motors are connected in parallel.
+ Remedy: Check the cables connecting the drive to the motor, and the motor insulation, connect motor chokes.

    SCF4 IGBT Short Circuit:
- Possible Causes: Internal power component short circuit detected at power-on.
+ Remedy: Contact your local Schneider Electric representative.

    SOF Overspeed:
- Possible Causes: Instability, overspeed associated with the inertia of the application.
+ Remedies: Check the motor, overspeed is 10% more than Maximum frequency tFr so adjust this parameter if necessary, add a braking resistor, check the size of the motor/drive/load, check parameters of the speed loop (gain and stability).

    tnF Auto-tuning:
- Possible Causes: Motor not connected to the drive, one motor phase loss, special motor, motor is rotating (being driven by the load, for example).
+ Remedies: Check that the motor/drive are compatible, check that the motor is present during auto-tuning, if an output contactor is being used, close it during auto-tuning, check that the motor is completely stopped.

    LFF1 AI Current Lost Fault:
        Detection if: Analog input AI1 is configured as current, AI1 current scaling parameter of 0% CrL1 is greater than 3 mA, analog input current is lower than 2 mA.
+ Remedy: Check the terminal connection.