IC697BEM733

Remote I/O Scanner (IC697BEM733/735) Overview

The IC697 Remote I/O Scanner (IC697BEM733/735) is an intelligent module designed for remote IC697 racks, allowing the interface of IC697 I/O modules with the IC66* bus. This enables remote I/O capabilities for various types of PLC systems.

  •     Long-distance installation: Can be located up to 7500 feet (2275 meters) from the controller.
  •     Supports various I/O modules: Works with standard IC697 discrete and analog I/O modules, PCM, ADS, and analog expander modules.
  •     Handles large input/output capacities: Manages up to 128 bytes of inputs and 128 bytes of outputs per remote drop.
  •     Easy configuration: Configurable using MS-DOS programming software or an IC66* Hand-held Monitor.
  •     Bus redundancy support: Works with both CPU and IC66* bus redundancy.
  •     Multiple racks: Supports up to eight racks per remote drop, with a Remote I/O Scanner located in rack 0.
  •     High scalability: Up to 30 remote drops can be connected on the same IC66* bus.

Module Description:
The Remote I/O Scanner is housed in a single slot with a faceplate that includes several connectors for communication. It does not require a battery for operation.

LED Indicators:

  •     Module OK: Lights up when the module passes its power-up diagnostic tests. If this LED flashes, a problem is detected.
  •     I/O Enabled: Lights up when the Remote I/O Scanner is receiving output data from the CPU. If it blinks, there is a conflict or forced I/O data.
  •     Bus B Active: In dual-bus (redundant) configurations, this LED indicates when Bus B is active.

Installation and Configuration:

  •     Rack installation: The Remote I/O Scanner should be installed in rack 0, slot 1 of a remote drop. For expansion, a Bus Transmitter can be placed in any slot of rack 0, and a Bus Receiver in slot 1 of each additional expansion rack.
  •     Bus connections: The module can be connected to a single or dual IC66* bus using appropriate terminals. In dual-bus configurations, bus termination resistors must be installed at the end of the bus.
  •     Configuration: The module can be configured using MS-DOS programming software or an IC66* Hand-held Monitor. Configuration includes assigning device numbers, setting baud rates, and specifying starting references for inputs and outputs.

Technical Specifications:

  • Current Required from +5V Bus: 0.8 Amps
  • Bus Type: Daisy-chained bus cable (twisted pair + shield or Twinax)
  • Maximum Cable Length: 7500 feet (2275 meters) at 38.4 Kbaud
  • Baud Rate: Configurable: 153.6 Kbaud, 76.8 Kbaud, 38.4 Kbaud
  • Number of Devices per Bus: Up to 32 devices at 153.6 Kbaud
  • Ports: One 15-pin RS-422/485 serial port, one 9-pin Hand-held Monitor port

Ordering Information:

  • IC697BEM733/735: Remote I/O Scanner Module
  • IC600WD Cable: Available in various lengths for connection