IC697MDL752

12 Volt DC 0.5 Amp, 32-Point Output Module

    32 output points, divided into four isolated groups of 8 points each
    0.5 amp capacity per point
    High inrush capacity (20 times the rated current)

The 12 Volt DC 0.5 Amp Output Module provides 32 output points across four isolated groups, each containing 8 points. The module supports high inrush currents, making it suitable for various loads with such characteristics. LED indicators at the top of the module display the ON-OFF status of each output on the PLC side.

This module is mechanically keyed to ensure correct field replacement, and I/O references can be configured by the user without the need for jumpers or DIP switches.

Configuration is performed using the MS-DOS or Windows programming software. The software runs on Windows 95 or Windows NT over Ethernet TCP/IP or through the SNP port. The programming device can be an IBM-compatible XT, AT, or PS/2 personal computer.


Output Characteristics:

This module is compatible with a wide variety of load devices, such as:

    Solenoids
    Motor starters
    Indicator lamps

The maximum long-term current capacity for each point is 0.5 amps. Due to the overall heat dissipation within the module, the maximum current for each group of 8 outputs is limited to 2 amps.

Each output on this module is capable of conducting transient surge currents that are much greater than its long-term rating. The frequency at which such surges can occur depends on the current rating of the device and its duty cycle (the percentage of time the device is ON).


Steady-State Current (mA)    Repetition Rate (Hz)
100    5.0
250    1.0
500    0.1


Fault Mode Selection:

This module can be configured to determine how output points respond to certain conditions. Two options are available:

    Maintain existing output state
    Turn outputs OFF

For more detailed configuration information, refer to the applicable Programming Software User’s Manual.


Fusing:

The 12 VDC 0.5 Amp Output Module does not have internal fuses. If protection is required, the user can externally connect fuses as specified below:

    Littlefuse 312.750 (3/4 amp, 250 volt, Fast Acting)
    Bussmann AGC-3/4 (3/4 amp, 250 volt, Fast Acting)


Mechanical Keying:

This module includes a mechanical key to prevent the incorrect insertion of another module type into its slot. The key fits into a uniquely shaped area on the board below the connector. The key remains in place when the module is removed, ensuring that only identical module types can be reinserted.


Field Wiring:

The module is wired as shown in Figure 2. Each group of 8 outputs is isolated from the others, so a power input wire must be connected to each group (the power input terminals are not connected inside the module). The detachable field wiring terminal board accepts wire sizes from AWG #22 (0.36 mm²) to AWG #14 (2.1 mm²).


Removing an I/O Module:

    Firmly grasp the top and bottom of the module cover.
    Squeeze the clips at the back to disengage the module from the rack.
    Slide the module out along the card guide.


Technical Specifications:
Parameter    Specification
    Rated Voltage    12 volts DC
    Outputs per Module    32 (four groups of 8 outputs each)
    Isolation    1500 volts to backplane, 500 volts between groups
    Output Voltage Range    10 to 15 volts
    Output Current    0.5 amps maximum per point
    Inrush Current    10 amps maximum for 20 ms
    Output Voltage Drop    1 volt maximum (2 ohms)
    Response Time (On/Off)    1 ms typical
    Output Leakage Current    1 mA maximum
    Current from 5V Bus    0.25 amps


This module is ideal for industrial applications requiring a wide voltage range and high inrush current capacity.



>> GE Fanuc IC697MDL752 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697MDL752 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."