IC697MDL340

120 Volt AC 2 Amp, 16-Point Output Module IC697MDL340

    16 output points divided into four isolated groups of 4 points each
    2 amp capacity per point
    High inrush current capacity (10x the rated current)

The 120 Volt AC 2 Amp Output Module provides 16 output points, grouped in four isolated sets of 4 points each. This setup allows each group to be used with different phases of the AC supply. Each group is protected by an individual 10-amp fuse.

The module can handle high inrush currents, making it suitable for a variety of inductive and incandescent loads. It is also capable of operating larger contactors, such as size 4 contactors.

LED indicators display the ON/OFF status of each point on the logic (PLC) side, and there is an additional LED for fuse status, all located at the top of the module.

The module is mechanically keyed to ensure correct replacement with a similar type. I/O references can be configured without using DIP switches or jumpers.


Operation:

The module is configured via MS-DOS or Windows programming software, which can run on Windows 95 or Windows NT. Configuration can be done over Ethernet TCP/IP or through the SNP port. The programming device can be an IBM PC or a compatible system.


Output Characteristics:

The 120 Volt AC 2 Amp Output Module is compatible with various load devices, including:

    Solenoids and motor starters
    Indicators

The 2-amp rating per point applies to the continuous current capacity. The total current capacity per group is limited to 4 amps due to heat dissipation within the module.

Each output can handle surge currents that exceed its long-term rating. The frequency of these surges depends on the current rating and the duty cycle (the percentage of time the device is ON). For incandescent loads operating at a 50% duty cycle, the following repetition rates apply:


Steady-state Current (amps)    Repetition Rate (Hz)
0.5    5
1.0    1
2.0    0.1


Fault Mode Selection:

The module can be configured so that output points respond to fault conditions by either:

    Maintaining the existing output state
    Turning all outputs OFF

Fusing:

Each group of 4 outputs is protected by a 10-amp fuse, which can be replaced with the following types:

    3AG - 10 amp, 250V, Fast Acting
    Metric 5 x 20 mm - 10 amp, 250V, Fast Acting

Mechanical Keying:

This module is keyed to prevent incorrect module installation. The key fits a unique area on the board below the connector, and once installed, it remains latched onto the backplane’s center rail. If the module needs to be moved, the key can be unlatched and moved along with the module.


Field Wiring:

Each group of four outputs is isolated from the others, requiring a separate power wire for each group. The detachable field wiring terminal board accepts wire sizes from AWG #22 (0.36 mm²) to AWG #14 (2.10 mm²). Two wires of the same size can be terminated on a single lug.


Removing an I/O Module:

To remove the module:

    Grasp the board at the top and bottom.
    Squeeze the rack clips to disengage the module from the rack rail.
    Slide the module out along the card guide.

Specifications:
Parameter    Value
Rated Voltage    120 volts AC
Outputs per Module    16 (four groups of four outputs each)
Isolation    1500 volts (any output to backplane), 500 volts between groups
Output Voltage Range    85 to 132 volts, 47 to 63 Hz
Output Current    2 amps max per point, 4 amps max per group
Inrush Current    20 amps max for one cycle (20 ms)
Voltage Drop    3 volts max
Response Time (On)    1 ms max
Response Time (Off)    1/2 cycle
Leakage Current    1.5 mA max
Current Required from 5V Bus    0.25 amps

This module's robust design makes it ideal for industrial environments requiring reliable AC output control with high current capabilities.



>> GE Fanuc IC697MDL340 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697MDL340 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."