The IC697MDL653 is a 24 Volt DC input module with both positive and negative logic compatibility, providing 32 input points arranged into four isolated groups of eight points each. This module is designed for use with Programmable Logic Controllers (PLCs) and meets IEC standards for input current-voltage characteristics. It supports proximity switches and features a selectable input filter and interrupt functionality.


Key Features:

    32 input points: Organized into four isolated groups of eight inputs each.

    Positive/Negative Logic Compatibility: Can handle both types of logic, making it versatile for various applications.

    Proximity switch compatibility: Works with both 2-wire and 3-wire proximity switches.

    Selectable input filter: Configurable between 1ms or 10ms, depending on the requirements.

    Interrupt capability: One input (A1) can be configured to generate an interrupt signal for the CPU.


Technical Specifications:

    Rated Voltage: 24 volts DC.

    Inputs per Module: 32 inputs (four groups of eight).

    Input Isolation: 1500 volts between input and backplane, and 500 volts between input groups.

    Input Voltage Range: -3V to +30V DC.

    Input Current: 10mA typical at rated voltage.

    Input Impedance: 2.6K ohms typical.

    On-state Voltage: 13.5V to 30V DC.

    On-state Current: 6mA to 15mA.

    Off-state Voltage: 0V to 5V DC.

    Off-state Current: Up to 2mA leakage current (2mA minimum at 5V input).

    Filter Delay: Configurable to either 1ms or 10ms.

    Current from 5V Bus: 0.30 amps.

    VME Compatibility: Supports the VME standard for system integration.


Input Characteristics:

This module supports both positive and negative logic by sourcing or sinking current from the input device to the user common. It is compatible with pushbuttons, limit switches, selector switches, and electronic proximity switches.

    2-wire and 3-wire proximity switches: The module is optimized for 3-wire proximity switches with low ON-state voltage drop and low OFF-state leakage current, but 2-wire proximity switches can also be used with careful evaluation of ON and OFF states.


Input Filter Selection:

    The input filter can be set to 1ms or 10ms, depending on the system's requirements. This filter applies to all input points and ensures stable signal processing in noisy environments.


Interrupt Configuration:

    Input point A1 can be configured as an interrupt input to signal the CPU when a rising or falling edge is detected. This interrupt capability can be useful in real-time control applications and is independent of the input filter time.


Mechanical Keying:

The module features a mechanical key to prevent incorrect insertion into the wrong slot. Once installed, the key latches onto the backplane rail to ensure that only identical module types can be installed in the same slot. The key can be removed and reinserted if the module needs to be relocated.


Removal Instructions:

    Firmly grasp the module at the top and bottom of the cover.

    Squeeze the rack clips at the back to disengage the module from the rail.

    Slide the module along the card guide and remove it from the rack.


Practical Tips:

When using this module, consider whether you need the 1ms or 10ms filter setting based on the noise levels in your environment. For interrupt-driven applications, configure input A1 accordingly to handle rising or falling edge signals, and ensure that the proximity switches or other input devices meet the current-voltage compatibility requirements.


>> GE Fanuc IC697MDL653 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697MDL653 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."