IC697MDL652
The IC697MDL652 12 Volt DC Positive/Negative Logic, 32-Point Input Module is designed for industrial automation systems, offering compatibility with both positive and negative logic. The module provides 32 input points organized into four isolated groups, each with 8 inputs. It meets IEC standards for input current-voltage characteristics and is compatible with proximity switches. Additionally, it features configurable input filtering and interrupt capabilities.
Key Features:
32 input points: Organized into four isolated groups of 8 points each.
Positive/Negative Logic Compatibility: Operates with both positive and negative logic.
Proximity switch compatibility: Compatible with both 2-wire and 3-wire proximity switches.
Selectable input filter: Configurable between 1ms or 10ms.
Interrupt feature: Input point A1 can be configured to trigger a CPU interrupt.
Technical Specifications:
Rated Voltage: 12 volts DC.
Inputs per Module: 32 inputs (four groups of 8 inputs).
Input Isolation: 1500 volts from input to backplane, 500 volts between input groups.
Input Voltage Range: -2.5V to +15V DC.
Input Current: Typically 4.7mA at rated voltage.
Input Impedance: 1.12K ohms typical.
On-state Voltage: 7.5V to 15V DC.
On-state Current: 6mA to 15mA.
Off-state Voltage: 0V to 2.5V DC.
Off-state Current: Up to 2.5mA leakage current (2mA minimum).
Filter Delay: Configurable to 1ms or 10ms.
Current Required from 5V Bus: 0.30 amps.
VME Compatibility: Supports the VME standard.
Input Characteristics:
This module supports both positive and negative logic, allowing it to source or sink current from the input device to the user common. It is compatible with pushbuttons, limit switches, selector switches, and electronic proximity sensors.
3-wire proximity switches: Ideal due to their low ON-state voltage drop and low OFF-state leakage current.
2-wire proximity switches: Require careful evaluation as they tend to have higher ON-state voltage and OFF-state leakage current.
Input Filter Selection:
The module provides a selectable input filter with options for 1ms or 10ms delay. This configuration applies to the entire module and ensures stable signal processing, particularly in noisy environments.
Interrupt Configuration:
Input point A1 can be configured to generate a CPU interrupt on the rising or falling edge of a signal transition. This interrupt functionality is independent of the input filter time and is useful for real-time control applications.
Mechanical Keying:
The module is mechanically keyed to prevent incorrect insertion into the wrong slot. Once installed, the key latches onto the backplane rail, ensuring only identical module types can be inserted into that slot. The key can be removed and reinserted if needed for relocation.
Removal Instructions:
Firmly grasp the top and bottom of the module cover.
Squeeze the rack clips at the back to disengage the module from the rail.
Slide the module along the card guide and carefully remove it from the backplane connector.