IC697MDL254

48 Volt AC, 32-Point Input Module - IC697MDL254

The IC697MDL254 is a 48-volt AC input module providing 32 input points, divided into four isolated groups of eight points each. This setup allows each group of inputs to be used on a different AC supply phase.

Key Features

    32 Input Points: Four isolated groups of eight points each.

    20 ms Input Filter: Ensures stable signal processing.

    Proximity Switch Compatibility: Compatible with both 2-wire and 3-wire proximity switches.

    LED Status Indicators: Displays the ON/OFF status for each point.

    Mechanical Keying: Prevents incorrect module installation.

    Software Configurable I/O References: Configuration is completed through MS-DOS® or Windows® programming software over Ethernet TCP/IP or SNP port.

Functions

The IC697MDL254 input module is designed to work with various input devices, such as:

    Pushbuttons, limit switches, and selector switches.

    Electronic proximity switches: Compatible with both 2-wire and 3-wire devices.

The input circuitry provides enough current to ensure the reliable operation of the switching devices. Typical input current is 4.7mA in the ON state, and the module can accept up to 2mA of leakage current in the OFF state without activating. The module also supports mechanical keying to prevent the incorrect installation of a different module type.

For 3-wire proximity switches, there is typically low voltage drop in the ON state and minimal leakage in the OFF state, making them highly compatible. For 2-wire proximity switches, which derive their power from the signal connection, there may be higher ON state voltage and OFF state leakage. The module is compatible with many 2-wire devices, but each device must be evaluated for compatibility in both states.

Module Power and Keying

The IC697MDL254 requires 0.30 amps from the 5-volt bus on the backplane. The module includes mechanical keying, which ensures the proper module is installed in the designated slot. The key fits into a unique area on the board and locks onto the backplane center rail when first installed.

Field Wiring

The module supports detachable field wiring, with each group of eight inputs being isolated from the others. A wire from the power source must be connected to the power input terminal for each group (terminals 10, 20, 30, and 40). The terminal board can accommodate wire sizes from #22 to #14, and two wires of the same size may be terminated on a single lug. A bundle of up to 40 #14 wires can be routed through the terminal board cavity and secured with a cable tie.

Technical Specifications

    Rated Voltage: 48 VAC, 47 to 63 Hz (Sinusoidal).

    Number of Inputs: 32 (four groups of eight inputs each).

    Isolation: 1500V RMS (input to backplane), 500V RMS (between input groups).

    Input Current: 4.7mA (typical) at rated voltage.

    Input Impedance: 10.3K ohms (typical).

    On-state Voltage: 33 to 56 volts RMS, 47 to 63 Hz (Sinusoidal).

    Off-state Voltage: 0 to 10 volts RMS, 47 to 63 Hz.

    On-state Current: 3mA to 7mA.

    Off-state Current: 0 to 2mA.

    Filter Delay Time: 20ms (typical).

    Current Required from 5VDC Backplane Bus: 0.3 amps.

The IC697MDL254 module is designed to support the VME standard C.1 and meets relevant product standards and regulations for industrial installations. It can be used in systems requiring compliance with more stringent requirements, such as FCC or European Union directives.

This module is ideal for applications requiring reliable 48V AC input with flexible phase separation, proximity switch compatibility, and easy field wiring.

>> GE Fanuc IC697MDL254 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697MDL254 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."