IC697MDL251
IC697MDL251 is a 120 Volt AC input module that provides 16 input points organized into four isolated groups, each containing four points. This design allows for flexibility, as each group can be connected to different phases of the AC power supply. The module is designed to meet IEC standards and is compatible with a wide range of proximity switches, making it versatile for industrial automation applications.
Key Features:
16 input points: Organized into four isolated groups of four points each.
20 ms input filter: Ensures stable signal processing and reduces noise interference.
Proximity switch compatibility: Works with both 2-wire and 3-wire proximity switches.
LED Indicators: Each input point has an LED indicator to show its ON-OFF status on the logic side (PLC).
Mechanical keying: Prevents incorrect module placement and ensures the correct type is used in the field.
Technical Specifications:
Rated Voltage: 120 VAC, 47 to 63 Hz sinusoidal.
Input Isolation: 1500 volts RMS from any input to the backplane, and 500 volts RMS between input groups.
Input Current: Typical input current is 10mA at rated voltage, with ON-state current ranging from 6mA to 15mA.
Input Characteristics:
ON-state voltage: 75 to 132 volts AC.
OFF-state voltage: 0 to 25 volts AC.
OFF-state current: Can sink up to 3mA (with 2.2mA minimum at 25V input).
Filter Delay: Typical delay time is 20ms to filter input signals.
Power Consumption: Requires 0.35 amps from the 5V bus on the backplane.
VME Compatibility: The module supports the VME standard for expanded system compatibility.
Installation and Field Wiring:
Field Wiring: The terminal board accepts wire sizes from #22 AWG to #14 AWG, and allows two wires of the same size to be terminated on one lug. Wiring for each group of four inputs is isolated, requiring a power source connection to each group individually (terminals 10, 20, 30, or 40).
Wire Bundling: The wire bundle can be neatly secured to the terminal board using cable ties, ensuring organized and safe connections.
Mechanical Keying:
The module includes a mechanical key that ensures it is correctly inserted into the appropriate slot. If the key latches into the backplane rail, it configures the slot to accept only identical module types. If necessary, the key can be removed and relocated to a different module slot.
Removal Instructions:
Firmly grasp the top and bottom of the module's cover.
Squeeze the rack clips on the back to disengage them from the rack rail.
Pull the module out of the backplane connector, sliding it along the card guide.
Practical Tips:
When installing this module, ensure that each group of four inputs is properly isolated and that each group has its own power source. Proper wire bundling and securing help maintain clean, reliable installations. For environments with electrical noise, take advantage of the 20ms input filtering feature to maintain signal integrity.
>> GE Fanuc IC697MDL251 User manual (pdf)
----------