IC697RCM711
Redundancy Communications Module (RCM) - IC697RCM711
The Redundancy Communications Module (RCM) provides high-speed communication between the primary and secondary PLCs in Hot Standby and Enhanced Hot Standby CPU redundancy systems in the IC697 series. This module enables the transfer of shared I/O data and synchronization messages between the two CPUs, ensuring system reliability and availability.
High-Speed Parallel Bus Expansion Interface: Ensures fast and efficient data transfer between primary and secondary systems.
Supports Hot Standby and Enhanced Hot Standby Configurations: Compatible with both standard and enhanced redundancy systems.
Data and Message Synchronization: Transfers shared I/O data and synchronizing messages between the primary and backup units.
Five LED Indicators: Displays board status and system health.
Manual Control Pushbutton: Allows manual switching from the active CPU to the backup CPU.
Software Configurable: Configured using MS-DOS programming software.
Functions
The RCM is responsible for synchronizing two CPUs in Hot Standby and Enhanced Hot Standby configurations by providing a communication path between them. It also facilitates the transfer of shared I/O data between the primary and backup units. The physical connection between the two units can extend up to 25 feet (7.5 meters) using appropriate interconnecting cables.
Supported CPUs: Compatible with IC697CPU780, IC697CGR935, and IC697CGR772 models.
Module Installation: Occupies a single slot and can be installed in slots 2 through 9 of rack 0 (CPU rack).
Status Indicators
The RCM module features five green LED indicators that provide real-time status updates on the module's and system's health:
BOARD OK: Lit when the module is powered, configured correctly, and has no communication errors.
LOCAL READY: Indicates the local system is ready for operation.
LOCAL ACTIVE: Shows that the local system is currently the active CPU.
REMOTE READY: Indicates the remote (backup) system is ready.
REMOTE ACTIVE: Shows the remote system is currently active.
Manual Control Pushbutton
The module has a pushbutton that allows for a manual switch from the active CPU to the backup CPU. To initiate the switch, the button must be held for at least 1 second and then released. After a switch, the system requires at least 10 seconds before another switch can be performed.
Installation Process
Installation should be done following the guidelines in the Hot Standby CPU Redundancy User’s Guide and the appropriate Programmable Controller Installation Manual.
Steps for Installation:
Power Off the System: Ensure that the rack power is turned off before installing the module.
Slot Installation: Insert the RCM into any available slot in rack 0, except slot 1.
Cable Connection: Connect the appropriate cable (IC697CBL811 or IC697CBL826) to the module.
Power On: Turn on the power and verify the LED status indicators to ensure the module is functioning properly.
Expansion and Cable Management
I/O Bus Termination: The RCM should be installed at the end of the expansion bus, connected using a terminated cable (catalog numbers IC697CBL811 or IC697CBL826). This setup allows for easy module replacement without disturbing the expansion bus.
Expansion Rack Attachment: Use IC600WDXXX cables to connect a Bus Transmitter Module (BTM) in the CPU rack to a Bus Receiver Module (BRM) in an expansion rack. Additional racks are daisy-chained, with the RCM always connected last in the chain.
Removing the Module
To remove the module:
Firmly Grasp the top and bottom of the module's cover.
Squeeze the Rack Clips to release the module from the rack.
Slide the Module out along the card guide and carefully remove it from the rack.
LED Indicators and Manual Switching
The five LED indicators provide critical feedback on the status of the redundancy system. The Unit Selection Pushbutton allows for manual switching between active and backup CPUs.
Ordering Information
Redundancy Communications Module: IC697RCM711
Supported CPU Modules for Hot Standby: IC697CPU780, IC697CGR772, IC697CGR935
Bus Transmitter Module: IC697BEM713
Terminator Plug: IC697ACC702
I/O Cable: Available in lengths of 5 feet (1.5m), 10 feet (3m), 25 feet (7.5m), and 50 feet (15m) (IC600WD005/010/025/050)
I/O Cable with Built-In Termination: IC697CBL811 (10 feet), IC697CBL826 (25 feet)
For more details and installation guidance, refer to the Hot Standby CPU Redundancy User’s Guide or the Enhanced Hot Standby CPU Redundancy User’s Guide.
>> GE Fanuc IC697RCM711 User manual (pdf)
----------
+ Ge-Fanuc Contact (for Automation Mall)