IC697CMM742

The Ethernet Interface (Type 2) module (IC697CMM742) connects the IC697 PLC to an IEEE 802.3 Ethernet LAN for communication and data exchange. Below is a summary of its key features and functions:

   Ethernet Connectivity: Provides a direct connection to a 10 Mbps Ethernet LAN via three network ports:
        10BaseT (RJ-45) for twisted-pair network connection
        10Base2 (BNC) for ThinWire coaxial cable connection
        AUI (15-pin D-connector) for attachment to various Ethernet media (e.g., 10Base5, 10BaseF) via a user-supplied transceiver
   Direct Connection without External Transceiver: The 10BaseT and 10Base2 ports allow direct connections without requiring external transceivers.
   Automatic Port Selection: The Ethernet Interface automatically selects the active network port. Only one port is used at a time.
   Preloaded Firmware: The firmware is pre-installed for easy setup and maintained indefinitely. It can be upgraded from a PC via the RS-485 serial port.

Supports Multiple Functions:
        Ethernet Global Data (for data exchange using configuration-based and logic-based data)
        TCP/IP Communications using the SRTP protocol
        Full PLC programming and configuration services
        Comprehensive management and diagnostic tools

Functions:

The IC697CMM742 Ethernet Interface (Type 2) enables high-performance TCP/IP communications for the IC697 PLC. It plugs into a single slot in the PLC rack and is configured using IC641 PLC programming software. Up to four Ethernet Interface modules can be installed in a single PLC system.

The Ethernet Interface supports communication with host computers running the Host Communications Toolkit, CIMPLICITY software, or MS-DOS/Windows-based programming software via the SRTP and Ethernet Global Data protocols. These communications occur over a 4-layer TCP/IP stack.

Supported Ethernet Media:

   10Base5 Coax: Thick coaxial cable (500m max length, up to 100 stations)
   10Base2 Coax: ThinWire coaxial cable (185m max length, up to 30 stations)
   10BaseT: Twisted-pair cable (100m max length, typically used in a star topology)
   10BaseF: Fiber optic cable (supports distances up to 500m or 2000m, depending on the variation)
   10Broad36: Broadband coaxial cable (supports distances up to 2800m)

Physical Description:

   LED Indicators: The front panel includes four LED indicators:
       MODULE OK: Indicates module status.
       LAN ONLINE: Shows network connectivity and activity.
       SERIAL ACTIVE: Indicates activity at the RS-485 serial port.
       STATUS: Displays the module’s overall operational status.

    These LEDs help in troubleshooting and show various states, such as data transfer, maintenance mode, and waiting for an IP address.

   Network Ports: The module has the following network ports:
       10BaseT (RJ-45)
       10Base2 (BNC)
       AUI (15-pin D-connector)

   Serial Ports: Two serial ports are provided for configuration and diagnostics:
       RS-232 for direct connection to a PC for management
       RS-485 for software loading or other services

   Restart Button: The Restart pushbutton serves multiple purposes, including restarting the module, entering the software load state, and performing LED tests.

Module Indicators and Restart Functions:

The four LEDs on the module provide feedback on the operational status. For example, if the MODULE OK LED is on, it indicates normal operation. If the LAN ONLINE LED is blinking, it means the Ethernet Interface is actively transferring data over the network.

The Restart pushbutton can be used to:

   Perform an LED test by pressing it briefly.
   Restart the module by pressing it momentarily (less than 5 seconds).
   Enter the software load state by holding the button for 5-10 seconds.
   Enter the maintenance state by holding it for more than 10 seconds.

Service Option Connector:

The module includes a Service Option connector, which allows a Lithium battery (IC697ACC701) to be connected to preserve log data if the module is removed from the PLC rack. Without the battery, the log is preserved for 2-3 days.

This module is essential for Ethernet-based communication in industrial environments, offering flexibility through various media support and providing reliable performance for data exchange and network connectivity.



>> GE Fanuc IC697CMM742 User manual (pdf)

++ Other 90-30 PLC modules

----------

+ Ge-Fanuc 2 Homepage

+ Ge-Fanuc Contact (for Automation Mall)

+ About Ge-Fanuc

Reminder: GE Fanuc IC697CMM742 and other Ge-Fanuc modules are available for sale at Otomasyon Mall. Please note that some of the devices are used products, so take this into consideration when purchasing. However, once products are out of stock, new ones will not be restocked. The information above is based on general knowledge and does not guarantee accuracy. For more detailed and precise information, it is recommended to refer to the relevant device’s user manual. 06.03.2013 

"Please note: The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."