IC697CMM711
Communications Coprocessor Module (CMM) - IC697CMM711
The Communications Coprocessor Module (CMM) provides high-performance communication capabilities for IC697 PLC systems. It supports several communication protocols, including SNP, CCM, and RTU, and allows communication with remote devices via its dual serial ports.
Single-Slot Module: Installs easily into an IC697 PLC rack.
Multiple Protocols Supported:
SNP/SNP-X: Master and slave modes.
CCM: Master, slave, and peer-to-peer communication.
RTU Modbus: Slave mode only.
MS-DOS/Windows Software Support: Monitor communications with the PLC.
12 MHz 80C186 Microprocessor: Ensures efficient data handling.
Dual Serial Ports: Compatible with both RS-232 and RS-422/RS-485 protocols.
Simultaneous Communication: Supports communication on both ports at up to 19.2 Kbps.
Three Status LEDs: Indicate operational status and port activity.
Reset Pushbutton: For quick restart of communication processes.
No Configuration Switches: Soft-switch configuration via software.
No Battery Required: Simplifies maintenance.
Functions
The CMM module provides several modes of communication:
CCM Mode:
Provides read/write access to PLC memory, including registers, inputs, and outputs (%R, %I, %Q).
Supports ladder logic program communication requests (COMREQs).
Operates in master, slave, or peer mode, allowing data exchange with remote devices.
RTU Mode:
Implements a query/response protocol for communication between the CMM and a host computer.
The host is the master, sending queries to the CMM, which operates in slave mode.
Supports reading/writing input/output tables, registers, and exception status.
SNP/SNP-X Mode:
SNP is the native protocol for IC69* PLCs.
Allows the CMM to act as either a master or slave in communication with other PLCs or SNP devices.
Provides access to various PLC memory types, such as %R, %I, %Q, %AI, and %AQ.
Supports the SNP-X extension, which enhances performance for high-speed data acquisition.
Installation & Configuration
Installation:
Ensure the rack power is OFF before installation.
The module plugs into a single slot in the IC697 PLC or I/O rack.
Turn on the power after installation, and the top LED should blink during diagnostics and remain on if successful.
Configuration:
The CMM must be configured using the MS-DOS or Windows programming software.
There are no hardware DIP switches or jumpers, so all settings are adjusted via the configuration software.
Serial Ports
The CMM has two serial ports, each of which can be configured for RS-232 or RS-422/RS-485 communication.
Both ports can operate simultaneously, allowing for full-duplex data transfer.
RS-232 Port Pinouts:
Pin 2: Transmitted Data (TD)
Pin 3: Received Data (RD)
Pin 4: Request To Send (RTS)
Pin 5: Clear To Send (CTS)
Pin 7: Signal Ground (0V)
RS-422/RS-485 Port Pinouts:
Pin 9: Send Data (A) (SD(A))
Pin 13: Receive Data (A) (RD(A))
Pin 21: Send Data (B) (SD(B))
Pin 25: Receive Data (B) (RD(B))
LED Indicators
Module OK: Indicates the operational status of the module.
Port 1 & Port 2 LEDs: Indicate data transfer or communication activity on each port.
Restart Pushbutton
A restart button is available to reinitialize the communications on both serial ports. Hold the button for less than 5 seconds for a simple restart, or for more than 5 seconds to reset to factory default settings.
This module offers flexible communication options for IC697 PLC systems, making it a vital tool for applications that require serial communication with external devices.