IC697ALG320
High-Level Analog Output System - Voltage/Current Module IC697ALG320
High-level analog voltage and current outputs on a single module.
Four output channels, each individually configurable for voltage or current.
Supports unipolar or bipolar analog voltage outputs up to ±10 volts full scale.
Provides 0 to 22.5 milliamp current loop signals.
User-defined scaling for each output channel.
Fast update rate for quick responsiveness.
Factory-calibrated with data stored in non-volatile EEPROM memory.
No jumpers or DIP switches for user configuration.
Easy configuration using MS-DOS or Windows programming software over Ethernet TCP/IP or SNP port.
System Operation:
The high-level analog output system converts digital data from the CPU into analog signals. These signals are outputted as up to ±10 volts for voltage or 0 to 22.5 mA for current loop signals. Each output can be configured for either voltage or current but not both simultaneously. Outputs are protected against transient and steady-state overvoltage conditions.
Resolution: 16 bits, with 14-bit monotonicity.
Isolation: Outputs are electrically isolated from the backplane.
Output Memory: Each output channel uses one 16-bit word in %AQ memory.
Field Wiring and Power Supply:
Connections to user devices are made through screw terminals on a removable 40-terminal connector block. For current output, a separate user power supply is required. Voltage outputs are powered from the PLC backplane. Shielded, twisted instrumentation cables are recommended for wiring to reduce noise interference.
Key Specifications:
Output Ranges:
Voltage: ±10V, 0 to +10V, ±5V, 0 to +5V.
Current: 4 to 20 mA.
Power Supply Requirements: User-supplied power for current outputs (e.g., a 24V supply for loads between 200-550 ohms).
Channel-to-Channel Compliance: Allows up to 0.5V DC difference between output channels, preventing ground loop errors.
Common Mode Voltage: Up to ±60V from ground potential.
Module Configuration:
Configuration is done using MS-DOS or Windows software, allowing the user to select output ranges, scaling points, and fault reporting options for each channel.
Fault Reporting: Fault conditions such as overrange, underrange, and open wire can be detected.
Scaling: Allows user-defined scaling of output signals. For instance, a default scaling range for current might be 4-20mA, and for voltage, ±10V.
Output Default Mode:
In the event that CPU communication is lost or during power-up, the outputs can be configured to either hold the last state or revert to a user-defined default value.
Recommended Field Wiring Procedures:
Use shielded, twisted-pair instrumentation cables for wiring outputs to prevent noise interference.
Ensure that power is off when installing or removing the terminal board.
The terminal board can accept wire sizes ranging from AWG #22 to AWG #14.
Summary of Configurable Features:
Feature Channel or Module Selections Default Setting
Voltage/Current ±10V, 0-10V, 4-20mA ±10V
Report Faults Enabled/Disabled Enabled
Scaling Points User Value ±32767 +20000, -4000 µA
Output Default Hold Last State/Off Off
Default Value Range ±32767 0
This module provides flexible and reliable analog outputs with high resolution and configurable options, making it suitable for various industrial automation and control applications.