IC697ALG441
Voltage Expander Module - IC697ALG441
Diagnostic Capabilities for the High-Level Analog Input System:
LED Indicators on Modules: For system status indication.
Monitoring Health of Base Converter and Expander Modules.
Detection of Configuration Errors.
Monitoring Communication Between Base Converter and Expander Modules.
Overrange and Underrange Detection.
Open Wire Detection.
Monitoring of High and Low Alarm Limits.
Expander Channel Not Responding.
Module LEDs:
There are two LEDs on the Base Converter module and one LED on each Expander module.
Base Converter Module:
BOARD OK LED: Flashes when the module powers up and passes its diagnostic tests. It remains on if the configuration data from the CPU is correct, and turns off if there is a configuration error.
PORT OK LED: Turns on when communication with one or more Expander modules is established. It indicates that the expansion bus is operating properly. If no configured expansion channels are responding, this LED turns off.
Expander Modules:
LED: Flashes when the Base Converter is waiting for configuration data. The LED turns on when the Expander module is configured and turns off if a module failure is detected.
Analog Input Diagnostics:
Alarm Comparator Function: Used to trigger special processing when an input signal exceeds a specified operating range. High and low thresholds can be set to define the desired operating range.
Alarm Contacts: When the scaled input value crosses the configured thresholds, the corresponding high (–[HIALR]–) or low (–[LOALR]–) alarm contact is activated.
Alarm Interrupts: When an alarm is triggered, an interrupt block is activated in the CPU, which allows the logic to determine which alarm occurred by examining the input data.
Input Overrange and Underrange Faults:
Overrange Fault: Occurs when the scaled input exceeds the maximum range (e.g., greater than 32767).
Underrange Fault: Occurs when the scaled input falls below the minimum range (e.g., less than –32767).
Open Wire Detection: Triggered when the input current in 4–20 mA mode drops below 2 mA.
Configuration Errors:
User Scaling Error: Occurs if the user-defined scaling points fall outside the valid range of signed 16-bit data.
Expander Module Configuration Error: Occurs when the Expander module’s range or number of channels does not match the configuration.
Analog Signal Terms:
Single-Ended: Signals measured relative to a common reference point, often the power supply.
Differential: Signals measured across two separate wires, reducing errors from ground currents.
Isolated: Signals electrically isolated from power supplies and grounds, allowing high