IC697ALG440
Base Converter Module - IC697ALG230, Current Expander Module - IC697ALG440
Complete Analog Subsystem: Includes Base Converter and Expander modules.
Base Converter Module: Has eight differential inputs that can be individually configured for voltage or current.
Unipolar/Bipolar Analog Inputs: Accepts signals up to ±10 volts full scale.
Current Input Support: Accepts 4 to 20 milliamp current loop signals.
User-Defined Scaling: Each input channel on the Base Converter module can be individually scaled; Expander modules are scaled on a per-module basis.
Fast Update Rate: The Base Converter module features a fast update rate.
Expander Modules: Each Expander module provides 16 inputs, allowing for additional inputs at a lower cost per point.
Maximum Inputs: The complete subsystem can support up to 120 inputs.
No Jumpers or DIP Switches: Configuration is easy and done through programming software, either MS-DOS or Windows.
Functions:
The High-Level Analog Input Subsystem for the PLC (Programmable Logic Controller) can accept analog inputs up to ±10 volts or 4 to 20 mA current loop signals. These inputs are converted to digital signals for use by the CPU or other controllers via the VME backplane.
Conversion: Inputs are converted to 2’s complement format with a resolution of 14 bits, further enhanced by oversampling techniques.
Input Protection: The system protects against transient and steady-state overvoltage conditions.
Field Wiring: Wiring is done through a removable terminal block, and mechanical keying ensures correct module replacement.
Module Types:
Base Converter Module (IC697ALG230):
Supports eight differential inputs.
Configurable for voltage or current input.
Features individual user scaling for each channel.
Includes on-board load resistors for typical input ranges, like ±10V or 4 to 20 mA, with external resistors available for other ranges.
Expander Modules:
Daisy-chain up to seven Expander modules off the Base Converter for a total of 120 inputs.
Each Expander module has a common scaling factor, configurable individually per module.
Current Input Expander Module (IC697ALG440): Provides 16 additional inputs for current signals.
Removing an I/O Module:
Grasp the board at the top and bottom of the cover.
Squeeze the rack clips to disengage from the rack rail.
Slide the board out along the card guide.
Field Wiring Considerations:
Connections: Field connections are made to a 40-terminal removable connector block. Use high-quality twisted, shielded cables to minimize noise interference.
Grounding: Ground connections (GND) should be used to connect shields, with best results achieved when the ground is near the rack.
Differential Inputs: Both input lines should be connected to the signal source for optimal noise rejection.
Current Inputs: For current signals, an internal shunt converts the 4 to 20 mA signal to a 1 to 5-volt signal.
Expansion Bus:
The expansion bus, consisting of terminals 35 through 40 on the Base Converter and Expander modules, allows daisy-chaining of Expander modules.
Analog Multiplexer: The Expander module uses a multiplexer to connect inputs to the Base Converter’s A/D converter.
Shielding: Connect shields on both ends of the bus for optimal noise rejection.
Input Sampling Technique:
The system’s input sampling method prioritizes the Base Converter’s eight channels for fast updates while Expander channels are updated sequentially, ensuring that all channels in the system are scanned.
Base Channel Update Rate: 2.4 milliseconds.
Expander Channel Update Rate: Increases as the number of Expander modules increases.
User Scaling:
This feature allows for custom scaling of input signals into engineering units. By default:
Current Inputs: 0 to 32,000 for a range of 4 to 20 mA.
>> GE Fanuc IC697ALG440 User manual (pdf)
----------