IC697ALG230
IC697ALG230 Base Converter Module, IC697ALG440 Current Expander Module, IC697ALG441 Voltage Expander Module
Analog Modules
Datasheet: GFK-0385F
Date: August 1997
Introduction
The Series 90-70 Analog Input System includes the Base Converter Module (IC697ALG230) and Expander Modules (IC697ALG440 and IC697ALG441). These modules are designed to accept analog inputs in the range of ±10 volts full scale or 4 to 20 milliamp current loop signals, converting them to digital form for use by the CPU or other controllers via the VME backplane.
Features
- Complete Analog Subsystem: Includes Base Converter and Expander Modules
- Eight differential inputs on the Base Converter Module, configurable for voltage or current
- Supports unipolar and bipolar analog inputs up to ±10V
- Accepts 4 to 20 mA current loop signals
- Individual user scaling on each Base Converter input; scaling on a per-module basis for Expander Modules
- Fast update rate on the Base Converter Module
- Voltage and Current Expander Modules (16 inputs each) provide additional inputs at lower cost per point
- The complete subsystem supports up to 120 inputs
- No jumpers or DIP switches required for configuration
- Easy configuration via MS-DOS or Windows software
Functions
The High-Level Analog Input System for the Programmable Logic Controller (PLC) accepts analog inputs up to ±10 volts full scale or 4 to 20 mA signals. These inputs are converted to digital form and stored in %AI memory for use by the CPU or other controllers. The Base Converter Module has 14-bit resolution, with oversampling and averaging enhancing the effective resolution.
Inputs are protected against transient and steady-state overvoltage conditions. Each input uses one word (16 bits) of %AI memory. The system supports up to 8K words of %AI memory. Configuration is performed through the MS-DOS or Windows programming software.
High-Level Analog Input System Modules
The system includes the following module types:
- Base Converter Module (IC697ALG230): This module features eight differential inputs, configurable for voltage or current. Each input channel supports individual user scaling. On-board load resistors handle normal input current ranges up to ±40 mA. External resistors can be used for other ranges or resolutions.
- Current Expander Module (IC697ALG440): This module features 16 current inputs, each accepting up to ±20 mA signals.
- Voltage Expander Module (IC697ALG441): This module features 16 differential voltage inputs, each accepting up to ±10V signals.
Up to seven Expander Modules can be daisy-chained to the Base Converter Module, allowing for a total of 120 inputs in the complete system. Expander modules accept both current and voltage types. A common scaling factor applies to all inputs on each Expander module, and scaling can be adjusted individually for each module.
Configuration and Field Wiring
- The system configuration is easy, with no jumpers or DIP switches. Configuration is handled through MS-DOS or Windows software over Ethernet TCP/IP or via the SNP port.
- Field wiring is done to a removable terminal board, ensuring easy replacement of modules without reconfiguring wiring. The modules are keyed for correct insertion and replacement in the field.
Standard System Configurations
The standard configurations for the system include support for ±10V voltage inputs and 4 to 20 mA current inputs. Additional configurations and lower input ranges can be set using the system's scaling feature, allowing the conversion of inputs into engineering units.
System Key Points
Supports up to 120 total inputs with the Base Converter and Expander modules
Provides 14-bit resolution with oversampling for enhanced accuracy
Protects against overvoltage conditions
Easy configuration with user-defined scaling and software-based setup
>> GE Fanuc IC697ALG230 User manual (pdf)
----------
+ Ge-Fanuc Contact (for Automation Mall)