IC693MDL734
IC693MDL734 - 125 Volt DC Positive/Negative Logic Output Module (1 Amp, 6 Points)
This module is designed for the Series 90-30 PLC system and provides 6 isolated output points. Each output point has a separate common terminal. The module can operate with either positive logic (sourcing current to the loads from the user common or positive power bus) or negative logic (sinking current from the loads to the user common or negative power bus). It is compatible with a wide range of devices such as motor starters, solenoids, and indicators. The power to operate the field devices must be supplied by the user.
Key Features:
6 isolated output points, each with its own common terminal.
Works with either positive or negative logic, meaning it can source or sink current depending on the application.
Compatible with motor starters, solenoids, indicators, and other user-supplied devices.
Requires a user-supplied power source to operate the field devices.
LED Indicators:
Green LEDs at the top of the module indicate the ON/OFF status of each output.
The first 6 LEDs, labeled A1 through A6, display the status of the outputs.
An insert is placed between the inside and outside surfaces of the hinged door, which provides circuit wiring information. The module is color-coded red on the outside edge to indicate it is a high-voltage module.
External fusing is recommended. If 2-amp loads are needed, two outputs can be wired and driven in parallel.
Technical Details:
Rated Voltage: 125 volts DC.
Output Voltage Range: +10.8 to +150 volts DC.
Isolation:
1500 volts between the field side and logic side.
500 volts between outputs.
Output Current:
1 amp maximum per point.
Inrush Current: 15.89 amps for 10 ms.
Output Voltage Drop: Maximum of 1 volt.
Off-state Leakage: Maximum of 1 mA.
On/Off Response Time:
On: Maximum of 7 ms.
Off: Maximum of 5 ms.
Power Consumption:
Draws 90 mA from the 5-volt bus on the backplane when all outputs are ON.
This module is ideal for systems requiring positive or negative logic DC output control at 125 volts DC. It can be installed in any I/O slot of a 5 or 10-slot baseplate in a Series 90-30 PLC system, offering flexibility and reliable operation. External fuses are recommended, and for driving 2-amp loads, two outputs can be wired in parallel.
>> IC693MDL734 User manual (pdf)
----------