6EW1110-5AB
Siemens 6EW1110-5AB System Power Supply
Siemens 6EW1110-5AB is a legacy system power supply in the 6EW1110-5 code family. The manufacturer’s S5-150A family instructions describe 24 V DC input converted to a 5 V system supply. Maintenance must distinguish its control-electronics supply function from the machine’s separate field-load supply.
It appears within the SITOP power supply and Siemens 6EV / 6EW model sections. When using SIMATIC S5 documentation, preserve the 5AB suffix and hardware revision. Establish this exact unit’s output-current rating separately; a rating found for 5AC or 5AE must not be assigned directly to 5AB.
Supply arrangement in the manufacturer’s family manual
The 6EW1110-5 family table in the S5-150A instructions gives a nominal 24 V DC input with a 20–30 V DC range, and a 5 V system output with a 5.1 V standard setting. These are family-document values. Match the actual 5AB nameplate, connections and document revision before using them as full-load or adjustment limits.
On the low-voltage system rail, assess load current and connection losses together. Preserve the rack connector, common reference and protective grounding according to the machine diagram. The 24 V input and 5 V system output serve different functions.
UAN and IAN measurement sockets
The family manual identifies UAN for output voltage and IAN for monitoring output current, with an IAN scale of 10 mV = 1 A. Where the actual front panel and circuit match this arrangement, use a suitable multimeter on DC millivolts; 30 mV represents 3 A on that scale. Do not draw load current from these sockets or short them through an ammeter.
Compare the supply output with the voltage reaching the CPU and memory boards. For intermittent CPU stops, investigate voltage fluctuations and connector losses. By Ohm’s law, 5 A through a 10 mΩ contact resistance produces a 0.05 V drop. This calculation illustrates connection losses on a 5 V system; it is not a prescribed test current.
Load testing and fault isolation
Plan full-load testing only after establishing the actual 5AB current limit. Record input voltage, output behaviour, load and temperature together. Exclude a downstream short circuit or an excessively demanding system board before condemning the power supply.
If the input fuse opens, do not increase its rating or repeatedly reapply power. After isolation and measurement confirming discharged stored voltage, inspect the power circuit, connections and diodes. A DC-input system still presents high-current and stored-energy hazards.
For delayed cold startup or unstable warm operation, electrolytic capacitors, solder joints and connectors are inspection candidates. Capacitance and ESR checks supplement visual inspection. Raising a voltage regulation adjustment to conceal poor contact can damage system boards. These are general service suggestions, not documented recurring 5AB faults.
Indicators and memory backup
The family document describes green Stromversorgung klar for supply status and yellow Pufferung gestört for a backup fault. Lastspannung fehlt concerns field-load voltage monitoring. Confirm the actual 5AB’s indicators and monitoring options against its front panel and circuit.
The manual describes a NiCd backup arrangement. Secure program and data backups before battery work, and match the battery chemistry to the charging circuit. Do not remove or insert the complete power supply while energized. Procedures for the battery module must not be confused with removal of the complete unit.
Related codes and used-unit selection
6EW1110-5AA, 6EW1110-5AC and 6EW1110-5AE have separate model records. A shared prefix or similar housing does not establish full electrical and mechanical interchangeability. Compare output capability, monitoring options, backup arrangement and connectors.
When selecting a used power supply, request a clear 6EW1110-5AB nameplate, front-panel and rack-connection photographs, and repair history. Establish whether testing was performed without load, with a controlled load or in the host system. Ask for current and duration rather than relying on a general statement that it works.
Editor’s Note
Start with a clear 5AB nameplate and revision. A neighbouring model’s current rating is not a sound basis for a full-load test. Resolve any nameplate and document mismatch before judging capacity.
Check the power path when the CPU stops. Voltage may be correct at the supply but fall at a board because of contact loss. Measure both points before changing an adjustment; do not compensate for a poor connector with excessive voltage.
An IAN socket is not a power output. Once the matching measurement arrangement is confirmed, its millivolt signal can indicate current. Do not short a test socket through a directly connected ammeter.
For a yellow backup warning, secure the program backup first. A leaking NiCd module warrants inspection of contacts and nearby tracks as well as the battery. Do not substitute another chemistry without verifying the charging circuit.
Capacitors and solder joints are inspection candidates for delayed cold startup, not an instruction to replace parts indiscriminately. Isolate power and verify discharge before component measurements. Record load, temperature and test duration after repair.
For a used unit, inspect rack connectors, missing covers, corrosion, burn marks and earlier repair work. Establish the conditions of the operating check; a no-load reading provides different evidence from testing in the host system.
OtomasyonAVM Resources and PDFs
Browse the Siemens 6EV / 6EW model pages and the Siemens SITOP files document index.
+ SIMATIC S5-150A Central Controller Operating Instructions — German PDF. C79000-B8500-C227-2; 25 PDF pages, 9.36 MiB. Family specifications: PDF 8 / printed 6; connections: PDF 9 / printed 7; indicators: PDF 11 / printed 9. This is a family reference; it does not establish the rated current for the complete 5AB order number. The outer cover belongs to an S5-150K binder; the internal C227-2 section concerns S5-150A.
Related Topics
Multimeter measurements + Ohm’s law + Capacitors + Protective grounding
Used equipment enquiries: Provide the model, quantity, working/faulty condition, nameplate photographs and price. Sales require an invoice; returns are not accepted for used products. Workshop testing can be arranged with an agreed scope. To offer equipment for sale, send details and photographs to otomasyonavm@gmail.com.
Browse Siemens Power Supplies
Siemens second-hand equipment + SITOP power supplies + 6EV / 6EW models + SIMATIC S5 + Used power supplies
Siemens and External References
+ Siemens S5-150A family instructions — manufacturer document hosted by SPS-Service