Siemens 6EV3054-0CC is a system power supply used with SINUMERIK 3 / SIROTEC controls, with a 24 V DC input and a main 5 V DC / 25 A output. It supplies control electronics. Maintenance should distinguish the control-card supply from the machine’s separate field-load supply.

The manufacturer’s nameplate shows the 6EV 3054-0CC order number and U1 = 5 V, I1 = 25 A output rating. It appears in the Siemens SITOP power supply and 6EV / 6EW model sections on OtomasyonAVM. This is a plug-in legacy system supply; preserve the rack interface and hardware revision when selecting a replacement.

Supply ratings and system connections

The nominal input is 24 V DC; the main output is 5 V DC at 25 A. Multiplying output current by voltage gives 5 × 25 = 125 W for that output; this calculation does not establish total input consumption. Distinguish input and output ratings carefully. Never connect 230 V AC directly to the 24 V DC input.

Preserve the rack reference, connectors and grounding according to the machine drawings. Match the actual type label before applying the manual’s 03500 family information. The inspected 0CC example carries a 03502 type marking; do not assume every revision has identical monitoring and connection details.

Front-panel measurement sockets

The inspected front panel has +5 V, M and Nominal Current 25 A ≙ 10 V markings. The indicated current-monitoring scale therefore equals 0.4 V/A; a 4 V signal corresponds to 10 A. This calculation applies only to a unit bearing that scale. Use a suitable multimeter for DC voltage measurement; these sockets must not supply a 25 A load or be shorted with an ammeter.

Measure both the supply output and the voltage reaching the control card. Investigate connectors, backplane connections and wiring when a voltage drop is present. At 10 A, a contact resistance of 10 mΩ causes a 0.1 V loss under Ohm’s law. This illustrates connection losses in a 5 V system; it is not a prescribed test current.

Fault isolation and controlled-load testing

For a CPU that fails to start or stops intermittently, record the input, output behaviour and voltage fluctuations together. Exclude a rack card drawing excessive current or causing a short circuit before condemning the supply alone. Prevent unintended axis movement during testing.

If a fuse opens, do not increase its rating; investigate why it failed. After disconnecting power and verifying that stored voltage has been safely removed, inspect power components, diodes, solder joints and capacitors. These are general service inspection points, not verified recurring faults specific to this model.

Apply load gradually using suitable wiring, connections and a controlled load. Observe voltage regulation during cold start and warm operation. Do not raise the 5 V setting to compensate for poor contacts. Apply a manufacturer service setting only after matching the system and measurement conditions.

Related order numbers and used-unit selection

6EV3054-0DC, 6EV3054-0FC and 6EV3054-0GC have separate model records. Matching main-output ratings do not establish direct interchangeability. Compare suffix, hardware revision, rack connections, monitoring arrangements and any auxiliary supplies.

When selecting a used power supply, request clear nameplate, front-panel and connector photographs plus repair history. A useful test report identifies load current, measured output, duration and thermal behaviour. Getting the CNC running again does not by itself verify every supply function.

Editor’s Note

First check that the 24 V input remains stable under load. A weak upstream source or connection can make a healthy module appear faulty. Record the input and system-side measurements together.

Do not underestimate contact losses on a 5 V rail. Repair hot, loose or discoloured contacts before adjusting the output. Raising the setting can expose other boards to unnecessary voltage.

Keep the current-monitoring socket separate from the power output. “25 A ≙ 10 V” is a measurement scale. Read it with a DC voltmeter; do not draw load current or bridge it with an ammeter.

Test cold and warm behaviour separately. For delayed starting, noise under load or thermal shutdown, measure and inspect solder joints, capacitors and power connections. Confirm the fault before replacing components indiscriminately.

Back up programs and machine data before removal. Legacy CNC supplies, RAM and backup arrangements may be linked. Verify battery chemistry and charging arrangements before replacement; do not insert or remove the module while energized.

Complete the test in a compatible system. Under safe conditions, record start-up, load and thermal behaviour together with monitoring functions. These are general service recommendations, not claims of recurring model-specific faults.

Documents and PDF Resources

Browse our Siemens SITOP files document index and the Siemens 6EV / 6EW model pages.

Siemens SINUMERIK System 3 – Service Manual Part 1. English, edition 12/85, 320 pages, 15.79 MiB. Document number: E80210-T147-X-A-7600. System service instructions for versions 0–3. Supply checks: PDF pages 71–72, printed pages 4-2 and 4-3. Use as a family service reference, not an exact 0CC datasheet.

Related Topics

6EV3054-0DC + 6EV3054-0FC + 6EV3054-0GC + 6EV3114-0AE00-0AA0 monitor supply. The last link illustrates a different supply function; these models are not all interchangeable.

Used equipment enquiries: Provide the brand, full model, quantity, working/faulty condition, nameplate photographs and price. Sales require an invoice; returns are not accepted for used products. Workshop testing can be arranged with an agreed scope. To offer equipment for sale, send details to otomasyonavm@gmail.com.

Browse Siemens Power Supplies

Siemens second-hand equipment + SITOP power supplies + 6EV / 6EW models + Used power supplies + SITOP PDF files

External References

Siemens manufacturer service manual – original scan hosted by Drivesul

6EV3054-0CC manufacturer nameplate and front-panel photographs – WM Industrietechnik