6EV1363-5AK

Siemens 6EV1363-5AK — 380 V Three-Phase AC / 24 V DC, 40 A Power Supply

Siemens 6EV1363-5AK is an external power supply with a 380 V three-phase AC input and a 24 V DC / 40 A output. The Siemens SINUMERIK 880 connection manual lists the complete order number. Used within an external supply arrangement for CNC control equipment, this power supply requires electrical and mechanical checks when selecting a replacement.

It appears in our Siemens 6EV / 6EW model directory and SITOP catalogue group. Verify 6EV1363-5AK on the nameplate; do not transfer detailed specifications from 6EV1362-5BK00 or another 40 A model. Matching output current does not establish matching input connections or protection behaviour.

380 V three-phase AC input

The manufacturer’s table specifies 380 V, three-phase AC. Assess input voltage using phase-to-phase measurements and the wiring diagram. Inspect upstream contactor contacts and fuses as well. Do not infer 400 V or 415 V compatibility from the 380 V nominal value alone; verify the actual nameplate and permitted input range separately.

24 V DC / 40 A output and power calculation

40 A is the current rating on the 24 V DC output side. It is not the mains input current or an input-fuse rating. Using nominal values, 24 V × 40 A = 960 W; this is an output-power calculation. Actual input consumption and losses cannot be established from that product alone. Assess protective earthing and DC-reference connections against the machine drawing.

No-load and loaded measurements

Record DC output with a multimeter separately at no load and under a defined load. Observe startup and load changes too. A nominal 24 V rating does not establish voltage tolerance or a ripple limit. Investigate voltage fluctuations together with load behaviour, incoming power and connection losses.

By Ohm’s law, 40 A through 0.01 Ω of connection resistance produces a 0.4 V drop and 16 W of heating. Small increases in cable, lug or terminal resistance therefore matter. Compare supply output and load input under the same operating load; do not hide a connection loss with an adjustment.

Progressive load testing

A 2.4 Ω load across 24 V draws approximately 10 A and dissipates 240 W. This is a partial-load example at one quarter of the 40 A rating. Use an adequately cooled electronic load or a load bank with suitable power margin. A full 40 A test needs 960 W of nominal load capacity, with measuring leads and connections selected accordingly.

Fault investigation and repair

If output is absent or falls under load, check the incoming phases, connections and external load first. Do not repeatedly energise equipment with a suspected short circuit. Before internal inspection, isolate all energy sources and verify absence of voltage. Live mains-side measurements require qualified personnel and suitable measuring equipment.

Rectifier diodes, power connections, thermal interfaces and any fitted filter capacitors are general diagnostic candidates. They are not a confirmed recurring-failure list for this model. Narrow down the fault through measurements before replacement; do not guess fuse ratings, semiconductor types or capacitor values.

Used-equipment and application checks

When buying a used power supply, inspect identification, revision, input connections, output terminals and cooling arrangements. Request the condition of power-supply connection accessories and a recorded load test. For use with used CNC control equipment, assess the total 24 V demand, startup requirements and protection arrangement; the 40 A marking alone is insufficient for replacement selection.

Editor’s Note

Confirm that all three phases actually reach the supply. Power at the cabinet incomer does not prove that every downstream connection is sound. Check phases, fuse holders and contactor contacts using appropriate methods. An upstream contact problem should be resolved before searching for failed internal parts.

A 40 A output does not call for an arbitrary 40 A input fuse. Select incoming protection from the nameplate and manufacturer’s instructions. Protect downstream load distribution separately. If a fuse opens, investigate the short circuit or wiring fault rather than trying a larger fuse.

Do not certify the supply from a no-load reading. Observe output under load and record current and duration. A 10 A trial is not a 40 A capacity test. When voltage drops, assess incoming power and cable losses alongside the supply.

Small contact faults can produce substantial heat at this current. Inspect discoloured lugs, loose terminals and damaged contact surfaces. Restore connections to the manufacturer’s torque and conductor requirements; excessive tightening is not a remedy. Recheck loaded voltage drop and thermal behaviour.

Narrow down the fault before repair. Check rectifiers, fitted filter components and power connections. Replacing a discoloured part is not a reason to apply full load immediately. A continuing load or contact fault can damage the replacement. Perform internal work only after isolation and absence-of-voltage verification.

Give the load bank proper attention. Even the 10 A example dissipates 240 W. Resistive testing needs adequate cooling, cables and secure connections. Full load approaches 1 kW, so preparation and the test record must reflect that level.

OtomasyonAVM Resources and PDF

Browse the 6EV1363-5AK model page and Siemens 6EV / 6EW used-model directory.

Siemens SITOP files — our common document page for this project.

Siemens SINUMERIK 880 — Interface Description, Part 2: Connection Conditions (English, 05.91, 6ZB5 410-0HF02, 218 pages, approximately 5.91 MiB). Section 7.3, printed page 7–7 / PDF page 177 identifies 6EV1363-5AK with a 380 V three-phase input and 24 V DC / 40 A output.

Documentation scope: This manual confirms basic product identification; it is not a detailed service schematic. Input tolerance, frequency range, output regulation, IP rating, terminal numbers and protection thresholds are not assumed here. Check these against the nameplate or manufacturer documentation for the complete code and revision.

Related Topics

Related reading: multimeter measurements, voltage fluctuations, fuses and earthing.

Browse Siemens and Power Supplies

+ Siemens second-hand catalogue

+ Siemens 6EV / 6EW models

+ Used power supplies

+ CNC control systems

External References

Siemens — SINUMERIK 880 Connection Conditions — manufacturer’s original PDF server.