6EV1336-5AK

Siemens 6EV1336-5AK External Power Supply

The OtomasyonAVM model record identifies Siemens 6EV1336-5AK as an external power supply with a three-phase 380 V input and 24 V DC / 10 A output. This record helps identify the equipment; verify connection and commissioning ratings against the actual unit's manufacturer nameplate and its own documentation.

This Siemens automation model is listed in our SITOP power supplies section. Alongside the general information on the about Siemens SITOP page, power supply selection requires the complete order number, input arrangement, load demand and mechanical installation details.

Assessing the input, output and load

Distinguish the AC input voltage from the DC output. The 10 A current in the model description refers to the output, not the input current. For a unit with 24 V and 10 A confirmed on its nameplate, the nominal output calculation is 240 W. This calculation does not establish input consumption or capacity at every temperature.

When checking a three-phase input, assess every phase pair and the connections. Investigate possible phase loss or voltage fluctuations under load as well. Suitability of equipment described as 380 V for a 400 V supply requires a verified permissible input range. Mains-side measurements require qualified personnel and suitable equipment.

Connections and output measurements

Identify the DC output reference before using a multimeter. Assess protective grounding and the output common against the wiring diagram. Inspect connectors for looseness, oxidation and heat damage; do not infer terminal numbers or bridges from another model.

Connection resistance can cause voltage loss and heating between the source and load. Compare supply-output and load-input readings under the same conditions. Whether the output is regulated, and its permissible ripple, require separate verification; a “24 V” description alone does not guarantee precision regulation.

Repair and testing under load

With power isolated, inspect any fuse, connections and possible short circuits. After establishing the circuit arrangement, assess diodes and capacitors through measurements. Do not treat a blown fuse by replacing it alone, or guess its rating and characteristic.

After verifying the input and connections, test using an appropriate load arrangement. Record DC output, ripple, load current, test duration and temperature. Keep unloaded and loaded results separate. Set acceptance limits against the model documentation and connected equipment's requirements; general power supply standards information does not constitute model approval.

Related models and replacement selection

The Siemens 6EV / 6EW range includes separate records for 6EV1320-4AC, 6EV1322-7AK00, 6EV1352-5BK00 and 6EV1363-5AK. These links do not establish direct interchangeability. Compare the input phase arrangement, every output, load capacity, connections and mounting together.

Editor's Note

Do not end the assessment because the unloaded output looks correct. If the output falls, check what the input is doing at the same time. The cause may be inside the supply, in its upstream wiring or in the connected load.

On a three-phase unit, one phase-pair reading does not establish a healthy mains supply. Have every phase and connection checked under suitable conditions. A capacitor replacement will not correct a missing phase.

Before replacing a rectifier or capacitor, establish the circuit arrangement and measure the fault. Look beyond capacitance or current alone; consider voltage, temperature, ripple-current capability and mounting requirements.

Raising the supply adjustment to compensate for connector or cable losses can put the load at risk. Find the connection loss first. Inspect connections that heat up as load increases.

When buying used equipment, establish the load and duration of the test. Cold-start and warmed-up results may differ. Check the complete code, nameplate and test scope before deciding suitability.

OtomasyonAVM Resources and PDF

Use the 6EV1336-5AK main page and Siemens SITOP files for model and series resources.

+ Siemens SIMATIC S5-130 / S5-150 — ST 53, 1985, German family catalogue

Document scope: Section 11/1, PDF page 135 of this 144-page Siemens catalogue, provides an overview of 6EV1 load power supplies. 6EV1336-5AK is not listed in that table. Do not transfer neighbouring models' input tolerances, output ranges or connections to this unit. A manufacturer data sheet for the exact code remains to be verified.

Related Topics

Phase-loss checks + Voltage fluctuations + Multimeter measurements + Capacitors

Used-equipment enquiries: Provide the brand, complete model, quantity, working/faulty condition, clear nameplate photographs and price. Sales are invoiced; returns are not accepted for used equipment. Workshop testing can be arranged with a defined scope. To offer a unit for sale, send its details to otomasyonavm@gmail.com.

Browse Categories

Siemens automation + SITOP power supplies + Siemens 6EV / 6EW models + SITOP PDF archive

Siemens and External References

+ Siemens ST 53, 1985 — original manufacturer catalogue hosted in a distributor archive