6EV1320-4AC

Siemens 6EV1320-4AC — 220 V AC / 24 V DC, 4.4 A Non-Stabilized Power Supply

Siemens 6EV1320-4AC is described in catalogue records as a non-stabilized power supply with a single-phase 220 V AC input and a +24 V DC / 4.4 A output. For older Siemens automation equipment, assess this power supply using the complete code, original nameplate and the load’s permitted voltage range. Apply this basic catalogue description within the documentation scope stated below.

The product appears in our Siemens 6EV / 6EW model directory and SITOP navigation group. Read 6EV1320-4AC from the nameplate; do not assume that a version with additional suffix characters or digits is identical. Match mounting, connections and electrical requirements separately when selecting a replacement.

Meaning of a non-stabilized supply

An unregulated output should not be treated as a source that maintains exactly 24.00 V at every load. Output can vary with incoming voltage and loading. Assess rectifier-based supplies using average DC level, ripple and load behaviour together. The nameplate’s 24 V is a nominal voltage; no minimum or maximum limit is assumed here for this complete code.

Single-phase 220 V AC input

The catalogue description specifies 220 V, single-phase AC. Before using it on 230 V, verify input tolerance and any primary-connection selection from the original markings or relevant manufacturer documentation. Inspect the incoming fuse, contactor contact and terminals. Do not guess mains terminal assignments; live measurements require qualified personnel and suitable equipment.

4.4 A output and power calculation

The listed 4.4 A belongs to the 24 V output side, not the input current or input fuse. Nominal values give 24 V × 4.4 A = 105.6 W. This is an output-power calculation, not input consumption or losses. Use actual measured output voltage in test calculations based on Ohm’s law.

No-load and loaded checks

Use a multimeter to measure input and DC output under defined conditions, then increase loading progressively and record the results. One no-load reading is insufficient for a health assessment. For voltage fluctuations, a meter’s AC range does not necessarily provide an accurate ripple reading; consider the measurement method and instrument bandwidth.

At 24 V, a 12 Ω load draws approximately 2 A and dissipates 48 W. Use a resistor with adequate power margin or a cooled electronic load. If unregulated output voltage rises, current and heating in the same resistor increase too. Avoid selecting a marginal load bank based solely on an assumed 24 V; a 2 A trial is not a 4.4 A capacity test.

Load compatibility and replacement

Check the voltage limits of connected relay coils, sensors and other electronic loads individually. When considering a modern regulated replacement, compare startup demand, protection behaviour, common references and mounting as well as continuous current. Do not parallel supplies or raise the output without documented suitability.

Repair and fault investigation

Do not repeatedly energise equipment with a suspected short circuit. Isolate all energy sources and verify absence of voltage. Rectifier diodes, connections and any fitted filter capacitors can be examined through measurements. These are general servicing suggestions, not confirmed recurring failures of this complete model.

Inspect the unit’s transformer and connections for thermal damage, loose terminals and insulation deterioration; do not alter winding connections or primary selection by guesswork. Check protective earthing continuity too. Adding arbitrary capacitance to increase capacity can change startup current and stress on other components.

When buying a used power supply, request complete nameplate photographs, revision, terminal condition and a recorded load test. Assess connection accessories, cooling and mounting requirements as well. A catalogue entry or representative illustration does not prove that a particular sale item has been tested.

Editor’s Note

Do not condemn an unregulated supply merely because it does not read 24.00 V at no load. Record input voltage and loading first. Observe how output changes with load and establish permitted limits from the actual nameplate and relevant documentation. Do not copy another model’s voltage range.

Apply the 4.4 A figure to the correct side. Catalogue records give it for the output. Do not select the input fuse from that number. Resolve any difference on the actual unit’s markings before full-load testing; match the catalogue record and physical hardware together.

Do not assume a 230 V connection is suitable. Check primary markings, any selection link and the allowed range. A wrong winding connection or loose terminal must be addressed before looking elsewhere. Mains-side work requires qualified personnel and appropriate equipment.

Use measurements to guide repair. Check rectifiers, connections and any fitted filter capacitor. A clean appearance does not prove health, and parallel paths can affect in-circuit readings. Repeated fuse replacement without identifying the cause is not diagnosis.

More capacitance is not automatically better. Establish the original circuit first. Arbitrary additions can increase startup current and rectifier stress. Match capacitance, voltage, temperature and current characteristics when replacing components, then verify operation under load.

Calculate test loading from actual voltage. The 12 Ω example dissipates 48 W at 24 V; a higher voltage produces more heat. Provide suitable cooling and connections. Record current, duration and output behaviour; a 2 A trial is not a 4.4 A test report.

OtomasyonAVM Resources and PDFs

Browse the 6EV1320-4AC model page and Siemens 6EV / 6EW used-model directory.

Siemens SITOP files — our common document page for this project.

Siemens SIMATIC S5-130 / S5-150 — ST 53, 1985 (German, reprint with 5.85 amendments, 144 pages, approximately 15.3 MiB). Printed page 11/1 / PDF page 135 provides family context for unregulated 6EV1 load supplies. It does not list 6EV1320-4AC; neighbouring models’ tolerances are not transferred to this unit.

TPCOVN / Thinh Phat Industrial Automation — Siemens parts list (predominantly English, 94 pages, approximately 2.21 MiB; edition date not stated). PDF page 40 lists the complete code as non-stabilized, 220 V single-phase / +24 V, 4.4 A. This is a third-party parts list, not a Siemens datasheet.

Documentation scope: A detailed manufacturer datasheet for the complete order number was not obtained. Basic identification remains at catalogue-record level. Establish circuit details, terminal numbers, input tolerance, frequency range, output ripple and protection thresholds from original markings or model-specific manufacturer documentation.

Related Topics

Related reading: rectifiers, transformers, capacitors and multimeter measurements.

Browse Siemens and Power Supplies

+ Siemens second-hand catalogue

+ Siemens 6EV / 6EW models

+ Used power supplies

+ Power-supply main page

External References

Siemens ST 53 — manufacturer catalogue archived by ADEGIS

TPCOVN — original third-party parts list

ADEGIS — 6EV1320-4AC catalogue record

BVS Electronics — 6EV1320-4AC catalogue record