6ES7 195-7HF80-0XA0
Siemens Main Menu › SIMATIC S7 › ET 200 Modules
Siemens 6ES7 195-7HF80-0XA0 — BM DP/PA / BM FDC Active Bus Module
6ES7 195-7HF80-0XA0, identified as BM DP/PA or BM FDC in Siemens documentation, is an active backplane bus module for one compatible coupler. When reviewing Siemens ET 200 products, identify this base separately from the coupler mounted on it. This component belongs among bus connection modules and bases; it does not independently perform DP/PA communication conversion.
System use and compatibility
BM FDC is used in approved DP/PA Link and FF Link combinations. For example, the FF Link manual lists it alongside FDC 157 / 6ES7157-0AC84-0XA0. When selecting PROFIBUS and other communication interfaces, distinguish DP/PA couplers from FOUNDATION Fieldbus couplers. Sharing a bus base does not make those couplers interchangeable.
Differences between 7HF80, 7HG80 and 7HD80
6ES7195-7HF80-0XA0 / BM FDC accommodates one coupler. 6ES7195-7HG80-0XA0 / BM FDC/FDC serves a redundant coupler pair, while 6ES7195-7HD80-0XA0 / BM IM/IM is the interface-module base. When comparing SIMATIC S7 system components, mark each module and its required base on the station layout instead of relying on similar order numbers.
Five checks before selection
1. Station function: Review the ET 200 system architecture together with the installed Link arrangement. Record the interface, coupler and bus-base codes separately; the front device label does not identify the base underneath.
2. Mounting rail: An FF Link configuration with active bus modules requires the special rail for module replacement during operation. Check the rail profile and connections between adjacent modules. Include damaged contacts when inspecting terminal blocks and connection hardware.
3. Redundancy: Two interface modules do not necessarily mean two couplers. Identify which component is redundant and assess which field devices would lose communication if a single coupler were removed.
4. Supply and environment: Compare the power supply modules, power distribution arrangement and industrial power supply with the station schematic. The FF Link manual specifies −25…+60 °C horizontally and −25…+40 °C vertically for these components. Assess the temperature inside the cabinet.
5. Post-replacement checks: Monitor station diagnostics and field-device status through the PLC and HMI system. Verify that process values update again as well as checking the physical connections.
Editor’s Note
Replacement during operation does not permit every component to be removed while energized. The FF Link manual requires disconnecting the FDC 157’s own 24 V DC supply before removal. Replacing a single coupler interrupts its connected FF devices. Do not apply the coupler replacement procedure to the underlying bus module; plan maintenance for the specific component being replaced.
PDF manuals and installation documents: Visit the Siemens ET 200 manuals and PDF documents page. In FF Link, A5E35651245-AB, 03/2015, section 5.3 covers installation, section 9.2 covers FDC replacement and Appendix A.1 lists order numbers. For DP/PA applications, also check the approved combinations in the applicable DP/PA Coupler, DP/PA Link and Y Link manual.