6ES7 195-1GA00-0XA0

Siemens Main Menu › SIMATIC S7 › ET 200 Modules

Siemens 6ES7 195-1GA00-0XA0 — ET 200M Active Bus Module Mounting Rail, 482.6 mm

6ES7 195-1GA00-0XA0 is a 482.6 mm mounting rail for ET 200M stations in the Siemens ET 200 family. It supports active bus modules used for the removal and insertion function. The rail provides mechanical support; it does not independently communicate or process I/O signals.

The rail and the active bus module

This rail forms the mechanical foundation for the relevant ET 200 connection modules. Active bus modules are selected separately, while network communication requires a suitable PROFIBUS or PROFINET interface. Installing this rail does not make every module hot-swappable. Check the interface version, active bus arrangement, hardware configuration and replacement instructions for the specific module.

Technical construction and similar rails

Length: 482.6 mm. Height: 122 mm. Material: Aluminum. Surface: Galvanically tin-plated. Cabinet planning must also account for the depth of installed modules, cable ducts and access for maintenance.

The standard S7-300 rail 6ES7390-1AE80-0AA0, listed among SIMATIC S7 hardware products, is also 482.6 mm long. Equal length does not establish suitability for active bus mounting. Siemens identifies 6ES7195-1GA00-0XA0 separately for active bus modules. Use the complete order number instead of specifying only a “482 mm Siemens rail.”

Other lengths in this active bus rail group include 530 mm: 6ES7195-1GF30-0XA0, 620 mm: 6ES7195-1GG30-0XA0 and 2000 mm: 6ES7195-1GC00-0XA0. Select the length from the station layout; a longer rail alone does not increase the permitted module count.

Five checks before selection

1. Station arrangement: Review the ET 200 system architecture to confirm the subfamily, interface order number and active bus configuration. Do not assume ET 200S or ET 200SP bases fit this rail.

2. Total space required: Include the ET 200 power supply modules, interface and I/O modules in the layout. Active bus options such as BM 2×40 and BM 1×80 serve different module widths; module count alone is insufficient for calculating space.

3. I/O inventory: Record the full order numbers of the digital input modules, digital output modules and analog input modules. A product appearing in one of these categories does not automatically establish compatibility with this ET 200M arrangement.

4. Wiring access: Check clearance for removing front connectors and reaching the terminal and field connections. A rail fitting inside the cabinet does not guarantee sufficient maintenance space for the wired station.

5. Mechanical condition: Inspect straightness, mounting holes and module retention surfaces. Prepare fastening and protective grounding according to the Siemens installation instructions; separately confirm which bus modules and covers are included in the delivery.

Editor's Note

The decisive detail is the correct rail profile for active bus modules, before length alone. Record the existing rail code, bus module arrangement and cabinet dimensions together. The removal and insertion function does not authorize removing the rail from an energized station. Plan rail replacement with the station in a safe state and the relevant supplies disconnected.

PDF and installation information: Use ET 200M Operating Instructions, EWA-4NEB780600602-08 alongside the resources on our Siemens ET 200 manuals and PDF documents page. Section 4.2.4 describes active bus installation; Appendix B lists rail and accessory order numbers.