6ES7 133-0BH01-0XB0
6ES7 133-0BH01-0XB0 – Siemens ET 200B 8DI/8DO Digital Input/Output Module
6ES7 133-0BH01-0XB0 is the ET 200B-8DI/8DO electronics block in the Siemens ET 200 family. It combines eight 24 V DC digital inputs and eight 24 V DC solid-state outputs. The module exchanges digital input and digital output data with the controller over PROFIBUS DP.
Supply and input characteristics
The nominal supply is 24 V DC, with an operating range of 18.5–30.2 V DC. Input thresholds are −30 to +5 V for “0” and 13–30 V for “1”. Siemens’ 2019 data sheet specifies a 2–3 ms input delay for the transition from 0 to 1. Comparing the sensor output with these thresholds is useful when investigating unstable input signals.
Output current and load selection
The limit is 0.5 A per output, with a 2 A total limit for the group of eight. The outputs have electronic short-circuit protection. Loading all eight channels at 0.5 A simultaneously would draw 4 A and exceed the group limit. Check individual loads and calculate the combined current of those that can operate at the same time.
When selecting a valve or contactor coil, check its current, switching rate and suppression arrangement as well as its rated voltage. Short-circuit protection does not permit using a load above the output rating. If a channel LED is on but its actuator does not operate, include the load supply and field wiring in the investigation.
The difference between L1+ and L3+
L1+ supplies the output loads; L3+ supplies the internal electronics and sensors. These two lines are not connected internally. Healthy communication therefore does not establish that output power is present. If every output is inactive, check the power supply at L1+ and L3+ against the appropriate M reference under load, rather than relying on a measurement at the power supply alone.
Terminal block and mechanical matching
Compatible terminal blocks are TB1/DC, TB1-4/DC, TB3/DC and TB3-4/DC. Match the wiring arrangement to the diagram for the installed base. The input and output circuits have no galvanic isolation; the PROFIBUS interface is isolated from the electronics block. Review the common reference arrangement when connecting separate field supplies.
Communication and troubleshooting
PROFIBUS DP supports up to 12 Mbit/s, limited to 1.5 Mbit/s with IM 308-B. BF indicates a bus fault, DIA provides group diagnostics for short circuits or missing load voltage, and L1+ monitors the load supply.
During commissioning, compare the station address and selected device definition with the existing PLC project. If an input LED changes but the corresponding program bit does not, examine I/O addressing and communication first. Record the complete order number, terminal block and existing wiring when selecting a replacement. See the Siemens ET 200 overview for information about the system families.
Editor’s Note: Two checks are particularly useful with this model: calculate the current of all simultaneously active outputs and measure the L1+ load supply separately. Healthy communication with inactive valves does not, by itself, establish an electronics-block fault. Assess a replacement by checking its inputs and outputs individually with the intended circuit loads.
User manuals and PDF documents
Use the Siemens ET 200 manuals and PDF documents page for references. This model appears in Section 7.3.7, pages 7-49–7-54, of ET 200B Distributed I/O Station, EWA 4NEB 812 6089-02c. The model-specific Siemens data sheet dated 16 August 2019 and page 4/12 of the ST 40 catalogue provide additional technical data.
Related topics
Explore other ET 200 options through special input modules, special output modules, analog and interface modules, function modules, counter modules, positioning modules, other network interfaces and additional modules and accessories. These sections cover different ET 200 subfamilies and are not a list of direct substitutes.