6ES7 132-4HB01-0AB0

Siemens Main Menu › SIMATIC S7 › ET 200 Modules

Siemens 6ES7 132-4HB01-0AB0 — ET 200S 2-Channel NO Relay Output Module

6ES7 132-4HB01-0AB0 is an ET 200S relay output module with two normally open contacts in the Siemens ET 200 distributed I/O family. This 15 mm-wide module belongs to the ET 200 digital output range and switches AC or DC loads through mechanical contacts. Its contact type is NO; it is not an NO/NC changeover module.

Module supply and load voltage

The electronics require a 24 V DC potential group. The contact-side load range is specified as 24–120 V DC or 24–230 V AC. Select the ET 200 power supply module for the electronics supply; switching 230 V AC at the contacts does not permit applying 230 V to the module supply. Identify power distribution and potential groups separately in the cabinet drawing.

The 5 A rating depends on the load

The maximum continuous thermal current is 5 A, but switching capacity depends on voltage and load type. For example, Siemens lists 0.2 A for a 120 V DC resistive load. The temperature table specifies 5 A per channel up to 50 °C and 4 A up to 60 °C; also observe the temperature limit for the mounting orientation.

Minimum load current is 8 mA. Maximum switching frequency is 2 Hz for resistive loads and 0.5 Hz for inductive loads. Assess mechanical relay suitability before using repetitive pulse commands. The outputs have no internal short-circuit protection; the manual requires external 6 A fuses. Select suitable external suppression for coil loads according to their characteristics.

Terminal selection and product version

Compatible base examples include TM-E15S24-01 and TM-E15C24-01. Check existing wiring and AUX requirements when selecting ET 200 terminal blocks. Product version also matters when comparing connection modules and terminal arrangements: the Siemens block diagram identifies an internal bridging change from product level 2. Do not rely on appearance alone when replacing an older module.

Five checks before selection

1. Full code and station: Read the 4HB01 order code and product level from the label. Use the ET 200 system and product family guide to confirm ET 200S. A similarly named relay module is not automatically an equivalent replacement.

2. Actual load: Record AC/DC type, running current and inrush current. Contactor coils, lamps and resistive loads impose different demands on contact life. Complete load selection using the manual’s switching-capacity table.

3. Wiring and protection: After safely isolating the supplies, compare contact wiring, bridges and external fuses against the drawing. Remember that contact-side power may remain live independently of the station supply.

4. STOP behaviour: Check hold-last-value and substitute-value settings in the SIMATIC S7 hardware configuration. Verify expected operation during CPU STOP and communication loss through the ET 200 communication interface.

5. Contact testing and delivery: An output LED alone does not prove healthy contacts. During an appropriate test, verify actual load switching and any feedback received through ET 200 digital inputs. The Siemens package contains 5 modules; confirm the quoted quantity for individual or used units.

Editor’s Note

Hearing a relay click does not establish that it carries the load correctly. For intermittent operation under load, examine contact wear, loose connections and inrush current together. Record the complete module code, product level, load type and a photograph of the existing bridge arrangement before replacement.

PDF manuals and wiring: Visit the Siemens ET 200 user manuals and PDF documentation page. In the model-specific A5E01077282-01, 04/2007 manual, pages 7–9 cover terminals and the block diagram, pages 10–11 cover electrical limits, and page 13 covers STOP parameters.