6ES7 131-4BB00-0AA0

6ES7 131-4BB00-0AA0 is a two-channel, 24 V DC Standard digital input module for the Siemens SIMATIC ET 200S distributed I/O system. It transfers switching signals from pushbuttons, limit switches and compatible proximity sensors to the control system. This 15 mm wide electronic module belongs to the ET200 digital input module range.

Device Description

Typical applications include detecting a component in position, reading a pushbutton and monitoring an auxiliary contact. The resulting signal is available to the PLC program. Connected sensors and relay contacts must be wired to suit the electrical characteristics of the inputs.

The product operates as an electronic module within an ET 200S station. Communication with the controller passes through the station's compatible interface module. When selecting a replacement, consider the terminal base, supply group and existing hardware configuration together with the electronic module.

Technical Data

Order number: 6ES7 131-4BB00-0AA0
System / class: SIMATIC ET 200S / 2DI Standard
Digital inputs: 2 channels
Rated supply: 24 V DC from the power module
Signal “0”: -30…+5 V
Signal “1”: +15…+30 V
Input current: Typically 7 mA at 24 V, signal “1”
Input delay: Typically 3 ms in both directions; 2…4.5 ms; not adjustable
Input characteristic: IEC 61131, Type 1
Two-wire sensors: Supported; maximum quiescent current 1.5 mA
Cable length: Maximum 600 m unshielded; 1,000 m shielded
Typical power loss: 0.4 W
Dimensions: 15 × 81 × 52 mm; width × height × depth
Weight: Approximately 35 g per electronic module

The cable lengths are manufacturer limits. Cable cross-section, voltage drop, sensor characteristics and the electromagnetic environment must also be considered for the actual installation.

Terminal Base and Wiring

Field wiring connects to the compatible ET200 terminal base beneath the electronic module. For the TM-E15S24-A1 example shown in the Siemens manual, the assignments are:

Terminal 1: DI0, channel 0 input
Terminal 5: DI1, channel 1 input
Terminals 2 and 6: 24 V DC sensor supply
Terminals 3 and 7: M, 0 V reference
A4 and A8: AUX1; function depends on the terminal base and wiring arrangement

Where AUX1 is used for PE, follow the grounding arrangement in the manual. Additional terminals on different bases should not be assumed to have identical functions. Check the group's PM-E power module, external 24 V DC DIN rail power supply and field sensor cables and connectors as one complete circuit.

Hardware Configuration and Addressing

The two input signals can occupy 2 bits when supported packing is used; the allocated address space without packing is 1 byte. The available arrangement depends on the interface module and configuration method. Compare the configured slot sequence with the physical station, and check the assigned input addresses in the project.

Verify the complete order number in the existing STEP 7 configuration or appropriate device description file. Using PROFIBUS or PROFINET communication does not by itself determine which PLC address represents a particular input.

Status LEDs and Troubleshooting

Each input has a green status LED. This Standard version does not provide channel-level wire-break or sensor short-circuit diagnostics. An unlit input LED alone therefore does not establish that the module is faulty.

The sensor operates but the input does not change: Measure the sensor output against the module's M reference. A sensor indicator confirms activity at the sensor, but does not prove that the signal reaches the terminal base. Check cable continuity, connector contacts and the channel assignment.

The module LED changes but the program value does not: Compare the monitored input address with the hardware configuration and check station communication. Monitoring the wrong address can make a working input appear defective.

Short pulses are missed: Review the pulse duration, input delay and controller sampling cycle together. Applications requiring fast pulse counting should be evaluated against suitable ET200 counter modules.

Commissioning and Editor's Recommendations

Isolate the relevant supply before wiring. Inspect terminal contacts, the module latch and cable identification. After restoring power, operate each channel separately and confirm that the field device, module LED and PLC input value show the same state change.

For intermittent faults, investigate loose terminals, cable movement and supply fluctuations before replacing the module. Clear cable routing and suitable control panel components also make later maintenance easier.

Emergency-stop and protective-door monitoring functions require appropriately selected safety modules and a design based on the application's risk assessment. This product belongs to the Standard digital input class.

Replacement Selection and Scope of Supply

6ES7 131-4BB00-0AA0 is the Standard model, while 6ES7 131-4BB00-0AB0 is the High Feature model. Similar appearance and an identical channel count do not establish equivalent functionality. Compare the full order number, terminal base and configured module before ordering.

The Siemens product description specifies a manufacturer packing unit of five modules. Each electronic module has two inputs. Whether an Otomasyon AVM offer covers an individual module or a complete pack must be confirmed separately. Also verify whether the terminal base and other accessories are included.

Related Topics

For other parts of the station, see ET200 digital output modules, analog input modules, power distribution modules and connection modules.

User Manuals and Technical Documents

+ Siemens ET200 PLC User Manuals — PDF archive page
+ Siemens ET 200S system manual: 6ES7 131-4BB00-0AA0 section — section 12.2; wiring and specifications
+ Siemens 6ES7 131-4BB00-0AA0 technical data sheet — English PDF
+ ET 200S installation and commissioning instructions — system arrangement and addressing
+ Siemens ET200 general product catalogue — range information, not a dedicated manual for this model

Technical sources: Siemens ET 200S, EWA-4NEB780602402-09, 07/2003, section 12.2; Siemens product data sheet dated 15 August 2019; ET 200S Operating Instructions, A5E00515771-06. The Standard and High Feature distinction is also identified in the Siemens module list. Observe the scope and hardware-version information in the relevant documents.

++ Siemens Automation Main Page >
++ Siemens ET200 Products >
++ About Siemens ET200 PLC >
++ Siemens Automation Contact — contact Otomasyon AVM

Reminder: Please confirm current availability, condition and scope of supply for Siemens 6ES7 131-4BB00-0AA0 and other SIMATIC products with Otomasyon AVM. Some devices are used products; take this into account when purchasing. Products will not be restocked once sold out. This page provides general information; the product label, hardware version and applicable manufacturer documentation must govern the actual installation.

Note: Manuals, commissioning suggestions and troubleshooting explanations are provided as non-binding information and may be updated. The Otomasyon AVM Community welcomes practical experience and suggestions. You can share your operating and maintenance observations with us.