6ES7313-5BE00-0AB0
Siemens 6ES7313-5BE00-0AB0 – CPU 313C Compact PLC
6ES7313-5BE00-0AB0 is a Siemens SIMATIC S7-300 CPU 313C with 32 KB of work memory. It combines 24 digital inputs, 16 digital outputs, four analog inputs, a separate Pt100 input and two analog outputs. The CPU uses a 24 V DC supply and provides MPI communication and three fast counters. A SIMATIC Micro Memory Card (MMC) is required for operation. When selecting S7-300 CPU modules, check the complete order number, channel arrangement and project compatibility.
Digital channels and fast counters
The integrated inputs accept 24 V DC digital signals. The outputs support up to 0.5 A per channel, subject to group current and temperature limits. Additional digital input modules and digital output modules can be selected to match the hardware configuration.
Three fast counters support signals up to 30 kHz. Counter functions share terminals with standard digital channels, so check pin assignments and available I/O for the intended application. Encoder or sensor selection should consider signal level, output type, frequency and wiring.
Analog inputs, Pt100 and analog outputs
The analog section provides four voltage/current inputs, one separate Pt100/resistance input and two analog outputs. These should not be treated as five interchangeable general-purpose analog inputs. Connect a Pt100 sensor according to the wiring diagram for its dedicated channel.
Supported voltage/current input ranges include 0–10 V and 4–20 mA; these signals are also available at the analog outputs. Measurement settings, terminal wiring and program scaling must agree. Where additional channels or other sensor types are needed, consider suitable S7-300 analog modules.
The integrated I/O uses two 40-pin front connectors. X1 carries the analog channels and eight digital inputs; X2 carries the remaining 16 digital inputs and 16 digital outputs. During replacement, compare connector positions, channel addresses and field wiring with the existing project.
MPI communication and MMC memory
The MPI interface supports programming and communication with compatible HMI panels. There is no integrated PROFIBUS-DP or PROFINET/Ethernet port. If network expansion is planned, verify communication module compatibility with the exact CPU order number and firmware.
The 32 KB work memory cannot be expanded. The MMC provides load memory; fitting a larger card does not increase work memory. When buying a used unit, check whether the MMC is included and readable. A program left from another machine should not be assumed suitable for the intended application.
Assessing a used CPU
When assessing this CPU among used Siemens products, check MPI access, MMC reading, RUN/STOP transitions and digital channels. Test analog inputs with a suitable signal source, the Pt100 channel with a suitable sensor or simulator, and analog outputs with measuring equipment and an appropriate load. Any fast counters required by the application should also be tested.
Before replacement, back up the STEP 7 project, hardware configuration, data blocks and analog scaling values. Confirm the label photograph, physical condition, test results and delivery contents before ordering. Do not assume that the MMC or both front connectors are included.
Related topics and product groups
S7-300 overview | S7-300 CPU modules | Digital input modules
Digital output modules | Function modules | Analog module range
Used Siemens products | Used equipment overview | OtomasyonAVM home
Manufacturer references
Siemens – 6ES7313-5BE00-0AB0 product information | Siemens – technical data sheet (archive copy) | Siemens – CPU 31xC manual, 10/2001 (archive copy)