6ES7 194-1KB00-0XA0
6ES7 194-1KB00-0XA0 – Siemens PROFIBUS address-setting plug
6ES7 194-1KB00-0XA0 is a Siemens identification and configuration plug for setting the PROFIBUS address. On supported ET 200eco and ET 200X DESINA/ECOFAST hardware, switches inside the plug determine the station address. Check the complete order number, connected device and connection type when selecting the part. See the ET 200 system overview for differences between the families.
ET 200eco and ET 200X applications
On an ET 200eco station using, for example, 6ES7 141-3BH00-0XA0, the plug is used with the 6ES7 194-3AA00-0AA0 ECOFAST terminal block. The 6ES7 194-3AA00-0BA0 version with M12 and 7/8-inch connections uses rotary address switches on the block. Check the complete terminal-block code when identifying the required addressing arrangement.
The ET 200X manual describes the removable configuration plug for BM 143-DESINA and BM 141-ECOFAST basic modules. 6ES7 141-1BF01-0AB0 is an example from the BM 141-ECOFAST family. On these basic modules, the plug is secured through an 8-pin M12 connection.
Address range and switch settings
The valid range depends on the connected device: 1–99 for ET 200eco and 1–125 for the specified ET 200X applications. The plug should therefore not be assigned one universal address limit. Selecting a value above 99 on ET 200eco is indicated by the module’s red bus-error LED.
The seven DIL switches under the cover use binary weights. For example, address 37 is selected by switching the 32 + 4 + 1 weights ON. Read the switch orientation against the marking on the assembly. The address must be unique on the PROFIBUS network and match the station address in the project. See the PROFIBUS FAQ for addressing background.
Commissioning and module replacement
An address change takes effect when the device supply is switched on again. After changing the plug setting, also check the address in the PLC project. When replacing a BM 143-DESINA or BM 141-ECOFAST basic module, retaining the existing serviceable plug avoids having to set its address again. The replacement module type and hardware configuration still require verification.
Functions of connection components
KB00 provides address selection. 6ES7 194-1AA01-0XA0 is an ET 200X connector assembly for PROFIBUS and supply cables; bus termination also uses separate components. When selecting terminal blocks and connection accessories, distinguish address setting, cable connection and bus termination.
Browse ET 200 PROFIBUS and PROFINET for station network types and network interfaces for other connection arrangements. Communication checks should also cover the device supply alongside its address; power supply modules are among the associated system components.
Selecting and checking a used unit
Inspect the body, cover, fastening threads and contacts. Request a test record showing that the switches change position positively and that a suitable device reads the selected address correctly. The record should identify the complete model of the test device. Browse ET 200 additional modules and accessories for other parts.
Editor’s Note: Before replacement, record the old plug’s switch positions and the station address in the project. Do not assume that a replacement plug’s existing setting is correct. A useful check records the selected number, the address read by the device and communication after power is restored, providing more evidence than appearance alone.
Manuals and PDF documents
Find relevant documentation in the Siemens ET 200 manuals section. The English 08/2014 ET 200eco manual covers address setting on pages 17–19 and lists this part on page 98. The 02/2003 ET 200X manual describes plug-based addressing on pages 3-16–3-19 and lists the accessory on page A-4.
Related topics
For the wider system, browse industrial communication, PLC and HMI and Siemens S7-300.
Navigation
Siemens ET 200 | Siemens SIMATIC S7 | Siemens automation | OtomasyonAVM home